ML17342A893: Difference between revisions

From kanterella
Jump to navigation Jump to search
(Created page by program invented by StriderTol)
(Created page by program invented by StriderTol)
Line 3: Line 3:
| issue date = 09/08/1987
| issue date = 09/08/1987
| title = Special Rept:On 860930 & 1001,schedular Exemptions for Safe Shutdown Mods Expired Due to Large Number of Mods Being Performed.Plant Continues to Implement Compensatory Measures as Applicable.Rept Will Be Updated on 30-day Basis
| title = Special Rept:On 860930 & 1001,schedular Exemptions for Safe Shutdown Mods Expired Due to Large Number of Mods Being Performed.Plant Continues to Implement Compensatory Measures as Applicable.Rept Will Be Updated on 30-day Basis
| author name = WOODY C O
| author name = Woody C
| author affiliation = FLORIDA POWER & LIGHT CO.
| author affiliation = FLORIDA POWER & LIGHT CO.
| addressee name =  
| addressee name =  

Revision as of 11:35, 18 June 2019

Special Rept:On 860930 & 1001,schedular Exemptions for Safe Shutdown Mods Expired Due to Large Number of Mods Being Performed.Plant Continues to Implement Compensatory Measures as Applicable.Rept Will Be Updated on 30-day Basis
ML17342A893
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 09/08/1987
From: Woody C
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
L-87-372, NUDOCS 8709110279
Download: ML17342A893 (5)


Text

ACCESSION NBR FAC IL: 50-250 50-251 AUTH.NAME WOODY>C.O.RECIP.NAME REGULATORY IFORMATION DISTRIBUTION SY M (RIDS)870110279 DOC.DATE: 87/09/08 NOTARIZED:

NO Turkey Point Planti Unit 3i Florida Poeer and Light C Turkey Point Plant.Unit 4i Florida Power and Light C AUTHOR AFFILIATION Florida Power h-Light Co.RECIP I ENT AFFILIATION Document Control Branch (Document Control Desk)DOCKET 05000250 05000251

SUBJECT:

Special rept: on 860930 h 1001I schedular exemptions for safe shutdoen mods expired due to large number of mods being performed.

Plant continues to implement compensatorg measures as applicable.

Rept mill be updated on 30-day basis.DISTRIBUTION CODE: IE22D.COPIES RECEIVED: LTR I ENCL+SIZE: TITLE: 50.73 Licensee Event Report (LER)i Incident Rpt.etc.NOTES: REC IP IENT ID CODE/NAME PD2-2 LA McDONALDi D INTERNAL: ACRS MICHELSON AEOD/DOA AEOD/DSP/ROAB DEDRO NRR/DEST/CEB NRR/DEST/I CSB NRR/DEST/MTB NRR/DEST/RSB NRR/DLPG/HFB NRR/DOEA/EAB NR E PB~LE 02 ORD)J RQN2 FILE 01 EXTERNAL: EGS<G GROH>M LPDR NSIC HARRISI J COPIES LTTR ENCL 1 1 1'1 1 1 2 2 1 1 1 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1 5 5 1 1 1 REC IP IENT ID CODE/NAME PD2-2 PD ACRS MOELLER AEOD/DSP/NAS AEOD/DSP/TP*B NRR/DEST/ADS NRR/DEST/ELB NRR/DEST/MEB NRR/DEST/PSB NRR/DEST/SQB NRR/DLPG/GAB NRR/DREP/RAB NRR/PMAS/ILRB RES DEPY QI RES/DE/EIB H ST LOBBY WARD NRC PDR NSIC MAYSI Q COPIES LTTR ENCL 1 1 2 2 1 1 1 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 TOTAL NUMBER OF COPIES REQUIRED: LTTR 43 ENCL 42 P.O.B 000, JUNO BEACH, f.L 33408 0420 SEPTEMBER 0 8 IS87 L-87-372 U.S.Nuclear Regulatory Commission A t tn: Documen t Control Desk Washington, D.C.20555 Gentlemen:

Re: Turkey Point Units 3 and 4 Docket Nos.50-250 and 50-25 I Special Report-Breached Fire Barriers and Other Fire Protection S stem lm airments In accordance with Technical Specification 6.9.3 the attached Special Report is provided for your information.

Should there be any questions on this information, please contact us.Very truly yours, C.O.Woody Group Vice resident Nuclear Energy COW/SDF/gp At tachrnent cc: Dr.J.Nelson Grace, Regional Administrator, Region II, USNRC Senior Resident Inspector, USNRC, Turkey Point Plant 8709fi0279'70908 PDR ADOCK 05000250 8 PDR SDF I/004/I gZ+an FPL Group company SPECIAL REPORT SEPTEMBER 8, 1987 FIRE PROTECTION SYSTEM IMPAIRMENTS REQUIRING NRC NOTIFICATION

~Pur eee: Technical Specification (TS)3.14.5.b requires the submission of a report to the NRC if a non-functional fire barrier penetration is not returned to functional status within 7 days.TS 3.14 states that certain other conditions also require NRC notification.

In accordance with the above requirements, this special report is being generated in order to notify the NRC.This report will be updated on a 30 day basis.Event: The plant has been and is continuing to implement modifications in accordance with Appendix R Alternate Shutdown requirements and other unrelated requirements.

The schedular exemptions for the Safe Shutdown modifications, which outlined the alternative compensatory measures to be taken when a barrier is breached, expired on September 30, 1986, and on October 1, 1986.Upon the expiration of the exemptions, the compensatory measures as described in Attachment 1 of our letter L-85-386 (dated October ll, 1985), are continuing to be in place until the Safe Shutdown modific'ations are complete.Impairments incurred during Alternate Shutdown modifications are governed by the Technical Specifications or the exemptions, as applicable.

Other impairments are governed strictly by the Technical Specifications.

Cause and Corrective Actions: The ma)or cause of the impairments is the large number of modifications being performed.

Due to the large volume of work being performed, the plant is reporting the impairments in this one report, rather than on a case-by-case basis.The impairments reported this month are either open or closed at the present time, but were open in excess of the time period permitted without requiring NRC notification (see lists on page 3).This report includes impairments which were: 1)opened prior to September and 2)stayed open for longer than the time permitted by the Technical Specifications, and 3)are either still open or were closed prior to September.

The plant continues to implement the compensatory measures as applicable.

FIRE PROTECTION SYSTEM IMPAl NTS OPENED SINCE JULY REPORT CH HAVE BEEN OPEN FOR LONGER THAN TECH SPEC LIMITS Imp//1150 1168 1046 1160 1161 87-0326 87-0323 87-0324 87-0325 Description Water Suppression System PTS 41&42 Fire Door 106.2 Conduit Seal Conduit Seal Fire Detection System Penetration Seal 097F"E014 Penetration Seal 106F-E368 R.P.A384-30-0181-3271 Open 08/06/87 08/18/87 07/24/87.08/14/87 08/14/87 07/30/87 07/30/87 07/30/87 07/30/87 Closed 08/11/87 08/26/87 08/26/87 08/14/87 FIRE PROTECTION SYSTEM IMPAIRMENTS CLOSED SINCE JULY REPORT BUT WERE OPEN FOR LONGER THAN TECH SPEC LIMITS Impt 1034 1071 87-0251 87-0314 87-0156 87-0290 87-0291 87-0293.87-0300 1089 1115 87-0154 87-0155 87-0156 87-0157 Description Fire Damper 72A Fire Barrier Thermal Lagging Penetration Seal 70C-E007 Raceway Protection Conduit Seal 106E-E015 Penetration Seal 30F-M003 Penetration Seal 30F-M046 Fire Door Elec.Penet.019.1 Penetration Seal 28E-H001 Fire Door 106.1 Fire Barrier Conduit Seal 70E-E008 Conduit Seal 71E-E007 Conduit Seal 106E-E015 Conduit Seal 1084E-E003 Open 01/28/87 04/02/87 05/05/87 07/07/87 03/14/87 06/12/87 06/12/87 06/15/87 06/09/87 05/08/87 06/21/87 03/14/87 03/14/87 03/14/87 03/14/87 Closed 08/11/87 08/25/87 08/14/87 08/17/87 07/10/87 07/10/87 07/10/87 07/31/87 07/10/87 07/13/87 07/09/87 07/24/87 07/24/87 07/10/87 07/10/87 A;4 4i~A.The following impairments were incurred prior to August 1987, owever they are being included in this report as they were not reported previously.

Imp8 87-0316 87-0317 Description Open Penetration Seal 067N-E003 07/16/87 Penetration Seal 068E-E002 07/16/87 Closed 07/24/87 07/24/87 3,