TURKEY POINT PLANT UNIT 4 1999 REFUELING OUTAGE INSERVICE INSPECTION REPORT This Inservice Inspection report is for the 1999 Turkey Point Unit 4 refueling outage. This was the second outage of the second period in the third ten-year interval.

The attached Inservice Inspection summary tables detail the examinations performed during the outage.

The attached NIS-2 forms document the repairs and replacement activities which have taken place since the previous Unit 4 submittal, as well as those performed during the 1999 refueling outage.

Inservice examinations completed during this outage:

Augmented Feedwater ultrasonic examinations were performed on the A, B, and C Steam Generator Feedwater nozzles, adjacent piping, and fittings.

Accessible Reactor Vessel internal surfaces and the RPV flange surface were visually examined.

Also examined were selected components from the Reactor Coolant, Residual Heat Removal, Safety Injection, Steam Generator Blowdown, Component Cooling Water, and Chemical and Volume Control systems.

Visual examination and functional testing of snubbers was performed in accordance with ASME Section XI, as modified by Relief Request No. 4, and Plant Technical Specifications.

System pressure testing was performed on Quality Group A, B, and C piping and components.

There were no eddy current examinations of Steam Generator tubes scheduled for this outage.

The examinations performed exceed the minimum requirements for ISI examinations for this period.

9907080068 990630 PDR ADOCK 05000251 8 PDR

Turkey Point Unit 4 1999 Refueling Outage Form NIS-1 Owners'ata Report for Inservice Inspections

0

0 FORM NIS-1 OWNERS'ATA REPORT FOR INSERVICE INSPECTIONS Page 1 of 6 Owner: Florida Power & Light Company 700 Universe Blvd.

Juno Beach, Florida 33408

2. Plant: Florida Power & Light Company Turkey Point Nuclear Power Plant 9760 SW 344 Street Florida City, Florida 33035
3. Plant Unit:~
4. Owner Certificate of Authorization (if recpxired)
5. Commercial Service Date
6. National Board Number for Unit:
7. Components Inspected:

Component or Manufacturer Manufacturer State or Nat'l Appurtenance or Installer or Installer Province Board Serial No. No. No.

Reactor Pressure Babcock and 610-0116 N/A N-161 Vessel Wilcox 4PSRV1 Regenerative Heat Westinghouse 4E200 N/A N/A Exchanger Reactor Coolant Bechtel N/A N/A N/A System Safety Injection Bechtel N/A N/A N/A System Chemical and Volume Bechtel N/A N/A Control System S/G Blowdown System Bechtel N/A N/A N/A Component Cooling Bechtel N/A N/A N/A Water System RHR System Bechtel N/A N/A N/A Main Feedwater Bechtel N/A N/A N/A System

h NIS-1 Report (continued)

1. Owner. Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408
2. Plant: Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035
3. Plant: Unit 4
4. Owner Certificate of Authorization (if required) N/A 5.
6. National board Number for Unit: N/A
8. Examination Dates: From
9. Inspection Period Identification  : Second Period QAI15C87-
10. Inspection Interval Identification: Third Interval,
11. Applicable Edition of Section ZI 'LB'ddenda~one
12. Date/Revision of Inspection Plan:
13. Abstract of examinations and test.

Inservice examinations of selected Class 1, 2, and 3 components and piping systems of Florida Power and Light's (FPL) Turkey Point Unit 4 were performed during the 1999 refueling outage. This outage was the second outage of the second period in the third ten-year interval. The 1999 outage began on March 15, 1999 and ended on April 7, 1999.

The components and piping systems examined were selected in accordance with the Third Ten-Year Inservice Inspection Program, which was prepared in accordance with the requirements of the American Society of Mechanical Engineers (ASME) Section XI, 1989 Edition.

Ultrasonic, visual, magnetic particle, and liquid penetrant nondestructive techniques were used to examine components, piping, and their supports. The examinations were performed to FPL NDE procedures, and supported by examiners supplied by Raytheon Engineers 8 Constructors (Raytheon). See the attached report: Inservi ce Inspection Summary for examination scope and results.

There were no Steam Generator tube eddy current examinations scheduled for this outage.

Snubber functional testing and visual examinations were conducted in accordance with ASME Section XI and Turkey Point Plant Technical Specifications as allowed under Relief Request number 4. Visual examination and functional testing services were supplied by Basic-PSA, Inc. See the attached report: Summary of Visual Examinations and Functional Testing of Snubbers for examination scope and results.

NIS-1 Report (continued)

1. Owner: Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408
2. Plant: Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035
3. Plant: Unit 4
4. Owner Certificate of Authorization (if required) N/A 5.
6. National board Number for Unit: N/A System pressure testing was conducted by FPL and Raytheon visual examiners to ASME Section XI and applicable plant procedures. See the attached report: Summary of System Pressure Testing for test boundaries and results.

Approximately one-third of the scheduled examinations for the second period were completed during this refueling outage. The remainder of the second period examinations are scheduled for completion during the next refueling outage.

This meets or exceeds the requirements of Program B of ASME Section XI and applicable relief requests.

14. Abstract of Results of Examinations and Tests.

Class 1 Reactor Pressure Vessel A B-N-1 Interior of Reactor Vessel examination was performed. There were no reportable indications noted.

Re enerative Heat Exchan er A VT-3 visual examination was performed near the beginning of the outage to examine for boric acid crystal accumulation and evidence of leakage. A VT-2 visual examination was performed during the system leakage test prior to startup to examine for evidence of leakage. There was no reportable leakage or indications noted.

Reactor Coolant S stem A support on the Pressurizer Surge line (SR-400) was re-examined per CRN 97-1560. During the re-exam, the support was found to have a loose U-bolt and inadequate thread engagement(See section 15, Abstract of Corrective Measures).

Other exams included Pressurizer Spray piping welds and one additional support using surface, volumetric, and visual techniques. There were no further reportable indications noted.

NlS-1 Report (continued)

1. Owner. Florida Power tt Light Company, 700 Universe Blvd. Juno Beach, Florida 334p8
2. Plant: Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33p35
3. Plant: Unit 4
4. Owner Certificate of Authorization (if required) N/A 5.
6. National board Number for Unit: N/A Safet In'ection S stem Safety Injection piping welds and supports were examined using volumetric, 'surface and visual techniques. There were no reportable indications noted.

Residual Heat Removal S stem Residual Heat Removal piping welds and supports were examined using surface, volumetric and visual techniques.

There were no reportable indications noted.

Chemical and Volume Control S stem Chemical and Volume Control piping welds were examined using liquid penetrant. Piping supports, components and pressure retaining bolting were examined with visual techniques. Two restraints were found to have improper clearances (See section 15, Abstract of Corrective Measures). On two welds, rejectable linear indications were recorded (See section 15, Abstract of Corrective Measures). There were no further reportable indications noted.

Class 2 Main Peedwater S stem Augmented ultrasonic examinations were performed on areas from the Steam Generator nozzle ramp out to a point of one pipe diameter on the upstream elbow, on each of the three main Feedwater lines. A previously recorded acceptable slag inclusion was noted during the exams. There were no reportable indications noted.

Steam Generator Blowdown S stem Magnetic particle and visual examinations were performed on two Blowdown system supports with integral attachments.

There were no reportable indications noted.

0 NIS-1 Report (continued) 1.. Owner. Florida Power 8 Light Company, 700 Universe Blvd. Juno Beach, Florida 33408

2. Plant: Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035
3. Plant: Unit 4
4. Owner Certificate of Authorization (if required) N/A
6. National board Number for Unit: N/A Class 3 Com onent Coolin Water S stem Visual exams were performed on anchors, restraints and welded attachments. On two supports, inadequate thread engagement was recorded (See section 15, Abstract of Corrective Measures).
15. Abstract of Corrective Measures Inadequate thread engagement and a loose U-bolt were found during a VT-3 exam of RCS support SR-400. The U-bolt was tightened, and the inadequate thread engagement was evaluated to be operable as-is per CRg 99-359.

A rejectable linear indication in the base material adjacent to CVCS weld 3-CH-1401-4 was recorded during a PT exam. The indication was removed, and the indication removal area was re-examined by PT and a UT thickness verification per CRg 99-425.

A rejectable linear indication in the toe of the integral attachment weld on CVCS support SR-934 IA was recorded during a PT exam. The indication was reduced to two acceptable linear indications following grinding, and was re-examined by PT per CRN 99-426.

Improper clearance between the U-bolt and pipe was found during a VT-3 exam of CVCS support 779D. The U-bolt was adjusted, and the support was re-examined per CRN 99-427.

Improper clearance between the U-bolt and pipe was found duri.'ng a VT-3 exam of CVCS support 4-VCH-63. The condition was evaluated as operable as-is per CRN 99-427.

Inadequate thread engagement was observed during a VT-3 exam of CCW anchor SR-688. The condition was evaluated as operable as-is per CRN 99-351.

Inadequate thread engagement and missing grout was observed during a VT-3 exam of CCW restraint SR-708. The grout was repaired and the inadequate thread engagement was evaluated to be operable as-is per CRN 99-351.

II I

NIS-1 Report (continued)

1. Owner. Florida Power & Light Company, 700 Universe Blvd. Juno Beach, Florida 33408
2. Plant: Turkey Point Nuclear Power Plant, 9760 SW 344 Street, Florida City, Florida 33035
3. Plant: Unit 4
4. Owner Certificate of Authorization (if required) N/A 5.
6. National board Number for Unit: N/A We certify that a) the statements made in this report are correct, b) the examinations and tests meet the Inspection Plan as required by the ASME Code,Section XI, and c) corrective measures taken conform to the rules of the ASME Code,Section XI.

Certificate of Authorization No. N A Expiration Date N A Date: W dg Signed: By PS'~z'.

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the State or Province of Dade County, Florida, and employed by Arkwright Mutual Insurance Company of Norwood, Massachusetts, have inspected the components described in this Owner's Report during the period 03/15/99 to 04/7/99, and state that to the best of my knowledge and belief, the Owner has performed examinations and tests and taken corrective measures described in the Owner's Data Report in accordance with the Inspection Plan and as rec(uired by the ASME Code,Section XI.

By signing this certificate, neither the inspector nor his employer makes any warranty, expressed or implied, concerning the examinations, tests, and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

3o N)(Z)

I spectorature National Board, State, Province, and Endorsements Date:

0 TURKEY POINT UNIT 4 1999 REFUELING OUTAGE Form NIS-2 Owners'ata Report of Repairs and Replacements

0 Abstract The attached NIS-2 reports detail the repair/replacement of Class 1, 2 and 3 piping and components for Florida Power and Light Company, Turkey Point Unit 4. These repairs or replacements were performed prior to and during the 1999 Unit 4 Spring refueling outage, which occurred between the dates of March 15, 1999 and April 7, 1999.

Piping and components were inspected/tested in accordance with Section XI of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code "Rules for Inservice Inspection of Nuclear Power Components," 1989 Edition with no addenda. For repair and replacement activities that utilized Code Case N-416-1, as allowed under Relief Request 16*, use of the Code Case has been documented on the NIS-2 forms.

  • Relief Request 16 was authorized for use under TAC Numbers M94326 and M94327.

Re ortNo. Date 98-001-4 02/02/98 98-002-4 02/02/98 98-003-4 02/02/98 98-004-4 02/02/98 98-005-4 02/09/98 98-006-4 02/27/98 98-007-4 08/03/98 98-008-4 10/07/98 98-009-4 12/09/98 99-001-4 01/05/99 99-002-4 02/17/99 99-003-4 02/11/99 99-004-4 02/17/99 99-005-4 02/17/99 99-006-4 02/24/99 99-007-4 03/22/99 99-008-4 03/25/99 99-009-4 03/29/99 99-010-4 03/31/99 99-011-4 04/03/99 99-012-4 04/02/99 99-013-4 04/02/99 99-014-4 04/02/99 99-015-4 04/03/99 99-016-4 04/03/99 99-017-4 04/03/99 99-018-4 04/07/99 99-019-4 04/07/99 99-020-4 04/07/99 99-021-4 04/07/99 99-022-4 04/07/99 99-023-4 04/09/99 99-024-4 04/09/99 99-025-4 04/09/99 99-026-4 04/14/99 99-027-4 04/14/99 99-028-4 04/14/99 99-029-4 04/14/99 99-030-4 04/28/99 99-031-4 05/03/99 99-032-4 05/03/99 99-033-4 05/03/99

Re ortNo. Date 99-034-4 05/24/99 99-035-4 05/24/99 99-036-4 05/25/99

FORH NlS 2 OMNERS REPORT FOR REPAlRS OR REPLACENENTS As Required by the Provisions of the ASHE Code Section Xl

1. (hrner Florfda Paver S Lf ht Date 02 02 98 700 Universe Blvd. Jum Beach Fl. 33408 Sheet 1 of 2 Address
2. Plant Turke Point Plant Uni t PMO Nr64/3369 MO Nr 97016181 9760 SM 344 Street Florfda Cft Fl. 33035 Address Repair Organfzatfon P.O. No.,Job No.,etc
3. Mork Performed by Florida Porrer 8 Li ht Type Code Symbol Stoa@ N A Name Authorization No. N A Expfratfon Date N A 9760 SM 344 Street Florida Cft FL. 33035 Address
4. identification of System: Intake Coolfn Mater S tern System fft 19 Duality Group: C
5. (a) Applicable Construction Code 831.1 1955 Edition, NA Addenda,~NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition,~NA Addenda,~NA Code Case
6. identification of Corrponents Repaired or Replaced and Replacement Corponents Name of iHanufncturer[ National i Other iYear i Repnfred i ASNE i Nnnufacturar .) Serial No. Board identification JBuflti Replaced or i Code i i Replacement istenp J I I Jr~et Ne iXJ 4 1406 IN/A (N/A IEXPANSfON JolNT iUNK /Replacement /No STOCK C(IE 0014195-1
7. Description of Mork: REPLACE EXPANSlON JOlNT XJ-4-1406 SYSTEN LEAKAGE TEST PERFORNED UNDER 04-1CM.1956.L.03.
8. Tests Conducted: Hydrostatics Pnerzrrat 1 c t Neuinel uperetlng pressure N Pressure~16 ig Test Tesgereture 79 4F Other VT-2 98-001.4

Sheet 2 of 2 FORH NIS.2 (Back)

9. Remarks: HECHANICAL JOINT NO NELDING REQUIRED.

CERTIFICATE OF CONPLIANCE

'e certify that the statements made in the report are correct and this replacement conforaa to the rules of the ASKE Code, Section XI.

Type Code Syahol Stamp N A Certificate of Aythorization No. N A Expiration Date N A Signed ~ Date OMner or Ow>>r's esignee, it e CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid comnission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and employed by Arkur3ght Nutual Insurance Company of Norwood, Na. have inspected the component% described in this Qners Report during the period 07/09/97 to 02/02/98 and state that to the best of my knowledge and belief, the Oner has performed examinations and taken corrective measures described in this OMners Report in accordance Mith the requirements of the ASHE Code, Section Xl.

By signing this certificate neither the Inspector nor his employer makes any Narranty, expressed or implied, concerning the examinations and corrective measures described in this Ouner's Report. Furthermore,'either the Inspector nor his eaployer shall be Liable in any manner for any personal injury or property damage or a Loss of any kind arising from or connected uith this inspection. I Caanissi ons NB 8230 N I Ins tora gnature National Board, State, Providence, and Endorsements Oat~

98.001-4

FORH NIS 2 OMNERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the Provisions of the ASHE Code Section XI

1. Owmr Florida Poser t Li ht Date 02 02 98 700 Universe Blvd. Jwe Beach Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Unit 4 PMO ¹:64/3516 MO ¹: 97016183 9760 SM 344 Street Florida Cit Fl. 33035 Address Repair Organization P.O. No.,Job No.,etc
3. Mork Performed by Florida PoMer B Li ht Type Code Symbol StaJJJJp N A Hame Authorization No. N A Expiration Date N A 9760 SM 344 Street Florida Cit FL. 33035 Address
4. Identification of System: Intake Coolin Mater S stem System ¹I 19 aual I ty Group: c 5~ (a) Applicable Construction Code 831.1 1955 Edi tion, NA Addenda,~NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition,~NA Addenda,~NA Code Case
6. Identification of Cceponents Repaired or Replaced and Replacement CJJJponents Name of Name of iHanufacturer National i Other iYear I Repaired I ASHE I CaJJponent 'anufacturer .

i Serial No. Board Identification iBuilti Replaced or i Code i i Replacement istaJ8p i I I J~Ves rte iPUHP 4P9A iJOHNSTON iH/A iN/A I4P9A IST 4 i N/A i Replaced i No I

IPUHP 4P9A iJOHNSTON IN/A IN/A I P A IST iH/A iReplacement iHo

7. Description of Morkt REPLACE 4A IST-4 ICM PUHP MITH SPARE PIMP IST-5 .

SYSTEH LEAKAGE TEST PERFORHED UNDER 04-1CM.1956-L.03.

8. Tests tendueted: tiydrestatie: Pnmmet is: gtminai Operating Pressure n Test Tmnerature 4F Other VT-2 pressure~16 ig 98.002-4

Sheet 2 of 2 FORH NIS-2 (Back)

9. Remarks: NECHANICAL CONNECTION NO WELDING REOUIRED.

CERTIFICATE OF CONPLIANCE Me certify that the statements made in the report are correct and this replacement conforms to the rules of the ASIDE Code, Section Xl.

Type Code Syahol Stamp N A Certificate of Autho isation No. N A Expiration Date N A Signed Date or r's Desig, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid cocmission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade County and employed by Arkwright Nutual Insurance Company of Norwood, Na. have inspected the components described in this Owners Report during the period 11/06/97 to 02/02/98 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASNE Code,Section XI.

By signing this certificate neither the Inspector nor his eaployer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermoreg neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comni ssi one NB BP30 N I tora ignature National Board, State, Providence, and Endorsements l~ 19%

98-002-4

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by ths Provisions of the ASME Code Section Xl

. Owner Rorids Power & Ught Date 2/2/98 700 Universe Blvd. Juno Beach, FL 33408 Sheet of

2. Plant Turks Point Plant Unit WO¹: 96030768 01 CR¹:

9760 SW 344 Street Rorlda City, FL 33035 RSPnir OrannlZS5On, P.O. NO, JOt9 NCe, etC.

3. Work Performed by Rorida Power & U ht Type Code Symbol Stamp NIA Authorization Number N/A 9760 SW 344 Street Rorida City, FL 33035 Expiration Date NIA
4. Identification of System: Intake Coclin Water S tern Systom ¹: 19 Quality Group
5. (a) Applicable Construction Code B31.1 1955 Edition, tt/A Addenda, ///A Code Case lb) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Manufacturer ational Other Year Replaced, or Stamp Component Manufacturer Serial Number Board Identification Built Roplacomsmt Yes/No 4-50-410 STRATA FLOW NIA NIA CHECK VALVE UNK REPLACEMENT NO STOCK CODE 0052450-2
7. Description of Work:

REPLACED EXISTING CHECK VAI.VE 4-50-410 WITH SPARE. LEAKAGE TEST PERFORMED UNDER PRESSURE TEST 04.ICW-1955-F.02.

. Tests Conducted: Pressure Pneumatic Nominal Operating Pressure X Other VT-2 Pressure 13.5 pslg Test Temperature 78 deg F 98.003-4

Sheet 2 of 2 FORM NIS-2 (Back)

MECHANICALCONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certifiy that the statements made in the report sre correct and this REPLACEMENT conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of horization No. N/A Expiration Date: N/A Signed Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Dade County and employed by Arkwright Mutual Insurance Company of Norwood, Ma. have inspected the components described in this Owners Report during the period of 11/22/96to 2/2/98 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners'eport in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners'eport. Furthermore, neither the Inspector nor his employer shell be liable in any mannor for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions Ins ctor'gnature Notional Board, State, Providence, end Endoreemente 98.003-4

FORH NIS-2 OMNERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the Provisions of the AQlE Code Section XI

1. oner Florida Poser S Li ht Oate 02 02 98 Name 700 Universe Blvd. Jwm Beach Fl. 33408 Sheet 1 of 2 Address 2 P lant Turke Point Plant Uni t Plo ¹:69/6167 MO ¹: 97026548 CR ¹: 96-1374 9760 SM 344 Street Florida Cit Fl. 33035 Address Repair Organization P.O. No.,Job No.,etc
3. Mork Performed by Florida PoMer S Li ht Type Coda Symbol Stamp N A Name Authorization No. H A Expiration Oats N A 9760 SM 344 Street Florida Cit FL. 33035 Address
4. Identification of System: Intake Coolin Mater S tern System ¹: 19 Ouality Group: C
5. (a) Applicable Construction Code B31.1 1955 Edition, NA Addenda,~NA Code Case

<b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition,~NA Addenda,~NA Code Case

6. Identification of CoJJJponents Repaired or Replaced and Replacement Components Name of Carponent

'ame of

'Hanufacturer (Nanufacturer( National

( Serial No. Board

(

Other I dent I f I cat i on (Year (Built(

(

Repaired ( ASNE Replaced or ( Code Replacement (Staap

(

(

I (

I I Jt~es So H/A IH/A IH/A I ICM PIPE SUPPORT (UHK (Repaired (Ho

7. Description of Mork: HMIFY SUPPORT ¹3 TO EXCLUOE MATER INTRUSION.
8. Ysoto COIIUUCtod: IIYU t ti t: soOCPfhuootiC: llclllillsi Ohotstihs PCCCCUI'o Other VT-3 98-004-4

Sheet 2 of 2-FORH NIS 2 (Back)

9. Remarks: ALL NELOING PERFORHEO IN ACCORDANCE NITN APPROVEO PLANT PROCEDURES.

CERTIFICATE OF CCSIPLIANCE Ne certify that the statements made in the report are correct and this repair conforms to the rules of the ASHE Code, Section XI.

Type Code Syahol Stamp N A Certificate of Authoris tion No. N A Expiration Date N A Signed Pk+ Date 19 ~+

amer o thner's signee, it e I

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid coamission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade County and employed by Arkuright Hutwl Insurance Carpany of NorMood, Ha. have inspected the coeponents described in this O>>>>rs Report during the period 12/02/97 to 02/02/98 and state that to the best of my knouledge and belief, the oner has performed examinations and taken corrective s>>asures described in this Owners Report in accordance Nith the requirements of the ASHE Code,Section XI.

By signing this certificate neither the Inspector nor his eapioyer makes any Marranty, expressed or implied, concerning the examinations and,corrective measures described in this Ow>>r's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected Nith this inspection.

Cocmissions NB 8230 N I nspect rs gnature National Board, State, Providence, and Endorsements Oat V 19 FP 98-004-4

FORH NIS 2 OWERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the Provisions of the ASHE Code Section XI

1. Owner Florida Power C Li t Date 02 09 98 700 Universe Blvd. Jun Beach Fl. 33408 Sheet 1 of 2
2. Plant Turke Point Plant Unit 4 PNO N:64/3370 QO 0t 97016182 9760 SJJ 344 street Florida Cit Fl.* 33035 Address Repair Organization P.O. No.,Job No.,etc
3. Mork Performed by Florida Power C Li ht Type Code SysJbol StaaJp N A N~ Authorization No. N A Expiration Oate N A 9760 Su 344 Street Florida Cit FL. 33035 Address
4. Identification of System: Intake Cool i Nater tesa System 0: 19 Ouali ty Group: C
5. (a) Applicable Construction Code 831.1 1955 Edition, NA Addenda,~NA Code Case (b) Applicable Edition of Section XI Utilized for Repairs or ReplacesJents 1989 Edition,~NA Addenda,~NA Code Case
6. Identif ication of Components Repaired or Replaced and ReplaceJaent CoJJJponents NeJse of N~ of ]Hanufactur'er Naticnal Other [Year i Repaired .

f ASHE )

CIJJponent Halfacturer Serial Noe Board I dent I f ication iBuilti Replaced or i Code i i Replacement )Stamp i I J~Yes No 14 50 311 I HARL IN i 100257 N/A iSTOCK CNE 0052545.2 UNK iReplacement iNo UTC 0000405011

7. Oescription of Morkt REPLACE CHEN VALVE 4-50-311 SYSTEH LEAXAGE TEST PERFORHED UNOER 04.1CMo1956.L.03.

S. Tests Conducted: Nrdroststtc: Prucdstic: Ncutnst Cperettno Pressure N Pressure~f6 Test Tespersture 79 'F Other VT-2 TN 98.005-4

Sheet 2 of 2 FORH NIS.2 (Back)

9. Remarks: HECMANICAL CONNECTION NO QELDING REQUIRED.

CERTIFICATE OF CSLPL LANCE lie certify that the statements made in the report are correct and this replacement conforms to the rules of the ASHE Code, Section XI.

Type Code Symbol Steap Certificate o Authori ation No. K A Expiration Date N A S~,neet Qner or OMne 's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid cmaission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and employed by Arkuright Hutual Insurance Cocpany of Norwood, Ha. have inspected the cceponents described in this (hners Report during the period 07/09/97 to 02/09/98 and state that to the best of my knouledge and belief, the Ouner has performed examinations and taken corrective measures described in this Owners Report in accordance uith the requirements of the ASHE Code,Section XI ~

By signing this certificate neither the Inspector nor his employer makes any uarranty, expressed or is@lied, concerning the exeainations and corrective measures described in this Ower's Report. Furthermore, neither the Inspector nor his employer shall be Liable in any abner for any personaL injury or property damage or a Loss of any kind arising fraa or corrected Hith this inspection.

Caasissions NB 8230 N I Ins to S i gnature National Board, State, Providence, and Endorsements Da J/ 195 98.005-4

FORH NIS-2 OMNERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the Provisions of the ASHE Code Section XI

1. Owner Florida Power 8 Li ht Date 02 27 98 700 Universe Blvd. J~ Beach Fl. 33408 Sheet of 2 Address 2~ Plant Turke Point Plant Unit 4 PMo <<t 63/74O2 Mo Ot 98O04133 02 9760 SM 344 Street Florida Cit Fl. 33035 Address Repair Organisation P.o. No.,Job No.,etc

~ Mork Performed by Florida Power 8 Li ht Type Code Symbol Stamp N A Authorization No. N A Expiration Date N A 9760 SM 344 Street Florida Cit FL. 33035 Address

4. Identification of System: Emer enc Feedwater S stem System 0t 75 Duality Group: C
5. (a) Applicable Construction Code 831.1 1955 Edftfon,~NA Addenda,~ca Code Case lb) Applicable Edition of section xi Utilized for Repairs or Replacements 1959 Edltfcn,~ca Addenda,cascade cess
6. Identifi'cation of Components Repaired or Replaced and Replacement Coeponents Name of Name of iHanufac'turel'.Serial Nat'Ional other iYear i Repaired i ASHE i CaJJponent .Hanufacturer No'. Board Identification iBuilti Replaced or i Code i i Replacement,isterp i I Jatos No I

I4-YPN-39 N/A iN/A N/A IAFM PIPING SUPPORT iN/A iReplaced iNo

. Description of Mork: REPLACED PIPE CLAHP ASSEHBLY UTCH 334081 ON SUPPORT 4-YPN-39.

Teste Conducted: Nrdrostatlc: Pnculmtltc: Ncmlnal Uperstins Pressure VT-3 NA 'F Other 98-006-4

Sheet 2 of 2 FORH NIS-2 (Back)

9. Remarks: HECHANICAL CONNECTION NO WELDING REQUIRED.

CERT IF I CATE OF COHPLI ANCE Me certify that the statements made 3n the report are correct and this replacement conforms to the rules of the ASHE Code, Section Xl.

Type Code Synhol Stamp N A Certificate o Authori ation No. N A Expiration Date N A Signed Owner r Ouneris Oes , Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid coemission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and employed by Arkuright Hutual insurance Coapany of Norwxxf, Ha. have inspected the conponents described in this Oaers Report during the period 02/19/98 to 02/23/98 and state that to the best of my lmwledge and belief, the Iver has performed examinations and taken corrective measures described in this Owers Report in accordance Hith the requirements of the ASHE Code, Section Xl.

By signing this certificate neither the Inspector nor his eayloyer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Amer's Report. Furthermore, neither the Inspector nor his employer shall be liable in any mercer for any personal Injury or property damage or a loss of any kind arising from or connected ulth this inspection.

Oat lns ors gnature FS'8 Coamlssions NB 8230 N I National Board/ State, Providence, and Endorsements 006 4

FORM HIS 2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASHE Code Section XI

1. Owner Florida Power 8 Li ht Date 08 03 98 700 Universe Blvd. Juno Beech Fl. 33408 Sheet of 2 Address I
2. Plant Turke Point Plant Uni t PWO fI: 64/7146 WO fi: 98009890 01 9760 SW 344 Street Florida Cit Fl. 33035 Address Repair Organization P.O. Ho.,Job Mo.,etc
3. Work Performed by Florida Power 8 t.i ht Type Code Symbol Stamp M A Authoritation Mo.

Expiration Date M A 9760 SW 344 Street Florida Cit FL. 33035 Address C. Identification of System: Safet ln ection S stem System lf: 62 Duality Group:

5. (a) Applicable Construction Code B31.1 7955 Edftfcn,~u A Addenda,~u A code casa ftr> Appffcatrte Edition ot Section Rl utlllted for Repairs or Replscesents 79S9 Edftfcn,~u A Addenda,~u A Code Case H

. Identification of Cmfponents Repaired or Replaced and Replacement Components Meme of Name of (Manufacturer( National ( Other (Year ( Repaired ( ASHE Coaponent Manufacturer ( Serial No. Board Identification (Built( Replaced or ( Code (

( Replacement (Stanp (

I I [v~es uo IBOLTE HEAVY HEX (8) IN/A IH/A IN/A (4 894R UTCH 409362 (H/A (Replaced (Mo I

(MUT, HEAVY HEX (8) (M/A (H/A IN/A 14-894R UTCt 391981 (H/A (Replaced (Ho

7. Description of Work: REPLACE FLANGE BOLTIMG OM FLAMGE BETWEEM VALVE 4.894R AMO REFUELIMQ WATER STORAGE TANK.

. Tests Conducted: Hydrostatic: Pneunetfct Hominal Operating Pressure Pressure~NA IS Test Tocpersture N A 'F 98.007.4

Sheet 2 of 2 FORN NIS.2 (Back)

9. Remarks: MECHANICAL CONNECTION MO llELDIHG RECUI RED.

CERTIFICATE OF COMPLIANCE Ne certify that the statements made in the report are correct and this replacement conforaa to the rules of the ASNE Code, Section XI.

Type Code Synhol Stenp ertificate of Authorization No. A Expiration gate H A

+

C H Z@VC ~~~9 . /'j oner o Owner 9s Oesignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid coasission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade County and elployed by Arkwright Nutual Insurance Company of Noruoad, Na. have inspected the ccaponents described in this Owners Report during the period / / to

/ / and state that to the best of my knouledge and belief, the Oner has performed examinations and taken corrective measures described in this OMners Report in accordance uith the requirements of the ASNE Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any Marranty, expressed or

' Report. Furthermore imp L I ed9 concerning the exami net i ons and corrective measures described In this oner neither the Inspector nor his ca@layer shaLL be liable in any manner for any parsonaL inJury or property damage or a Loss of any kind arising from or connected Mith this inspection.

Comnissions NB 8230 N I Ins ors S nature National Board, State, Providence, and Endorsements gate CF 98.007.I9

FORH NIS-2 ONNERS REPORT FOR REPAIRS OR REPLACEHEHTS As Required by the provisions of the ASHE Code Section XI

1. Ower F l or ide PoMer & L i ht Date 10 07 98 700 Universe Blvd. Jwm Beach Fl. 33408 Sheet of 2 Address
2. Plant Turks Point Plant Unit 4 PMO ¹: 64/4367 MO ¹: 97020847 01 9760 SM 344 Street Florida Cft Fl. 33035 Address Repair Organization P.O. No.,Job Ho.,etc

. llork Performed by Florida Power & Lf ht Type Code Symbol Stamp Authorizatfon Ho. H A Expiration Date N A 9760 SM 344 Street Florida Cft FL. 33035 Address

4. Identification of System: S nt Fuel Pit Coolf S stem System ¹: 33 Duality Group: C
5. (a) Applicable Construction Code B31.1 1955 Edition,~us Addenda,~us Code Case (8) Appliosule Edition ofBLITT seotlon Rl utilized for Repairs or Replsonaents f989 Edition,~MA Addenda,~NA code ossa
6. Identification of Ccsponents Repaired or Replaced and Replacement Components Name of Name of )Manufacturer National Other iYear i Repaired i ASHE i Component Hanufacturer i Serial No. Board Identf f ication ]Built( Replaced or J Code i J

Replacement istsmp i I J~rea Eo IBOHNETE VALVE ENGINEERED H/A iH/A iUTC 4'f0018 UNK iReplaced iNo VALVES STK CODE 52627

7. Description of llork: REPLACED BONNET ON VALVE 4-7988.

SYSTEH LEAKAGE TEST PERFORMED UNDER 04 SFPC-3332-1 01.

Tests Conducted: Hydrostatics Pneunat I c: Hominal Operating Pressure

~

Other VT-2 Pressure~62 io Test Terperature 86 F 98.008-4

Sheet 2 of 2 FORH NIS-2 (Back)

9. Remarkst HECNANICAL CONNECTION NO lJELDING REOUIRED.

CERTIFICATE OF COHPLIANCE Me certify that the statements made in the report are correct and this replacement conforms to the rules of the ASHE Code, Section XI.

Type Code Symbol Stan@ N A Cer t i fi cate Expiration Date of hor 1 zat I No.

~

A N A N A Date 4~++ 19 Owner or r's esignee 'itle CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid caanission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and employed by Arkwright Hutual Insurance Company of Norwood, Ha. have inspected the cerponents described 3n this Owners Report during the period 09/03/98 to 10/05/98 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASHE Code, Sect3on XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his esployer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Comnissions NB 8230 N I Inspectors ignatur National Board, State, Providence, and Endorsements Date ~~ &5 1952 98-008-4

FORN NIS.2 ONNERS REPORT FOR REPAIRS OR REPLACENENTS As Required by the Provisions of the ASNE Code Section Xl

1. Owwr Florida Power B Li ht Date 12 09 98 700 Universe Blvd. Jun Beach Fl. 3340S Sheet of 2 Address
2. Plant Turk Point Plant Unit Pl% ¹: 64/8231 MO ¹: 98015323 01 CR ¹:9S-1144 9760 344 Str t Florida Cit F l. 33035 Repair OrBanization P.O. No.,Job No.,etc
3. Mork Perforafed by Florida PoMer C Li ht Type Code Sysfbol Stamp N A Authorization No. N A Expirat'ion Date N A 9760 SM 344 Street Florida Cit FL 330 5
4. Identification of Systeat Nein Steafa S tee Systea ¹: Qual I ty Group: 8 5~ (a) Appl icable Construction Code B31.1 f955 Edition ~NA Addenda ~NA Code Casa (N) Applicssl ~ Edition of section xl Utilized for Rapefrs or Replaceannts l9E9 Editftn,~NA Addenda,s~acoda case Identification of Coaponents Repaired or Replaced and Repiacaeent Coayonents Naca of N~ of iNawfactwer) National i Other )Year ) Repaired i ASNE i Coaponent Nanuf acturer i Serial No. Board I dent i fI cat Ion /Builti Replaced or )

Code i I i Replaceeent /Staay J i~res so I

iANGLE9 3 X 3 X 1/2 iN/A )N/A )N/A iUTC 404047 JUNK ]No FABRICATE STK CODE 29626 1 I 1 iANGLEP 4 X 3 X 1/2 )N/A iN/A IN/A iUTC 374185 iUNK ]No STK CCOE 29660 1 i 2 FABRICATED

7. Description of Morkt HN F TION OF NOV-4-1401 SUPPORT STRUCTURE TO TH INSTAL AT ON OF A FURNANITE BOX PER CR 98-1144 8.~ Tests Conducted:t Hydrostatic: Pnetpstflo: Ntnfnst cperstlns pressure Other VT-3 98.009.4

Sheet 2 of 2 FORN N1S-2 (Back)

9. Reearks: A lKLDINQ RF N ACCORDANCE NITN APPR P ANT PROCEDURES CERTlF I CATE OF COIPLl ANCE Me certify that the statoeents code in the report are correct and this replac~t confo~ to the rules of the ASNE Code, Section X1.

Type Code Syabol Steep N A Certificate of Aut orization No. Expiration Da'te N A Signed Ouner or r~s Desi, Title

~ Date CERT1F1CATE OF 1NSERV1CE INSPECTION 1, the undersigned, holding a valid caaaission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade City and enployed by Arkuright Nutual insurance Cocpany of Noruood, Na. have inspected the coaponents described in this Oners Report during the period 08/19/98 to 12/09/98 and state that to the best of a/ knouledge and belief, the Ower has perforaed examinations and taken corrective ac@auras described in this Owwrs Report in accordance Nith the roquireeents of the ASNE Code, Section Xl.

By signing this certificate neither the inspector nor his eeployer cakes any uarranty, expressed or i apl I ed/ concerning the exeainati one and corrective seasures descr ibad in this Ouner ' Report . Furthermore, neither the inspector nor hfa eaployer shall be liable in any ecwxwr for any personal injury or property dosage or a loss of any kind arising froe or comected Nith this inspection.

C~issions NB 8230 N 1 1 to gnature National Board, State, Providence, and Endorseecnts Dat 98-009-4

FORH NIS 2 OUNERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the provisions of the ASHE Code Section XI

1. oner Flori Power 8 Lf t Oats 01 05 99 700 Universe ~ lvd. um beach Fl. 33408 Sheet of 2
2. Plant Turk Pofnt Plant Unit Naca PMO 0c 69/6949 NO Nt 98005813 01 CR b:98.428 97 Flor fde It F 33 3 Repair Organfzatfon P.O. No.,Job No.,etc
3. 1Jork Perforsfed by Florida Pofder t Li ht Type Code Syefbol Steep N A Authorization No. N A Expiration Oate N A 9760 SQ Stree Florida Cf t FL 3035
4. Identf f ication of Systeoc Eaer FeecLtster tee Systea Nc 75 Quality Or mpt C 5~ ( ~ ) Appl'lcable Construction Code 831.1 f955 Editfon,~NA Addenda,~NA Coda Case INI Appfiosfrf~ Edltftn of Eeotfon RI Utllfted for Repsfrs or Rapfaoemnts f959 Edftlon,~NA Addenda,~sa Coda case Identl f ication of Co55fponents Repaired or Replaced and Replaceeent Coeponents N~ of Noae of )Nanufacturer[ National [ Year / Repaired / ASHE /

i fI cation built)

Othec'dent Nanufacturer Serial board Coaponent ) No.

[

I Repla ~t iSt~

Replaced or ( Code

[TwrWlaloo

)

]

JBOLTE HEAVY HEX (2) IN/A IN/A )UTC 418479 )UNX [ Replacceent ] No t

iNUTR HEAVY HEX (2) IN/A /N/A JN/A )UTC 418459 /UN@ )Repiacoeent )No

7. Oescrfptfon of Uorki R TQO TS AIO TN NUTS ON HANCER 80117.H-324 0 Pneumat
8. Tests Conducted: Hydrostatic: Ic t Nonlnsl CperatlnR pressure Other VT-3 Preasura~ll A IN Test Teatnrstws 99.001-4

Sheet 2 of 2 FORH NIS-2 (Beck)

9. Remarkst NECNANICAE CONNECTION NO lJELDING REQUIRED.

CERTIFICATE OF CCWPI.IANCE lJe certify that the stateswnts made in the report are correct and this repLacement conforms to the rules of the ASNE Code,Section XI.

Type Code SyaboL Stamp N A Certificate of Authorization No. N A Expiration Date N A Date Ouner or r's Designee, Ti ~

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid comaission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and employed by Arkuright Nutual Insurance Company Ne. have inspected the components described in this O>>>>rs Report during the period 04/16/98 of'orwood, to 01/04/99 and state that to the best of wy knouLedge and belief, the Qner has performed exesinations and taken corrective aeasures described in this Oners Report ln accordance uith the requirements of the ASNE Code, Sect l on XI.

By signing this certificate neither the Inspector nor his employer makes any uarranty, expressed or implied, concerning the examinations and corrective measures described in this Ow>>r 's Report. Furthermore, neither the Inspector nor hia eapLoyer shaLL be Liable in any mwx>>r for any personaL injury or property damage or ~ Loss of any kind arising froe or connected Nith this inspection.

Comissions NB 8230 N I I for Signature National Board, State, Providence, and Endorscments Oa 99-001-4

FORN NlS 2 OQfERS REPORT FOR REPAlRS OR REPLACEHENTS As Required by the Provfsione of the ASNE Code Section Xf

1. Oner Florf P r 8 f t Date 02 17 99 700 fverse lvd Jum Reach Fl. 33408 of 2 Address
2. Plant Turke Point Plant Unf t 4 PNO ¹t 64/9283 QO ¹: 98023845.01 97 r Florida Cft Fl 330 Repair Organization P.O. No.,Job No.,etc
3. IJork Perfonaed by Florida PoMer 8 Lf t Type Code Syafbol Steep N A Authorization No. N A Expiration Date N A 9760 Su 344 Street Florida Cit FL. 3303S
4. identification of Systmt Cool f Nate r tee System ¹:

S. (a) Appl feeble Constructfon Code 831. 1 'f955 Ecfftfon ~NA Addenda,~ss Code ceca (fr> Afa>>fee>>fe Editfon of Eectfcn x! Ntfllted for Repairs or Rspfaccmnts >959 Edftfcn,~cs Addenda,~cs cafe casa

6. identification of Coaponents Repaired or Replaced and Replacement Coefponents BIVALVE Naae of N~ of [Hanufactwer) National ( Other !Year I Repaired I AQK I Casponent Nenufacturer ) Ser f al No. 8oard ldentf ffcatfon )Suflt) Replaced or ) Code )

) Replace )Staap (

I I /~tes No SONNET N/A N/A IN/A (UTC M00421730 (SC IReplaced [No STY CtIE 0053117 2

7. Description of Marks OONN T ON'VAL 4 1'1 SYST N LMA T ST PERFORNED UNDER 04.CCN-3023S 1 01 E. >sate condcctsdf Nrdrostetfc: pnetnatfcl: Ncefnal Oparatfn¹ Pressure Other VT.2 Prssstcc~50 >5 Test Teefperatwe 86 'F 99-M2.4

Sheet 2 of 2 FORN NLS-2 (Back)

9. Reaarkst l%CHANICAL CtWNECTICSI NO WELDINQ REOUIRED.

CERTIFICATE OF CONPLIANCE Me certify that the stataeonts aade fn the report are correct and this replaceeent confo~ to the rules of the ASNE Code, Section Xl.

Type Code Syabol Staep N A Certificate of A thorfzatfon No. N A Expiration Date N A Signed E~ Date Seer or r'esfgnee, Tf e CERTIFICATE OF INSERVfCE INSPECTION I, the undersfgned, holding a valid caaaission issued by the Natfonal Board of Softer and Pressure Vessel inspectors and the state or Province of Dade Catty and oapfoyed by ArkMrfght autual Insurance Company of NorMood, Na. have inspected the coaponents descrfbed fn thfs Owners Report during the period 12/01/98 to 01/06/99 and state that to the best of wy knouledge and belief, the Oaer has perforaed exawinatfons and taken corrective measures described tn thfs Oaers Report in accordance Nith the requirtaents of the AS% Code, Section Xl.

By sfgnfng thfs certificate nefther the Inspector nor hfa eapfoyer mkes any Narranty, expressed or feplfed, concerning the e~fnatfona and corrective measures described fn this Ouner's Report. Furtheraore, nef ther the Inspector nor hfs eapfoyer shaLL be liabl ~ fn any aama for any personaL fnjury or property daeoge or ~ Loss of any kind arising froa or canected ufth this inspection.

Coaafssions NB 8230 N I Inspec ors gnature National Board, State, Providence, and Endorseeents Dat 99.002-C

FDRN Nls-2 ouNERs REpORT FOR REPAIRS 0R REpLAcENENTs Aa Required by the Proviaiona of the ASNE Code Section XI

1. Ouner Fl ri P r I t Date 02 11 99 Iwrae J~ Beech Fl. 33408 Sheet of 2
2. Plant Turk Point Plant Unit 4 PNO N: 64/7688 uO <<t 98012656 r Florida Cit Fl 33035 Repair Oryanlzation P.O. No.,Job No.,etc
3. Mork Performed by Fl I Powr 8 Li t Type Code Symbol Staefp N A Author Ization No.

Expiration Date N A 9760 SV Street Ftori Ci FL. 33035 Addreaa

4. Identification of Syatm! C t Cooli uater tee Syatm Mt Quality Gr~: C 5 (a) Appl icabl ~ Conetruction Code 831.1 IP55 Edit lan,~aa Addenda,~aA Eacfe ossa (5) Applleadle Edltfon of Eeetfon El ptff feed for Eapafrs or Aapfea~ta leap Edftftn,~aa Addenda,~aa code case
6. Identl fication of Coefponenta Repaired or Replaced and Replacement Coeponenta Nme of N~ of IHanufacturerl National I Other )Year i Repaired i ASNE i Caeponent Manufacturer J Seri ~ l Mo. Ident i f I cat 1 on )Built( Replaced or J Code i I i Replacement istaefp )

I I i~res Ilo I ROD ~ THREADED N/A iN/A iSTM aeE 29493 1 IN/A IReplacoeent INo I STUDS FABR CAT UTC 420599

7. Deacription of IJorkt R ON 0 4C NX
8. Testa Conductedt Ilvdroetetle: pnafpatlo: Eonfnal Epsfetf lip Pl'essltre Presawa~fd Test T~ratwe 'F 99.003-4

FlXN NIS 2 (Back) 9 R~rksc NE HANICAL ON NO WELD NO REOUIR CERT IF I CATE OF IXXIPLIANCE Me certify that the statoeents Nede fn the report ate correct and this replaceeent confo~ to the wlea of the AQ% Coda, Section Xl.

Type Code Syabol Steep Certificate ot Authorfzatfon No. Expf I'at'ion Da'te N A Sf~~ Oaer r's Oaie or esfgnee, T ~

CERTI flCATE Of INSERVICE INSPECTION I, the undersfgned, holding a valfd comfasion fasued by the National Board of Boiler and Pressure Vessel fnspectors and the state or Province of Dade Catty and eeployed by Arkurfght Nutual Insurance Coipany of Noruood, Na. have inspected the coaponents described in this Ouners Report during the period 06/22/95 to 06/12/99 and state that to the beat of ay knouledge and belief, the Ower has perfoneed exmfnatfona and taken correctlw mas~s described in this Ow>>ra Report fn accordance Nfth the requfraaents of the AQK Code, Section Xl.

By sfgnfng this certff feats neither the Inspector nor hfa oaployer aakes any Warranty, expressed or neither the inspector nor hia asployar shalL be liable fn any daeage or a Loss of eny kind arising fry

~r fspl fed, concernfng the exmfnatfons and correctfw caesuras described fn this Oeer's Report Furtheraore, for any persmaL fnJury or property or cocnected With this inspection.

Comf ss f one N N I ora ~t~ National Board, State, Providence, and Endorsaaents 19'9-003.4

FORN NlS-2 BRIERS REPORT fOR REPAlRS OR REPLACKNKNTS Ae Required by the provisions of the ASNE Code Section Xl

1. Ouner Florf P r 8 Lf t Date 02 17 99 700 lveree 8 Jmo Beech Fl. 33408 Sheet of 2
2. Plant Turk P int Plant Unit 4 Noae PUO ¹I 64/6487 NO ¹: 98002103 01 CR ¹:96-1222 r Flor fde Clt Fl 330 Addrace Repair Or¹anlzatfon P.O. No.,Job No.,etc
3. Uork Performed by Pouer 8 Lf t Type Code Symbol Steep N A Author l zat lan No. N A Expiration Date N A 9760 SM 344 Street Florida Cft FL. 3303S
4. ldentlf ication of Syetm! n ool f Voter t Syetea ¹: 19 Oual lty Croupc
5. (a) Appl feeble Conetructlon Code 831.1 TPPP tdltltOI,~NA Addssds,~NA Cods Cosa tbi ACPIlodds CdltlM oi ~ tlm Sl Stitit~ for S>> irs or S>>I~~to IPCP Sditim,~oa Add ~,~SA C~ Case
6. identification of Coeponenta Repaired or Replaced and Replecaaent Coaponenta Noae of Naae of ]Nanufacturer] National Other )Year Repaired ) AO>> )

Coaponent Nenufactwer (

Serfal No. ldentlf fcatfon (Buf t t Replaced or ) Code )

(

Replaceeent (Steep )

I ~tos So NUT ~ HEAVY HKX (16) [N/A (N/A N/A STK C(XJE 27835 1 JUNK Replaceaent No

)3 4" I NUT ~ HEAVY HEX (4) IN/A (N/A )N/A (STK CME 27835 1 /UNK (Replacaeent (No (3 4. UTC 419456 JNUTP HEAVY HKX (1) /N/A JN/A (N/A JSTK CMK 27092 1 /UNK JReplaceeent /No

/7 e UTC 373 69

7. Deecrfptlon of QerkJ T ANCNOR ON NARK ¹4A REPLA PLAT HOR NUTS ON NARK ¹48.

R PLACED PLAT S Oi NARK ¹4C REPLACED 2 BASE PLATE ANCIKR IRJTS ON NARK ¹4F. REPLACED 4 BASE P AT ANCHOR ON 1 .N- -01 REPLA 4 BASE PLATE ANCHOR NUTS NARK ¹ 8123-N-254.02. REPLACED 1 BAS PLAT ANCHN OI NAR ¹4 N-190-06o RKPLACED 1 BASE PLATE ANCHOR NUT ON NARK ¹4-8046-Ho190-01. REPLACED 1 BASK AT AN NOR Oi

8. Teate Conducted! Hydroetat fc: P~tfc! stofsst cpsrat ills prsastso Other VT-3 Prssssro~ll A ls Tost Tt>>srottoo 99.004.4

Sheet 2 of 2 FDRN NIS.2 (Back)

9. Remrksi & NANICAL CDNNKCTI(W Mo uELDINa REouIRED.

CERT IF ICATE OF CQOLIANCK Me certify that the statements mde ln the report are correct and this replacement conform to the rules of the AQ% Code, Section XI.

Type Code Sy<<bol Steep Certificate of A thorlzatfon No. Expiration Date N A Si~~ Date ~4 7 19 Ower or r's D , Tl tl~

CERTIFICATE OF INSERVICK INSPECTION I, the undersigned, holding a valid comlssion issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Dade Catty and <<aployed by Arkurlaht Nutual Insurance Caspany of Norwood, Ne. have inspected the cceponents described ln this Oners Report during the period 03/19/90 to 02/16/99 and state that to the best of iy knouledge and belief, the Oner has performd examinations and taken corrective masures described ln this Ouners Report ln accordance uith the requfrceents of the A$% Code,Section XI.

Sy siwinB this certificate neither the Inspector nor his a<<player mkee any uerranty, expressed or Iaplied, concerniny ttw exainatlora and corrective aeasures described ln this Oeeris Report. Furtherare, neither the Inspector ner his esployar shaLL be Liable ln any mar for any personaL lnJury or property damge or e Loss ef any kind arising frow or corrected uith this inspection.

C~fssfone KB 8230 I National Board/ State/ Providenceg and Endorsments Da /cF 19~

99.004.4

FIN NIS-2 ORIERS REPORT FOR REPAIRS OR REPLACENENTS Aa Required by the Provieione of the AQR Code Section Xl

1. Ouner Flori P r I I Date 02 17 99 700 Iveree I Jwa leach FI. 33408 of 2
2. Plant Turk Point Plant Unit 4 PNO ¹! 44/9214 lo ¹l 98021775 r F ride Clt Fl. 330 Repair Or¹anixation p.O. No.,Job No.,etc
3. Mark Perforaed by F I Pewr S Li t Type Code Syefbot Steefp Authorization No.

Expiration Date N A 9760 Str Florida Ci FL. 33035

4. Identification ef Syatoas 5~ (e) Applicable Conetructlon Code $ 31.1 1999 Rditfen,~ss Addenda,~as Code Case (fe> Appllcacls Rdltlan of Reetfon xl Util ised for Repairs or Resist~to 1999 Rditi ~esne Addenda ~leeds case identification of Coefpenenta Repaired or Replaced and Replacement Coeponenta N~ of Nme of [Hanufactwer] National ) Other [Teer ) Repaired ) AS% /

Ccefponent Nenufacturer I Serial No. Qoard ldent f fI cation JBulltf Replaced or ) Code )

I ) Replace )Steep /

I I I /~ree so ICYLIIOER~ FLUID ASSSENSLY IN/A IN/A [N/A STN aeE 70887 1 (LNC [Replac~t /No I UT 422184

)RCNP THREADED fN/A IN/A IN/A ISTK CSE 29490 1 )UNE [Replaceaent )No I 1 Tle FARRICAT UTC 410924 JRODP TNREADED iN/A IN/A )N/A ]STr uOE 2Oaaa 1 )INIK (Replaceaent )No I F I UTC 41

7. Deecrfptfon of QoAT 4P 01 DISCHARGE F R. feet ~ Condestsdt Rpdrostatfsl: pnsfnstial: Ncalnal Operatlni Preaaure

~

91 F 99-005.4

FDRN NIS-2 (Sack)

9. R~rkst CA Ok uELD ING REQUIR CERTIFICATE Of COOlIANCE Me certify that the statoaents swde fn the report are correct and this replacaaent confo~ to the rules of the AQR Code, Section Xl.

Type Code Syabol StaN1 N A Certificate of A fxatfon ko. N A Expiration Date N A Sf~3~

owwr or r9s ionee, Tftl~

m ~ D.t. 19 +~

I CERTIPICATE 019 INSERVICE INSPECTION I, the undersfiwd, holdfnE a valid comfssfon issued by. the National Nacrd of Qof ler and Pressure Vessel inspectors and the state or Provfnce of Dade Catty and eaployed by Arkkrfsht Nutual Inswance Coapeny of Norwood, Ne. have inspected the coaponents described fn this Owners Report durfng the period 11/23/9$ to 02/16/99 and state that to the best of ay knouledge and belief, the Ovner has perforswd exsafnations and taken corrective aaaswes described fn this Sacra Report in accordance Nfth the requfr~ts of the As% code,Section XI.

Sy sfgnfng this certificate nefther the Inspector nor hfa eaployer awkes any Narranty, .expressed or faplfed, oencernfny the oxminatfona and corrective <<assures described in thi ~ Owwr9a Report. Furthereore, neither the Inspector nor hi ~ eaployer shaLL be liabl~ in any mrna'or any personal fnJury or property daaaoe or e Loaa ef any kfnd arfafng froa or comected Nf th this fnspectfon.

Cemfssfona NS 8230 N I I ors ture National Board, State, Providence, and Endorseeents Da 19~7 99-005.4

FORN NIS 2 OSIERS REPORT FOR REPAIRS OR REPLACENENTS As Required by the provisions of the ASNE Code Section Xl

1. Owwr Fl ri P t 1 t Date 02 4 99 700 Universe Ql Jwn Beech Fl. 33408 Sheet of 2
2. Plant Turke Point Plant Unit Nme PMO Bt 64/7687 MO B: 98012655 01 9760 344 tr Florida Cit Fl 3303 Address Repair OrSani!ation P.O. No.,Job No.,etc
3. Mork PerforJeed by Fl rideP rtLi t Type Code Syabol Stasp N A Author(Sation No.

Expiration Date N A 9760 SM 344 Street Florida Cit FL. 3303S

4. Identification of Systea: C t Cool i Mater tea Systea 0: 30 aual l ty Croup; C S. ( ~ ) Applicable Construction Code $ 31 1 1999 Est tltn,~NA Addenda,~ll A code cIse iui Applfoaule Edition oi station xl utl littd ior Repairs or Reptaoments 1999 Edttltn.~ss Addeoda,~ss code case
6. Identification of Coaponenta Repaired or Replaced and Replacement Coeponenta Name of N~ of )N~acture ( Natio Other )Year ) Repaired ) ASHE )

Cceponent Nanufacturer (

Serial No. Board Identification )Built) Replaced or ) Code )

I ( R~i~~t (St~ )

I I I (T~es So (RJXJ 9 THREADED (N/A (N/A (STX C<<OE 29493 1 )UNJ<< (Replaceaent )Ko l 36 STUDS FABRICAT D UTC 420599 INUT ~ HEAVY HEX <<12) )N/A IN/A (N/A )

STX CODE 27847 1 )UHK )Replacaaent )No

)3 4N-10

)NUT,HEAVY HEX

)3 4"-1 (4 )N/A IN/A (N/A UTC 418106

)STJ<<CODE 27847 UTC 396745 1 )UNJ<<)Repla ~t )No

7. Description of Morkt R 36 STLR)S NO 12 NJTS ON THE <<XJTLET ENO ANO 4 NJTS ON INLET ENO OF 4$ CCM HX 4E2078 .
8. Testa Conducted: Hydrostatic: PneIsetict Nowinai Operatiny Pressure Other Pressure~it Test Teepsrature ~

F 99-006-4

Sheet 2 of 2 FORN NIS-2 (Sack)

9. R~rks: HANICAL CT ION NO IJELDING REOOIREO.

CERTIFICATE OF C(NPLIANCE Me certify that the state<<ants cade in the report are correct and this replace<<ant confo~ to the rules of the ASME Code, Section XI.

Type Code, Symbol Steep N A Certificate ut Iz ion N A Expiration Oats N A Si~ l~ gate Oner o r~s Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid comission issued by the National Qoard of Boiler and Pressure Vessel inspectors and the state or Province of Oade Catty and ceployed by Arkuright Nutual Insurance Cospany of Norwood, Na. have inspected the coeponents described in this Owners Report curing the period 06/22/94 to 02/22/99 <<nd state that to the beat of ay knowledge and belief, the Ouner has per fonaed exaafnations and taken corrective aeaaures described in this Oaers Report in accordance Nith the requireeents of the ASNE Code,Section XI.

gy signing this certificate neither the Inspector nor his eeyloyer sakes any wrranty, expressed or iapL i ed/ concerning the exminationa and corrective <<assures described in this Oawr's Report. Further<<ore, neither the Inspector nor his employer shaLL be liable in any manner for any personal in)ury or property daaage or ~ Loss of any kind arising froe or corrected Nith this inspection.

C~issions NB 8230 I ora gnature National Board, State, Providence, and Endorseeents Oate 99.006-4

FORN NIS-2 OWERS REPORT FOR REPAIRS OR REPLACENENTS As Required by the Provisions of the ASNE Code Section XI

1. Ower Flori ~ r 8 Li t Date 03 22 99 700 Universe ~ l Jw5o Beach Fl. 33408 of 2
2. Plant Turks Point Plant Unit PMO B: 64/7048 MO B: 98008771 01 97 344 S r t Florida Cit Fl. 33035 Address Repair OrGanisation P.O. No.,Job No.,etc
3. llork Perfonaed by Florida PoMer 8 Li t Type Code Syefbol Steep N A Authoriaation No. N A Expiration Date N A 9760 344 Street Florida Cit FL. 33035
4. Identification of Systae: C t Cooli Mater S tefe System Bt 30 Guality Group: C
5. (a) Applicable Construction Code $ 31.1 '1955 Edftfon,~NA Addenda,~ll A Coda ossa (5) Appl loadie Edition of seotion xi Utilited for aepairs er aeplaotaants 19$ I Edition,~aa Addenda ~NA soda ossa
6. Identification of Cofwponents Repaired or Replaced and Replaceeent Coeponents N~ of N~ of )Narafacturer) National C~t Nanufacturer )

I Serial No. Board Other Ident i f ication

)Year

)Built)

) Repaired ) ASHE Replaced or ) Code Replaceoent )Staap

)

)

) )

) I I /~rss No

)BO.T, 1>> (1) )N/A IN/A IN/A ISTK CODE 71359 1 fUNK )Replaceeent )No

)8 UN THREAD UTC 410524

)BOLT,HEX I1> )N/A )N/A IN/A ISTK CME 71360 1 )UNK )Replacenent )No UTC 400188

7. Description of lJork: REP A TMO CASING T ON THE 4C COiPONENT COOLING MATER POOE
8. Tests Conducted: Hydrostatic: Pnasetic: Nosinal OperatinG Pressure N A 4F 99-007-4

FORN NIS.2 (Back)

9. Remarks: HANICA K CTION NO IJELD INC REQUIRED CERTIFICATE'F CtNPLIANCE lJe certify that the statements made in the report are correct and this replacement conforse to the rules of the ASNE Code, Section XI.

Type Code SymboL Stamp N A S3~ ~

Certificate of Authorization Ouner No.

Ouner'esignee, N A Title Expiration Date Date N A CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a val fd coeaission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and employed by Arkuright Nutual Insurance Coo@any of Norwxxf, Na. have inspected the coaponents described in th)e Owners Report during the period 05/11/98 to 03/22/99 and state that to the best of my knowledge and belief, the Ovner has performed examinat3ons and taken corrective measures described in this Owners Report in accordance uith the requirements of the ASNE Code,Section XI.

gy signing this certificate neither the Inspector nor his esployer makes any uarranty, expressed or Implied, concerning the exminations and corrective measures described 3n this taJner's Report. Furthermore, ne3ther the Inspector nor his employer shaLL be Liable in eny aemer for any personal 3njury or property damage or ~ Loss of any kind arising fry or corrected with this inspection.

Coaaissions NB S230 N I Inspect rs ture National Board, State, Providence, and Endorsements 99-007-4

FORM NIS 2 OMNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASNE Coda Section NI

1. ONner Fl or i ~ r 8 I t Date 03 25 99 700 I rse I Jun ach fI 33408 Sheet of 2
2. Plant Turk ~ n Pl t Unit 4 PMO N! 64/9'130 MO N: 98022379 01 PCN Q: 96 093 97 S r t Florida Cit Fl. 33035 Repair OrGanization P.O. No.,Job No.,etc
3. Mork Perforaed by Fl ride Pouer S Li t Type Code Syefbol Steep N A Authorization No. N A Expiration Date 9760 tr f l or i Ci t FL Address
4. Identification of Systeet t Cool i Mater S tee Systee Q: 30 Duality Groups C 5~ ( ~ ) Appl'lcabl ~ Construction Code S31.1 1555 Edltlon,~NA Addenda,~wl coda ease (h) Appl1 sepia Edltltn of seotlen xl utl littd for Repairs or Repleoenents Ipep Edl sion,~ea Addenda,~ue ldenti f ication of Coaponents Repaired or Replaced and Replaceeent Coeponents Mme of N~ of IN~facturerI Nation l I Other IYear I Repaired I ASNE I Coaponent Nanuf acturer I Serial No. Qoard f Ident i Ication IQuiltI Replaced or I Code I I I Repiaceeent IStaap I I I I /~ras llo IPCV.4.832 IVARImS IVARIQIS IN/A ICCM HEAD TNC I VAR. IReplaceaent INo f

INZII I CAT ION

7. Description of Morkt T F 4 2 00 AS OCIATEO PIPING FITTINGS ERNEPORTS AND VALVES PER PC N 96-093 I NCLIS IMG MORN R 01. CCOE CASE N-416-1 MAS INVOKED FOR THIS NCOIF ICATION. PRESSMRE TEST 04-CCM-30320-L-01 MAS PERFOR R PC 96.093
8. Tests Conducted: Hydrostatic: Pneuaat ic: Naainal OperatinG Pressure Other VT.I 2 Alp 3 presaure~lrt IE Test Tesparature 78 99-008-4

Sheet 2 of 2 FORN NIS-2 (Back)

9. Re<<arkst LOIN ACCORDANCE NITH THE NELO CONTROL NANUAL 41 .1 FOR THIS REP AC T ACTIVITY COMPLIANCE CERTIFICATE OF Ma certify that the state<<ants made in the report are correct and this replaceaent conform to the rules of the ASNE Code, Section XI.

Type Code Symbol Steep Certificate of Authorixation No. Expiration Oate

~

N A N A SI~~ Oner or r's eslgnee, T tie gate P 19 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid coaeission issued by the National Board of Boiler and Pressure Vessel, inspectors and the state or Province of Dade County and enpioyed by Arkuright Nutual Insurance Company of Norwood, Na. have inspected the components described in this &aors Report during the period 12/14/98 to 03/25/99 and state that to the best of my knowledge and belief, the Ovrwr hss perforswd ex<<sinstions and taken corrective measures described in this Owwrs Report in accordance uith the require<<ents of the ASNE Code, Section Xl.

Sy signing this certificate neither the Inspector nor his eapioyer makes any uarranty, expressed or iapiled, concerning the exainations and correctiw measures described in this Oeer's Report. Further<<ore, neither the Inspector nor his employer shalL be Liable in any earner for any personaL injury or property d<<asge or a Loss of any kind arising fro<<or camected arith this inspection.

Coswissions NB 8230 N I Inspector Si e National Board, State, Providence, snd Endorsceents Oats99-008.4

FORN Nls 2 04iERS REPORT FOR REPAlRS OR REPLACENENTS As Required by the Provisions of the ASNE Code Section Xl

1. Oner Flori Pouer S Li t Date 03 29 99 iv r each Fl. 3 of Address
2. Plant Turk Point Plant Unit PMO 0: 64/0316 lQ 4t 99005046 01 CR N:99-343 97 344 t Florida Cit Fl. 330 Repair OrSanization P.O. NoadJob Noedetc
3. liork Perfoneed by Florida Po5der C Li ht Type Code Sye5bol Steep N A Author I sat lan No N A Expiration Oats N A 97 Str t Florida Cit FL. 33035 Address
4. identification of Systea: CVCS Char 1 t Letckwn teds System N: 47 Ouality Srmp: 8
5. (a) Applicable Construction Code 831.1 TP55 Edfticn,~aa Addenda,~sa Code Casa ia> Applicaal ~ Edition of section Rl utilitsd for Repairs or Reptacments leap Edfticn,~NA Addenda,~NA code case
6. identification of Caaponents Repaired or Replaced and Replaceaent Coeponents Nme of iNanufactweri National i Other iYear i Repaired i ASNE i Nanuf acturer i Seri ~ l No. Soard l dent i f ication iSuilti Replaced or i Code i I

i Replacooent istaap i I I /T~es No I ROD ~ THREAOEO iN/A iN/A iN/A ISTK C(X)E 29499 1 iUNK i Replaceient i No 8 TUOS FASR CATED UTC 403918 I

iNUT, HEAVY HEX (16) iN/A iN/A IN/A ISTK CME 27838 1 iUMK iReplace555ent iNo UTC 419762

7. Description of Uorkt REPLACED 8 STLIS ANO 16 NUTS ON FlC-4-154 FLANGES.
8. Tests Ccnduotal: Nfdrostatie: Pnacaatfc: Nculnsl Cparatfn8 Pressure Other Pressure~is Test Teatcerature

~

F 99-009.4

Sheet 2 of 2 FORM MIS-2 (Back)

9. Remerkst CAL CTIOM NO QELOIMG REQUIRED.

CERTIFICATE OF COIPLIANCE W certffy that the statements made fn the report are correct and this replacement conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N A Certificate of Authorization No. N A Expiration Oats N A Oats Oune or s Oesfgnee, T le CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holdfng a valid conefssfon fssued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and eaployed by Arkurfght Mutual Insurance Coo@any of Noruood, Ma. have inspected the coeponents descrfbed fn thfs Ouners Report during the perfod IQ/19/99 to 05/29/99 and state that to the best of my knouledge and belief, the Ouner has performed examinations and taken correctfw measures described fn thfs Ouners Report fn accordance ufth the requfrements of the ASME Code,Section XI.

By signing this certfffcate neither the Inspector nor hfs eapioyer makes any Marranty, expressed or faplfed, concerning the e~fnatfons and corrective measures described fn this %acr's Report. Furthermore, neither the Inspector nor hfs esployer shall be liable fn any marner for any personal fnjury or property damage or a Loss of any kind arising from or ccenected Mith this inspection.

Coaafssfons NB 8230 N I I ors gnatwe National Board, State, Providence, and Endorsements Oat 99.009-4

FOUI NlS 2 OSERS REPORT FOR REPAIRS OR REPLACENENTS Aa Required by the Proviaiona of the ASNE Code Section XI

1. Ow>>r F lori P r Li t Date 03 31 99 Sheet of
2. Plant Turk Point Plan Unit 4 PNO ¹: 64/0372 IR) ¹: 99005048 CR <<:99-476 9760 OJ 344 Street Florida Cit Fl. 33035 Addreaa Repair Organization P.O. No.,Job No.,etc
1. Mork Perfore>>d by Florida Pouer 8 I t Type Code Syebol Steep N A Authorization No.

Expiration Date N A 97 S r F ri I FL 035

4. ldentif ication of Syatmt Safe ln ection Acc~letor Syatm ¹i
5. (a) Applicable Conatruction Code lplp Edltfcn,~ss Addenda,~ss Code Case (Nl Appllcsul ~ Editicn of Rection xl utilfted for Repsfra or R p et~ sc~ ttpdp Edftfcn,~ll A Actfenda,~gg coda cess
6. Identi f ication of Coaponenta Repaired or Replaced and Replaceoent Coeponenta N~ of Nme of (Nanufacturer( National ( Other (Year ( Repaired ( AQIE (

Coagx~t Nanufacturer ( Serial No. Board ldent i f ication (Built( Replaced or ( Code (

I ( Repiac~t (Steep I ( i~res No (NUTS I8) HEAVY HEX (N/A IN/A IN/A ISTK CE 229969 1 (UNK (Replac~t (No I UTC 424385 (NUTS (24) HEAVY HEX (N/A (N/A (N/A (STK CCOE 27869 1 (UNK (Replacenent (No I UTC 424390 (STUDS ('l6) (N/A (N/A (N/A (STK CSE 29516.1, UTC (UNK (Replacement (No 424362 405745 424346 e

7. Description of Mark) R P S 16 STNS ON NOV.4-865$
8. Teata Conductadt Hydroatatic: Pnaaatict Ncninal Cperatlnp Pressure Other VT-1 Pressure~I A ip 99.010.4

Sheet 2 of 2 FORN NIS 2 (Back)

9. R~rks: HAN CA CT ON NO QE NO REOUIRE CERTIFICATE OF CLWPL LANCE Me certify that the statements mde fn the report are correct and this reptacemnt conform to the rules of the AQK Code, Section XI.

Type Code Syabot Steep N A Certificate of Authorfzatfon No. N A Expiration Date N A Sf~~ Oeer or Oewr'esignee, I Tl ~

Date CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valfd ccaaissfon issued by the Natfonal Board of Bofler and Pressure Vessel inspectors and the state or Province of Dade Catty and <<sployed by Ar kurfght Mutual Insurance Coepany of Noruood, Na. have inspected the coaponents described fn this Owers Report during the period 03/19/99 to 03/30/99 and state that to the beat of ay knoutedge and belief, the Qewr has performd exaefnatfons and taken corrective aeasures described In this Ouners Report in accordance Nfth the requfreeents of the ASNE Code,Section XI.

By signing thfa certlf fcate neither the Inspector nor his <<sptoyer mkes any uarranty, expressed or Ieptfed, concerning the exmfnatfona and corrective masures described ln this Oewr's Report. Furthersere, neither the Inspector nor his eaptoyer shaLL be Lfabl ~ In any warner for any personal Injury or property damge or a Loss of any kind arising fry or ccxvwcted uith this lnspectfon.

C~fssiona NB 0 N I ors gnature National Board, State, Providence, and Endorseeents Date 99.010.4

FDRN Nls 2 ouNERs REPoRT F0R REPA1Rs 0R REPQAGEHEHTs Ae Requfred by the Provieione of the ASHE Code Section Xl

1. Ouner F rf P r f Date Sheet of Addrace
2. Plant Turk Pofnt Plant Unft 4 PlO Nt 64/6454 fa) N: 98005482 01 CR N:97 1377 F rf f F Repefr Oryenfzetfon P.O. No.,Job No.,etc W. Nork Perfoneed by Fl rf P r t Type Code Syebol Steep Authorfzatfon No. N A Expfratfon Date H A 9760 SM Stree Florfda f FL.

Addreea

'4. ldentfffcatfon of Syetm!

5. ( ~ ) Applfcabl ~ C~tructfon Code 1 1 1555 Edit tan,~ssddondo,gl Code Casa (tat Ilppliascl ~ Edition of section El util ised for Eopofrs or sonics~to tccp Edition,~ns Addenda,~cs cade case
6. ldentfffcatlon of Coaponente Repefred or Replaced end Replaceeent Coeponente N~ of N~ of (Nanufactwer) Natfonal ) Other )Year I R~frcd I AS E I Coeponent Nenufacturer ( Serfal No. Soard ldentff fcatfon )Suflt( Replaced or ) Code )

I ) Replacefppent (Stony (

I l I /~Yes ao

)CHECK VAlVE (1 1/2") ) SONNET FORGE )N/A (N/A (4-721S - STK C(OE 222259 (UHK (Replaceeent (Ho

( 4 I IP1PE (1 1/255) (N/A )N/A (STK CCOE 306117.AQ% SA106 )UHK )Replaceecnt )Ho I 417701 (ELS(N (1 1/2") )N/A IN/A IN/A (STK C(OE 34037.AQR SA105 (UNK )Repleceeent )Mo I

)NUTS (S) HEAVY NEX )N/A IN/A )N/A ) STK C(SE 27840.UTC 415395 (UNK ) Replaceaent (Ho (ST1NS 4 N N A T 4 4097 (FLANGE (N/A IN/A (N/A )STK C(S)E 102064 (UNK ) Replac~t ) Ho I 4 1- 1

7. Deecrfptlon of Uork: R P VA 4- 1 N Pl E S(HI F 4 STtNS.

N.41 .1 UA F TH R P T A TY AKA T ST RF RPR S T T04- - 1 ..0'f

b. Teeta Conducted: Hydroetatfc: pnamtic: Ecninsl ctnratfnc pressure E 83 'F 99.011-4

FtXN N15-2 (Back)

9. R~rksc A COROAN HIT APPR P T PR CERT I F I CATE OF CNPLIANCE Me cer tify that the stat~to aede fn the report are correct and this replacement conform to the rules o~ che AO% Code, Section XI.

Type Code Syabol Steep Certificate of horfxatfon No. N A Expiration gate N A Sfgned gate 3 Ovner or r e Oeetgnee, Titl~

CERTlFICATE OF lNSERVlCE lNSPECTlON l, the undersigned, holdfng a valid omission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Provfnce of Dade Catty and ecployed by Arkvrfght Nutuel insurance Caopany of Norvood, Na. have Inspected the coaponenta described In this Ovners Report during the period 03/12/99 to 04/02/99 and state that to the best of ary knovledge and belief, the Ovner haa perfors>>d exminatfons and taken corrective assures described fn this Ovners Report fn accordance vfth the requires>>nts of the AQ% code,Section XI.

By signing thfa certificate neither the Inspector nor hi ~ eeployer sakes eny varrenty, expressed or faplfed, concerning the examinations and corrective aeasures described in this Ovner's Report. Furthermore, neither the Inspector nor hia eaployer shall be 'liable In eny freer for any personal injury or property daaege or a loaa of eny kfnd arising fry or ccxnected vith this Inspection.

I Cceaiss fons NB N I I inspectors Si ture National Board, State, Providence, and Endorses>>nts I I I

Date 19~ I

FOHN NIS-2 ONIERS REPORT FOR REPAIRS OR REPLACENENTS As Required by the Provfsfons of the ASHE Code Section XI

1. Oewr Fior I r8 f t Date 04 02 99

~ ach Fl. 33408 Sheet of

2. Plant Turk Pofnt Plant Unf t 4 PNO ¹: 64/9053 MO ¹: 98022142 01 97 F ride Ct Fl. 3 0 Repair Or¹anfzatfon P.O. ko.,lob No.,etc
3. Qork Perfors8ed by Florfde Poser t Lf ht Type Code Syeboi Stafsp Authorization No. N A Expfratfen Date 9760 Str F r Cit FL. 35
4. Identl f ication ef Systoat
5. ( ~ ) Applfcebl ~ Construction Code ~ 31.1 199$ Edl ~ I ~cno sAddonfa,~sa Cock Casa (8) Apptlookt ~ Edltlcn of Reetlcn NI Utilized for Repairs or Naples~to 1989 Edltlcn,~es Addenda~No cock case Identification of Coelanents Repaired or Replaced and Replaceaent Cosfponents N~ of N~ of iHanufactureri National i Other iYear i Repaired i ASHE i Coaponent Nanuf acturer l Serfel No. Board Identff fcatfon flufitf Replaced or ( Code )

I i Replaceaent iStaep i I I )~yes P~H iRELIEF VALVE IN/A IN/A I N/A TH180&2 iuHK )Replaced /No I RV.4-1426 IRELIEF VALVE IN/A iN/A IN/A ITH18081 iuHK iRepiacesent iNo RV-4.1426

7. Description of Marks 4 14 6 R P A N TH SPAR
8. toots CcndUktodl Rpdrootetlc: Pneccsotlo: Noafnai Operating Pressure Pressure~88 18 Test T68fperature 83 NF 99.012.4

Sheet 2 of 2 FORN NIS-2 (Back)

9. R~rkst S A CONNECTION lKLO INC R QJIRED.

CERTIFICATE OF COIPLIANCE Me certify that the statements sede ln the report are correct and this reptaceaent confo~ to the wies of the ASK Code,Section XI.

Type Code Syabol Steep N A Certl fiesta of ther ization No. N A Expiration Oats N A Signed e~gate 19 Orwr or r's 0 fgnee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid comaisslon issued by the Na( -nal Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Canty and eaployed 4 kurlght Nutual Insurance Conpany of Norwood, Na. have inspected the coeponents described ln this Owners Report during the period 02/01/99 to 04/02/99 end state that to the best of iy knowledge end belief, the thawr has perforaed exminations and taken corrective assures described in this Ouners Report ln accordance Nith the requlreaents of the AS% Code, Section Xl.

~ y signing this certificate neither the Inspector nor hla eaployer wakes any uarranty, expressed or laplied, concerning the exminstions and corrective aeasures described ln this Ouner's Report. Furthermore, neither the Inspector nor his eaployer shall be Ilabie ln any earner for any personal injury or property dosage or a Loss of any kind arl ~ lng frca or comected uith this inspection.

Coeai salons NB 8230 Inspecto Sl ture National Board, State, Providence, and Endorseeents 99.012.4

FORN NIS-2 OVERS REPORT FOR REPAiRS OR REPLACE)ANTS As Required by the Provisions of the ASNE Code Section Ni

1. lhaer Flori P r 8 Li ht Date 04 02 99 700 ivers l Beach Fl. 33408 of 2
2. Plant T rk P in P t Unit 4 PMO N: Vi/9040 lm N: 98022097 01 it Fl 3 Repair Orsanizatfon P.O. No.,Job No.,etc
3. ~ Performed by Fl fde Pover I Li t Type Code Symbol Steep Authori sation No.

N A N A Expi rat ien Date N A 9760 SN Street Florida Ci t FL. 33035

4. identification of Systoa: t Cool i lister tee Systee Nt Ouali ty Crmpt C 5~ (a) Applicable Construct'Ion Code e31 1 TPKK Kdftfnc,~sa Addenda,~sa Cccfa Case (a) Applfcaols Kdltlcn of Kn:ticn Kl Utflfted for Rspsfrs or Repfsc~ts fpop Kdftfcn, ffLA Addenda,~RA coda case
6. ldentif ication ef Ccefponenta Repaired or Replaced and Replacaaent Cceponents N~ of iHanufactureri National ) Other /Year i Repaired ) ASHE (

Nanuf acturer ) Serial No. Board ident ification (Built( Replaced or / code I I i Replaceeent Lstaffffp )

I I I i~res so IRELlEF VALVE iN/A iN/A IN/A ITH108083 iljNK iReplaced )No I RV.4-14 7 IRELiEF VALVE iN/A IN/A IN/A ITH18079 iWX iReplacepfpent iNo RV.4.1427

7. Description of Morkt R V RV-4-14 7 ANO REPLA NiTH SPARE.
8. Teste Conducted: Hydrostatic: P~tfc; Rcnffnf Cpslstfoo Pressure K Other VT-2 Pressure~66 ip Test Teaparaturs 83 'F 99-013-4

FORN NIS-2 (Sack)

9. Remarks: TN S CONNECTION NO IKLOINQ REOUIREO.

CERT IF I CATE OF COIPLIANCE Ne certify that the atatemnta mde in the report are correct and this replacemnt conform to the rules of the A$% Code,Section XI.

Type Code Syabol Staay N A Cert'if icate of thor'Izat'ion No N A Expiration Oate N A Signed Oner or r's 0 ignee, Title

~~ gate 19 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid cooaission issued by the National Soard of loller and Pressure Vessel inspectors and the state or Province of Oade Catty and esployed by Arkuright Nutual Insurance Coapany of Noruood, Na. have inspected the coeponents described in this Ouners Report during the period 02/01/99 to 04/02/99 and state that to the best of ey knouledge and belief, the Owwr has performd examinations and taken corrective masures described in this Ouners Report in accordance uith the requiremnts of the ASME Code,Section XI.

gy signing thi ~ certificate neither the Inspector nor hia eaployer mkes any uarr anty, expressed or iaplied, concerning the exainations and corrective masures described in this Oeer'a Report. Furtheraore, neither the Inspecter nor hfa eaployer shall be liable in any mnner for any personal injury or property damge or a loss of any kind arising fromm or comected uith this inspection.

C<<aaissi one NB 8230 N Inspecto S1 ure National Board, State, Providence, and Endorseaents Oa 99.013-4

FORN NIS.2 OVERS REPORT FOR REPAIRS OR REPENTS As Required by the Provisions of the ASNE Code Section XI

1. @acr Flori ~ r t Li t Date 04 02 99

~ ch Fl 33408

2. Plant Turk ~ Int Plant Uni t PIN ¹: 64/0381 IN ¹: 99005330 01 CR ¹:99 0344 97 S r Fl ride Cit Fl. 330 Address Repair Organization P.O. No.,Job No.,etc
3. Mark Performed by P rSLI t Typo Code Symbol Steep Author I xat I on No. N A Expiration Date N A 97 Str t F l or I C it FL. 33035
4. Ident l f icatien of System! t Cooli kater tm System ¹: Quali ty greapr 5~ Ia) Appl icable Construction Code f888 Rdtff on~ca Addenda,8~Icosa tace (81 Applfcahl ~ Rcfftfon of sectfon xl lftf1feed for Ref>>frs or Rapfac~ts fpdp Rdftfcn,~ua Addsrck~ua coda cess
6. Identification of Coaponenta Repaired or Replaced and Replacement Ccaponenta N~ of Name of (Hanufacturer National ( Other (Year ( Repaired ( ASNE (

Component Nanuf acturer ( Serial No. goard I dent i f Ication (guilt( Replaced or ( Code (

( Replacement (Steep (

I I (~Yeso (RELEIF VALVE (N/A (N/A (N/A ITK36208 (UNK (Replaced (No I RV.4 1428 (RELIFF VALVE (N/A (N/A (TK36209 Sl'K CSE 53514 (UNK (Replacement (No RV 4-1428 T 3 4

7. Description of lierkt R F A RV 4-14 8 REPLACE.

8 Taste Conducted: RVdrcatatlc; Poet>>etio: Nominal Operating Pressure Other VT-1 VT RPressu-re~88 18 Test Toot>>ratwe 83 ~

F 99-014.4

Sheet 2 of 2 FORK NIS-2 (Rack)

9. R~rksc T A CTI ON NO uEL N REOUIR CERTIFICATE OF ALLIANCE Me certify that the statcaents aede in the report are correct and this replaceaent conforae to the rules of the ASNE Code, Section XI.

Type Code Syabol Steep Certificate of Signed thorization Owwr or r'e No.

eeignee, N

Title A

~~ Expiration Date Date N A 19 ~5 CERTIFICATE OF IKSERVICE INSPECTION I, the undersigned, holding a valid coeaission issued by the National goerd of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and ocploycd by Arkuright Mutual insurance Ccepnny of Noruood, Ha. have inspected the cocponents described in this Seers Report during the period 03/19/99 to 04/02/99 and state that to the best of ay knouledge and belief, the Owwr has perforaed exm(nations and taken corrective aeaeures described in this Owners Report in accordance Kith the requir~ts of the ASHE Code,Section XI.

Sy signing this certificate neither the Inspector nor hia eaployer aakes any Nerranty, expressed or iiplied, concerning the examinations and corrective aeasures described in this Owwr's Report. Furtheraore, neither the Inspector nor hie esployer shall be liable in any asrxwr for any personal Iniury or property daaage or ~ lose of any kind arising froa or ccemected Kith this inspection.

Coeaias i one Ng 8230 N Inspect s Si ture National Board, State, Providence, end Endorscaente D t 99.014-4

FORN NIS 2 OSIERS REPORT FOR REPAIRS OR REPLACENENTS As Required by the provisions of the ASNE Code Section XI

1. Owwr Flori P S Li t Date 700 Universe SI ua leach Fl. 33408 . Sheet of 2
2. Plant Turk ~ in P Unit 4 PIN ¹: 64/0382 IN ¹: 99005331 D1 CR ¹:99.0344 Florida Cit Fl. 330 Repair Organization P.O. No.,Job No.,etc
3. Mork Perfonaed by F fde Po5der 8 Li t Type Code STekoi Staefp N A Authorization No. N A Expiration Date N A 9760 tr F pride it FL 330
4. Identification of Systee: t Cooli Mater S tee Systea ¹:
5. (a) Appl icabl ~ Construction Code $ 31.1 1555 Editfon,~ua Addenda,~ua Code Case (s) Appfioaul ~ Edftfon ol caotfon xl utf1 ized for Repairs or Repfsocmnts fpcp Edftfut,~sa Ackfenda,~sa cade cess
6. Identification of Coaponents Repaired or Replaced and Repiacaaent Coeponents N~ of Nay of Nanufacturer National ) Other /Year i Repaired i ASNE i Coeponent Nanufacturer Serial No. Board Identification )Qu)tt( Replaced or ( Code (

i Repiaceeent IStaep I I I i~res so IRELIEF VALVE IN/A 1N/A JN/A iTH18085 JUNK ) Replaced )No I RV.C.1429 IRELIEF VALVE IN/A IN/A IN/A tTHI8082 IUW'Replaceeent (No RV.C-1429

7. Description of Morkt R I F VALVE RV.4-1429 AND REPLACE ARITH SPARE VAL
8. Tests Conducted: Hydrostatic: Pnelwacfot'uefnsf Cperatlnp pressure x

~

Other VT-2 Pressure~6$ id Teat Toeperatura 83 F 99.015-4

Sheet 2 of 2 FORN NIS 2 <Back)

9. R~rkst T S A RECT ON NO & REQUIR COMPLIANCE CERTIFICATE OF Qe certify that the statements Wade in the report are correct and thfs replacoaont conforae to the rules of the AQK Code, Sect)on Xl.

Type Code Syabol Steep N A Certificate of Author)sat)on No. N A Expl rat I on Date N A Signed Queer Ovne a Designee, tie Date r/ ~ 19~

CERTIFICATE OF INSERVICE INSPECTION I, the mdersfgned, holding a valid coma)as)on issued by the National Board of Boiler and Pressure Vessel inspectors and the state oI Province of Dade Catty and eaployed by Arkurfght Nutual Insur ance Company of Noruood, Na. have inspected the components described in this Ouners Report during the period . 03/19/99 to 04/02/99 and state that to the beat of Iay kncwledge and belief, the Owwr has perforjaed exes)nat)ons and taken corrective maaures described fn this Oners Report fn accordance N)th the requirements of the ASNE Code,Section XI.

By sfgning this certificate neither the Inspector nor hia eeployer sakes any warranty, expressed or illpL l ed/ concerning the a~)net) one and correct l ve measures described f n this Owwr ' Report . Furthermore, neither the Inspector nor his aaployar shaLL be Liable fn any esawr for any personal fnjury or proper ty dmaage or ~ Loss of any kind arfsfng from or corrected ufth thfs inspection.

Coax)as)one NB 8230 N I I tor f Nwture National Board, State, Providence, and Endorseoents Dat 99.015-4

C FORM MISE OWNERS REPORT FOR REPA(RS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Florida Power & Light Date Noma 700 Universe Blvd. Juno Beach, FL 33408 Sheet of Turkey Point Phnt Unit WO¹: 9800547901 CR>>: 97.1377 9760 SW 344 Street Florkia City, FL 33035 Addraaa Ra pair Organlaadon, p.O. No, Job No. otc.

~

3. Work Performed by Florida Power & L ht NIA Type Code Symbol Stamp Authorization Number N/A 9760 SW 344 Street Florida City, FL 33035 Expiration Date N/A
4. IdentiTication of System: Com nt Cooli Water S tern System ¹: 30 Quality Group
5. (a) Applicable Construction Code B31.1 19 55 Edition, N/A Addenda, N/A Code Case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 19 89 Edition, N/A Addenda, N<16-1 Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Manufacturer National Other Year Replaced, or Stamp Component Manufacturer Serial Number Board IdentNcation Built Replacememt Yes/No CHECK VALVE(1 BONNEY FORGE N/A N/A 4721A - STK CODE 222259 UNK REPLACEMENT NO 1/2") MODEL 1 UTC 422387 1/2"9HL~SW PIPE (1 1/2") NIA NIA NIA STK CDE 30687-ASME SA106 UNK REPlACEMENT NO UTC 417701 CARBON STEEL ELBOW (1 1/2") N/A N/A N/A STK CDE 34037-ASME SA105 UNK REPlACEMENT NO UTC 422200 NUTS (8) HEAVY NIA N/A N/A STK CDE 27840-UTC 415395 UNK EPIACEMENT NO HEX, STUDS (4) STK CDE 29501-UTC 424097 FIANGE N/A STK CDE 102064 UNK EPLACEMENT NO UTC 422481-ASME SA-105
7. Descrtpthn of Work:

REPLACED VALVE4721A INCLUDING PIPING, ELBOW, FLANGE, 8 NUTS AND 4 STUDS. CODE CASE N-41 6-1 WAS INVOKED FOR THIS REPLACEMENT ACTIVITY. LEAKAGETEST PERFORMED UNDER PRESSURE TEST 04CCWM315-L41.

8. Tests Conducted: Pressure Pneumatic Nominal Operating Pressure X Other VT-1,VT-2,PT Pressure 88 pslg Test Temperature 83 deg F

Sheet 2 of 2 FORM NIS.2 IBack)

ALI. WELDING PERFORMED IN ACCORDANCE WITH APPROVED PLANT PROCEDURES.

CERTIFICATE OF COMPLIANCE We certifiy that the statements made in the report ere correct and this REPLACEMENT conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp N/A Certificate of t orization No N/A Expiration Date: N/A Signed Owner or Owner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned. holding a valid commission issued by the Nedonal Board of Boiler and Pressure Vessel Inspectors and the state or Province of Dade County and employed by Arkwright Mutual Insurance Company of Norwood, Ma. have inspected the components described in this Owners Report during the period of 3/12/98 to ¹/2/99 and state that to the best of my knowledge and belief, the Owner has performed examinations end token corrective measures described in this Owners'eport in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations end corrective measures described in this Owners'eport. Furthermore, neither the Inspector nor his employer sheii be liable in any manner for any personal Injury or property damage or a loss of any kind arising from or connected with this spection.

NB 8230 IN)ill Insp c or's ture risdonsl Board, State, Provklence, end Endorsements Date 99-016.¹

FORN NlS-2 QSKRS REPORT FOR REPAlRS OR REPLACENENTS Aa Required by the Proviaiona of the AQK Code Section Nl

1. Ouner Flori P r S Li t Date 04 03 99
2. Plant Turk P fnt Plant Unit 4 PVO ¹: 64/6455 VO ¹: 98005403 01 CR ¹:97 1377 Repair Or¹anixation P.O. No.,Job No.,etc
3. Mork Perforeed iy Type Code Syafbol Steep N A Authoriaation No. N A Expiration Date S r Fl ri Ci FL
4. identification of Syatm~ t Cooti Va er tea Syatea ¹g Ouat i ty Cr~! C
5. ia) Applicable Cenatruction Code TCNN Ndltlen,~eA Addende,+A Cede Csee ib) Applicabl ~ Edition of Section Xl Utilized for Repaira or Reptaceeenta 1959 Edition,~Addenda,+~Code Caae
6. identification ef Coaponenta Repaired or Replaced and Replace Coaponenta N~ of Naae of (Nanufacturer( National ( Other (Tear ) R~ired Coaponent Nanufacturer ( Serial No. Board ident i f ication (Built( Replaced or ( Cofge )

I ) Replaceaent )Staofp (

I I iTesrcee (CNECK VALVE I BONNET FORGE IN/A )N/A )4-721C STK CE 222259 UNK ) Replaceeent (No 1 1 '9N ~ 4 7 (PlPE <1 1/2") )N/A (STK aeE 30607-ASNE SA106 )UNK ) Replaceflent )

No I UTC 417701 CAR ST E (ELBiRg l1 1/2a) IN/A )N/A )STK CME 34037 AQ% SA105 )UNK )Replaceeent )No I 4

)FLANOE )N/A IN/A ) N/A ) STK CCIE 102064 (LWK ) Replec~t )

No 4 1 SA-1

7. Description of Vorkg R 4. N TN R P T V TY T T 04..30 1 ..01.

N. Tests ccndectsdc Ntdrsststie: pnsmtfc: Ncnfnel cperetfns pressers N 99.017-4

FDOI NIS.R (Sack)

9. Neearkac CKNT1$ 1CATK OF COOLIANCE Qe certify that \he ~ cat~to leads ln che roper'I ere correct and thfe repfeceaent conf~ to che ruLes of cho i'ode, Sestfcn Xl.

Type Code Syabof Stoa¹ Certificate of i@ation No. Kxpfratfon Date 4eler C~4r~~

4elerIe Deef¹lse, Tftl~

~~~ DaCe 2 CKNTIFICATE OF INSKNVICE INN9KCTIIXI 1, the Ieldersfsned, holding ~ vaild ~fssfon issued by the Naticnai Soard of Soiler end Pressure veeseL inspectors end the state or Province of Dade CCIelty and eeployed by Arkwrfsht NutuaL lnswance Ccepeny of Norwood, Na. have inspected the coaponllta deecrfbed fn this osiers Nefort dwins the perfod D3/1R/99 to 04/D91/90 and etsce that te the bast of %g knowLedge end beLlefg the owner haa perfonaed txMfnetfone end takm corrective mee~ described fn this osiers Nape>>t ln accordance with the recsIf~ta of the AQK code, Section Xl ~

Sy ef¹dnS this certlf fcate neither tha inspector noc his eepLoyer aakae any I¹rranty, expressed or fapLfed9 concernfni the eamfnatfona and corrective ~swee described ln this 4eler9a Neport. Fwchereore9 nefther the inspector nor hie ~Layer shaLL be Liable fn any macr for any persINlaL injury or property dcweye or a toes ef any kind arfafnS frtm or camected with this fnepectfm.

Comf se f one Inspectors Sl ture Natfonai Soar49 State, Providence, and Kndors~cs Date 99.017-4

FORM NIS.2 OMNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASNE Code Section XI

1. Owner Florida Power t Li ht Date 04 07 99 Name 700 Universe Blvd. Jum Beach Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Uni t PMO ZI: 64/6212 MO fft 98003506 01 CR B:98-0254 9760 SM 344 Street Florida Cit Fl. 33035 Address Repair Organization P.O. Mo.,Job No.,etc
3. Mork Performed by Florida Power B Li ht Type Code Symbol Stamp N A Authorization No. N A Expiration Date N A 9760 SU 344 Street Florida Cit FL. 33035 Adcfress 4~ Identification of System: Feedwater S stem System S: /4 Dual I ty Group: C 5 ~ (~) Applicable Construction Code 831.1 T955 Edition,~a A Addenda,~s A code case (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition,~MA Addenda,N416-1 Code Case
6. Identification of Coayonents Repaired or Replaced and Replacement Cceyonents Name of Noae of }Manufacturer} National Other }Year } Repaired } ASNE }

Cadent Manufacturer } Serial No. Board Identification }Bui(t} Replaced or ', Code }

} Replacement }Staap }

} } i~tee uol

}NUTS (I) IN/A }N/A }STK CODE 27975 }UHK }Replacement }Mo I

UTC 409569 I

}

}STUDS (2) IN/A }M/A }H/A }STK CODE 28014 }UHK } Replacement }

Ho I UTC 410522 }

}STUDS (4) IH/A }M/A }STK CCOE 28031 }UHK }Replacement }Mo UTC 370211 I

} I

}STUFFING BOX COVER }N/A }N/A }STK CODE 203937 }

UNK" } Replacement } No UTC 423760 }

} }

I

7. Description of Mork: REPLACED STUFFING COVER 4 NUTS AMD 6 STUDS ON CV-4-2902.

CODE CASE N ~ 416-1 HAS INVOKED FOR THIS REPAIR ACTIVITY.

SYSTEM LEAKAGE PERFORMED UMDER 04-FU 7434-L 01.

. Tests Conducted: Hydrostatic: Pneunatic: Nominal Operating Pressure other vi.l vT.2 oressure~98D ia Test Teettereture 80 dF 99.018.4

Sheet 2 of 2 FORN NIS-2 <Back)

9. Remarks: NECHANICAL CONNECTION MELD REPAIR OF STUFFING BOX COVER.

CERT IF I CATE OF COMPLIANCE Me certify that the statements made in the report are correct and this replacement conforms to the rules of the ASHE Code, Section Xl.

Type Code Symbol Stamp N A Certificate of Authorization No. N A Expiration Date N A Signed ~4~vZr ~ Date C~ Orner r Orner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid comnission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or province of Dade comty and enpioyed by ArkNright Mutual Insurance Cerpany of Norgood, Na. have inspected the cccponents described in this Osmers Report during the period 03/12/98 to 03/07/99 and state that to the best of my knowledge and belief, the Ouner has performed examinations and taken corrective measures described in this Ouners Report in accordance with the requirements of the ASNE Code,Section XI.

By signing this certificate neither the Inspector nor his eayioyer makes any Marranty, expressed or implied, concerning the examinations and corrective measures described in this OMner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected Mith this inspection.

Coamissions NB 8230 N I I Inspecto Si ure National Board, State, Providence, and Endorsements (

Date 19/ P 99.018.4

FORH NIS 2 ONMERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the Provisions of the ASHE Code Section XI

1. Ower Florida PoMer 8 Li ht Date OC 07 99 700 Universe Blvd. Jwm Beach Fl. 33C08 Sheet of 2 Address
2. Plant Turks Point Plant Uni t 4 PlJO ¹: 64/7458 NO ¹: 98011891 01 9760 SM 3C4 Street Florida Clt Fl. 33035 Address Repair Organization P.O. No.,Job No.,etc
3. Work Performed by Florida Poser 8 Ll ht Type Code Symbol Stamp Authorization Mo. N A Expiration Date 9760 SM 34C Street Florida Cit FL. 33035 Address
4. Identification of Systemt Steam Generator S stem System ¹: 71 Duality Group: B 5 ( ~ ) Applicable Construction Code B31.1 1955 Edit fan,~NA Addenda,~MA Code Case (8) lippllcasle Edltlon of sectlcn xl utlllted for Rcpelrs or Replacements 1989 Ed tfloe~RA Addenda,~s A cede case
6. Identification of Components Repaired or Replaced and Replacement Components Name of (Hanufacturer( National (

Other (Year (

Repaired ( ASHE (

Hanufacturer ( Serial No. Board Identification (Built( Replaced or ( Code (

( Replacement (Staap (

I l [r~svo (SECONDARY HANNAY COVER (N/A (N/A (N/A (STK CODE 75160 1 (UMK (Replacement (No UTC 359560 I I

7. Description of ilork: REPLACED STEAN GENERATOR A SECOMDARY HANUAY COVER SYSTEH LEAKAGE TEST PERFORHED UNDER 04 HS-7222-L-01

. Tests Conducted: Nydrostatict Pneunatict Nominal Operating Pressure Test Teapersture 540 PF Other VT-2 pressure~229l ls 99-019-4

Sheet 2 of 2 FORH NIS-2 (Back)

9. Remarks: CHANI CAL CONNECTION NO uELDING REOUIRED.

CERTIFICATE OF COHPL.IANCE Me certify that the statements made in the report are correct and this replacement conforms to the rules of the ASIDE Code, Section XI.

Type Code Symbol Stamp N A Certificate of thorization No. N A Expiration Date N A Signed D.t.

&acr Ower's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid comnission issued by the NationaL Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade County and eaployed by Arkw ight Kutual Insurance Company of Korgood, Na. have inspected the components described in this &mars Report during the per iod 06/10/98 to 04/07/99 and state that to the best of my knowledge and belief, the Ower has performed examinations and taken corrective measures described in this Owers Report in accordance uith the requirements of the ASNE Code,Section XI.

By signing this certificate neither the Inspector nor his eeployer makes any Narranty, expressed or implied, concerning the examinations and corrective measures described in this Amer's Report. Furthermore, neither the Inspector nor his ecployer shall be Liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected uith this inspection.

Conmissions NB 8230 N I Inspecto s Si ture National Board, State, Providence, and Endorsements Date yC 99.019. C

FORH NIS-2 OMNERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the Provisions of the ASHE Code Section XI

1. Ckner Florida Pouer B Li ht Date 04 07 99 70D Universe Blvd. Jwm Beach Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Uni t 4 PMO ¹: 64/5903 QO ¹: 98001029 01 9760 SM 344 Street Florida Cit Fl. 33035 Address Repair Organization P.O. No.,Job No.,etc
3. llork Performed by Florida Po~er g Li ht Type Code Syaboi Stamp N A Authorization No.

Expiration Date N A 9760 SM 344 Street Florida Cit FL. 33035 Address 4~ Identification of System: Emer enc Feechrater S stem System ¹: 75 Quality Group: C

5. (a) Applicable Construction Code 831.1 f999 Edftfcn,~MA Ackknde,M~ACcde Case (U) Afpcfcakce Edltlocc of section xl Utllltccf for Repairs or Replacnaents 1999 Edit(cn,~e A Ackfende,a~a code case
6. Identification of Conyonents Repaired or Replaced and Replacement Components 1

Name of Name of IHanufacturerl National I Other lyear l Repaired I ASHE l Conponent Hanufacturer [ Serial No. Board Identification (Built) Replaced or t Code (

I I I Replacement tstanp I I I I /~Yes Mo IRON THREADED I N/A )N/A ISTK CODE 204436 1

) UNK f Replacement ) No

)

9 STUDS FABRICATED UTC 400981

7. Description of Mork: REPLACED 9 STUDS ON CV.4.2816.

8~ Tests Conducted: Hydrostatic: Pneunat ic: Nominal Operat ing Pressure 4F

~O-<

(q

Sheet 2 of 2 FORH NIS-2 (Back)

9. Remarks: HECHANICAL CONHECTION NO MELDING REGUIRED.

CERTIFICATE OF CONPLIAHCE lie certify that the statements made in the report are correct and this replacement conforms to the rules of the ASHE Code, Section XI.

Type Code Symbol Stamp Certificate of Authorization No. N A Expiration Date N A Signed Date CI 0 r or r's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid conmisslon issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and employed by Arkuright Hutual Insurance Company of Norwood, Na. have inspected the components described in this Owners Report during the period 01/22/98 to 04/07/99 and state that to the best of my knouledge and belief, the Ouner has performed examinations and taken corrective measures described In this &rners Report in accordance uith the requirements of the ASHE Code, Section Xl.

By signing this certificate neither the Inspector nor his erpioyer makes any Harranty, expressed or ispiied, concerning the examinations and corrective measures described in this IhaM.r's Report. Furthermore, neither the Inspector nor his eepioyer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or c onnected uith this inspection. I I

I I

I Comnissions NB 8230 N I I Inspect rs S ture Hational Board, State, Providence, and Endorsements Date 99.020-C

FORM NIS-2 OMHERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASHE Code Section XI

1. thner Florida Power t Li ht Date 04 07 99 700 Universe Blvd. Jmm Beach Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Uni t 4 PNO ¹: 69/7112 MO ¹: 98010491 01 CR ¹:98 0276 97 SM 344 Street Florida Cit Fl. 33035 Address Repair Organization P.O. Mo.,Job Mo.,etc
3. Mork Performed by Florida PoMer 8 Li ht Type Code Symbol Stanp Authorization No. N A Expiration Date N A 9760 SM 344 Street Florida Cit FL. 33035 Address
4. Identification of System: Emer enc Feedsater S stem System ¹t 75 Oual i ty Group: C 5~ (a) Applicable Construe't Ion Code B31.1 1955 Nd1ttoo,~NA Adderrde,~NA code case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition,~NA Addenda,N416-1 Code Case
6. Identification of Components Repaired or Replaced and Replacement Coaponents Name of Name of (Hanufacturer( National ( Other (Year ( Repaired ( ASHE (

Coaponent Hanufacturer ( Serial No. Board Identification (Built( Replaced or ( Code (

( Replacement (Stamp (

I I (~Yes Mo (PIPE ~ CARBON STEEL (N/A (H/A (M/A ISTK CODE 30635 I (UHK (Replacement (Mo (SCHEDULE 80 UTC 416324 (ELBOMN CARBON STEEL IN/A IH/A ISTK CODE 33902 1 (UMK (Replacement (Mo (90 DEGREE UTC 416323

7. Description of Qorkt REPLACED SECTION OF STEAN SUPPLY PIPING DOUMSTREAH OF VAI.VE AFSS ~ 4-004.

CODE CASE N-416-1 'MAS INVOKED FOR THIS llELDED REPLACEHEMT ACTIVITY t PRESSURE TESTING PERFORMED UNDER PRESSURE TEST PACKAGE:

8. Tests Conducted: Hydrostatict Other VT-2 VT-3 Pneunattc:

Pressure~940 04-AFll 7504-L-01.

15 Nominal Operating Pressure Test Toopereture 296 4F 99.021-4

fORk M1$ .2 (Back)

9. Remarks: ALL MELDING PERFORKED IN ACCORDAMCE MITH THE FPL MELO CONTROL MANUAL.

CSE CASE K 416-1 LQS INVOKED FOR THIS MELDED REPI.ACEHENT ACTIVITY.

CERTIFICATE OF COHPLIAMCE Me certify that the statements made in the report are correct and this replacement conforms to the rules of the ASHE Code, Section Xl.

Type Code Symbol Stamp Certificate of Authorization Ko. N A Expiration Dat N A Sig~ D.t. Y 19 ~+

Ower o Ower'esignee, Title CERTIF ICA'TE OF IMSERVICE INSPECTION I, the undersigned, holding a valid coamission issued by the Mational Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade County and employed by ArkNright Mutual Insurance company of Norgood, Na. have inspected the components described in this Owners Report during the period 05/19/98 to 04/07/99 and state that to the best of my knowledge and belief, the Ower has performed examinations and taken corrective measures described in this Ow>>rs Report in accordance uith the requirements of the ASHE Code, Sect ion Xl.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this ~r's Report. Furthermore, neither the Inspector nor his eayloyer shaLL be Liable in any manner for any personal inJury or property damage or a loss of any kind arising from or connected Kith this inspection.

tenmissions sa 8230 ii i inspect s Si ture sationsi Board, state providenc,e, srd Endorsements Date 99-021-4

FORM NIS-2 OUNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASNE Code Section XI

1. fldner Florida PoMer C Ll ht Date 04 07 99 700 Universe Blvd. Juno Beach FL. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Unit PMO ¹: 64/0067 MO ¹: 99003180 01 9760 344 Street Florida Cit Fl. 33035 Address RePair Organization P.O. Mo.sJob Mo.,etc
5. Uork Performed by Florida Power 8 Li ht Type Code Symbol Stanp Authoritation No. N A Expiration Date N A 9760 SM 344 Street Florida Cit FL. 33035 Address
4. Identification of System: Emer enc Feedgdeter S stem System ¹: 75 Dual I ty Group; C
5. (a) Applicable Construction Code 831.1 1955 gdssssn,~ss sddends,~ss code case (b) Applicable Edition of Section Xl Utilized for Repairs or Replacements 1989 Edition,~MA Addenda,N416-1 Code Case

. Identification of Components Repaired or Replaced and Replacement Components Name of Name of (Manufacturer( National Other (Year ( Repaired ( ASNE (

Component Manufacturer (

Serial No. Board Identification (Built( Replaced or ( Code (

( Replacement (Stamp (

I I IY~es No (GATE VALVE IPAC IF I C (09 2 2 IN/A ISTK CODE 195717 1 (UHK (Replacement (No (4gg UTC 392915 (PIPE CARBOM STEEL (UHK IN/A IN/A ISTK CODE 30635 (UHK (Replacement (Ho (SCHEDULE 80 UTC 416324

7. Description of Morkt ADDITION OF ISOLATIOM VALVE AFSS-4-010 TO TRAIH 2 AFM SYSTEN.

CODE CASE N-416-1 MAS INVOKED FOR THIS MELDED REPLACEMENT ACTIVITY.

LEAKAGE TEST PERFORMED UNDER PRESSURE TEST 04-AFll-7504-L-01.

. Tests Conducted: Hydrostatic: Pneunatic: Nominal Operating Pressure Other VT-2 gresssre~OCO Sg Test Tenperature 296 'F 99.022-4

Sheet 2 of 2 FORH NIS-2 (Back)

9. Remarks: ALL MELDING PERFORMED IM ACCORDANCE NITH THE FPL MELD CONTROL HANUAL.

CCOE CASE N.416-1 l!AS INVOKED FOR THIS IIELDED REPLACEHEMT ACTIVITY.

CERTIFICATE OF COHPLIAHCE Ne certify that the statements made in the report are correct and this replacement conforms to the rules of the ASME Code, Section XI. I I

I Type Cod Symbol Staap N A I I

Certific~ie of uthoriz tion Mo. N A Expiration Date N A

~

I Signed Owner Owner s Designee, 4/~~

Title a ~C Date Yr 19 CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid conmlsslon issued by the National Board of Boiler snd Pressure Vessel inspectors and the state or Province of Dade Cmmty and employed by Arkwright Mutual Insurance Conpany of Norwood, Ha. have inspected the components described in this Owners Report during the period 02/24/99 to 04/07/99 snd state that to the best of my knowledge snd belief, the Owner hss performed examinations snd taken corrective measures described in this Owners Report in accordance with the requirements of the ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Implied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his eaptoyer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Conmissions HB 8230 N I Inspec ors 'ature National Board, State, Providence, and Endorsements Date

/C 99.022.4

FORH NIS 2 OSIERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the Provisions of the ASHE Code Section XI

1. Owner Florida Power t Li ht Date 700 Universe Blvd. Jmo Beach Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Uni t 4 PQO gt 64/7733 NO g: 9801173801 CR S:98.0847 9760 SM 344 Street Florida Cit Fl. 33035 Address Repair Organization P.O. No.,Job No.,etc
3. Mor k Performed by Florida Power t Li ht Type Code Symbol Stamp Authorization No. N A Expiration Date N A 9760 SU 344 Street Florida Cit FL. 33035 Address
4. Identification of System: CVCS Char I 8 Letdown S stem System II: 47 Quality Group: B
5. (a) Applicable Construction Code B31.1 f955 Edftfon.~ps Addenda,~NA code Case (hf Appllcshl ~ Edition of section xf Utflfted for Repairs or Replacements f989 Edition,~s A Addenda,ffs'ls-i code case
6. Identification of Co3yonents Repaired or Replaced and Replacement Conponents Name of Name of (Hanufacturer( National Other (Year ( Repaired ( ASHE (

Ccafponent Hanufacturer ( Serial No. Board Identification (Built( Replaced or ( Code 3I

( Replacement (Staf3p (

I I iTes/eso (PIPE, 316 S.S (N/A (N/A IN/A ISTK CODE 30938 1 (UNK (Replacement (No UTC 374075 (

VALVE 2w GLOBE (ROCKNELL EDMARDS (N/A IN/A (STK CODE 53135 1 JUNK (Replacement (No UTC 423076 I (

7. Description of Qorkt REPLACED VALVE 4-2938.

CODE CASE N ~ 416-1 MAS INVOKED FOR THIS REPLACEHENT ACTIVITY.

LEAKAGE TEST PERFORHED UNDER PRESSURE TEST 04-CVCS-4764.L-01.

. Tests Conducted: Hydrostatic: Pneunatic: Nominal Operating Pressure other NT-2 NT-3 pT pressure~2soo TE Test Tospersture 93 99.023.4

Sheet 2 of 2 FORH NIS-2 (Back)

9. Remarks: ALL MELOING PERFORHEO IN ACCOROANCE IJITN THE FPL ilELO CONTROL HANUAL.

CQ)E CASE N C16 1 WAS INVOKED FOR THIS REPLACEHENET ACTIVITY.

CERTIFICATE OF COHPLIANCE Me certffy that the statements made fn the report are correct and thfs replacement conforms to the rules of the ASHE Code, Section Xl.

Type Code Syshol Stamp N A Certificate of Authorization No. N A Expiration Date N A Signed Oste 19~ I Owner or Owner9s esfgnee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid cotllnissfon issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Cmmty and eapioyed by Arkwright Hutual Insurance Company of Norwood, Ha. have inspected the components described fn this Owners Report during the perfod 06/26/98 to 04/09/99 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASHE Code, Section Xl.

By signing this certificate neither the Inspector nor his eepioyer makes any warranty, expressed or implied, concerning the examinations and correctfve measures descrfbed fn this Owner's Report. Furthermore, nefther the Inspector nor his employer shall be liable fn any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection. I I

l 1

Comafssfons NB 8230 N I I Inspector Signet e National Board, State, Providence, and Endorsements I I

I Date I I

I 99.023.4

FORH NIS 2 OWNERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the provisions of the ASHE Code Section XI

1. Ouner Florida Pover S Li ht Date 700 Universe Blvd. Jum Beach Fl. 33408 Sheet 1 of 2 Address
2. Plant Turke Point Plant Uni t 4 PWO ¹: 64/5314 WO ¹: 97022798 01 9760 SW 3C4 Street Florida Cit Fl. 33035 Address Repair Organization P.O, NoJob Noetc
3. Work Performed by Florfds Po~er B Lf ht Type Code Symbol Stamp N A Authorization Ilo. N A Expiration Da'te N A 9760 SW 344 Street Florida Cft FL. 33035 Address
4. Identification of System: Nafn Steam S stem System ¹: 72 Quality Gra~t B
5. (a) Applicable Construction Code B31.1 f955 Edftfen,~ss Addenda,~ua code cess (u) Applicable Edition of section xl utllited for Repairs er Replacements f959 Edftton,~u A Addenda,~s A code case
6. Identification of Coeponents Repaired or RepLaced and RepLacement Components Name of Name of )Nanufacturer) National ) Other )Year ) Repaired ) ASHE )

Coeponent Nanufacturer ) Serial No. Board Ident i f ication )Built) Replaced or ) Code )

) Replacement )Staff@ )

I I )Y~es BONNET CAP )N/A IM/A IM/A )STK CODE 1M425 I )UMK )Replacement )No No'SCREW, UTC 421618

7. Description of Work: REPLACED 4 BONNET CAP SCREWS ON NN-C-1401.

. Tests Conducted: Hydrostatic: Pnematfc: NominaL Operat fng Pressure Other VT-1 Pressure~N A lc Test Tmepersture MA mF 99.024.4

Sheet 2 of 2 FORH NIS-2 <Back)

9. Remarks: NECHANICAL CONNECTION NO NELDING REQUIRED.

CERTIFICATE OF CORI.IANCE Me certify that the statements made in the report are correct and this replacement conforms to the rules of the ASNE Code, Section XI.

Type Code Symbol Steap Certificate of Authorization No. N A Expiration Date N A cP Ci'~

Signed Date q9 C~ r or Ovner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid comnission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade County and employed by Arkuright Mutual Insurance Company of Korgood, Ha. have inspected the conponents described in this owners Report during the period to 04/09/99 and state that to the best of my knowledge and belief, the ~r 11/05/97 has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASIDE Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or iaylied, concerning the examinations and corrective measures described in this OwM.>>r's Report. Furthermore, neither the Inspector nor his employer shall be Liable in any manner for any personal injury or property damage or a Loss of any kind arising from or connected uith this inspection.

I I

(

Cermissions NB 8230 N I Inspect s Si ure National Board, State, Providence, and Endorsements Date 99.024.4

FORN NIS-2 OuNERS REPORT FOR REPAIRS OR REPLACENENTS As Requfred by the Provisions of the ASNE Code Section XI

1. Oner Florida Poser B Li ht Date 04 09 99 Name 700 Universe Blvd. J~ Beach Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Unit 4 puo ¹: 64/9114 Mo ¹: 98021632 01 9760 SM 344 Street Florida Cft Fl. 33D35 Address Repair OrBanization P.O. No.,Job No.,etc I. Mork Perforaid by Florfda Pcwer B Li ht Type Code Syafboi Stafsp N A Authorization No. N A Expiration Date N A 9760 SM 344 Street Florfda Cft FL. 33035
4. Identfffcatfon of system! CVcS Char I 8 Letddwn S tefa Systoa ¹: 47 oualfty Group: B
5. (a) Applicabl ~ Construction Code B31.1 1900 Edit ion,~aa Addenda,~sa Cods Case ia) Apptiosnt ~ Edition of satoi onxl utl littd for Repairs or Replaoesents 1909 Edition,~aa Adderde,xsls-l code case
6. Identfffcatfon of Coeponents Repaired or Replaced and Replacoaent Components BIVALVE Name of Name of iNonufactureri Notional i Other i Year i Repaired i ASHE )

Ccwponent Nanuf acturer i Serial No. Board Identff fcatfon (Buflt( Replaced or / Code I I ) Replaceaent )Stamp I I I I i~res So IP IPE ~ 316 iN/A IN/A (N/A )STK CODE 30938 1 iUNK (Replacement (No UTC 374075 2" GLOBE )

ROCKMELL-EDMARDS i N/A IN/A ISTK CODE 53135 1 JUNK )Replacement iNo UTC 423113

7. Dascriptfon ot ilork: REP A VAL 4-293A.

CX)E CASE N.416 1 NS INVOKED FOR THIS REPLACENENT ACTIVITY.

LEAKAGE TEST PERFORNED UND R PRESSURE TEST 04-CVCS.7466.L.01.

8. Tests Conducted: Hydrostatic: Pneuaotfc: Nomfnal OperatfnB Pressure other VT-2 PT prassure~2C00 10 Test Teapersture 95 'F 99-025-4

Sheet 2 of 2 FORN NIS-2 (Back)

9. Reaerkst AL MELDING PERFORNED IN ACCORDANCE NITH FPL MELD CONTROL MANUAL.

CADE CASE N 416-1 INVOKED FOR THIS REPLACENENT ACTIVITY.

CERTIFICATE OF CON'LIANCE Me certify that the statceents made in the report are correct and this replaceeent confores to the rules of the ASNE Code, Section Xl.

Type Code Syebol St~

Certificate of thorftatfon No. N A Expiration Date N A Signed Date 8-2 Ower or r's D fgnee, Tit CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a val fd costsfssfon fssucd by the Natfonal Board of Boiler and Pressure Vessel fnspectors and the state or Province of Dade Catty and esployed by Arkurfght Nutual Insurance Coapany of Norwxd, Na. have inspected the coeponents described in this Owners Report during the period 11/10/98 to 04/09/99 and state that to the beat of wy lmwledge and belief, the Ouner has perfonaed examinations and taken corrective measures described fn this Owners Report In accordance arith the requfreaents of the ASNE Code,Section XI.

By sfgning this certificate neither the Inspector nor hfs esployer cakes any uarranty, expressed or iepifed, concerning the exminatfone and corrective aeasures described in this Oeer's Report. Furtheroore, neither the Inspector nor hfa eaployer shall be liable In any earner for any personal Injury or property dwaage or ~ loss of any kind arising froa or camected ufth this Inspection.

Coaafssfons NB 8230 N I Inspect s Sf ture National Board, State, Providence, and Endorseeents Date 99.025.4

FORN NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the Provisions of the ASHE Code Section XI

1. Orner Florida PoMer 8 Li ht Da'te 04 14 99 Name 700 Universe Blvd. Jun Beach Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Uni t PWO ¹t 64/7326 WO ¹: 98011405 01 9760 SW 344 Str t Florida Cit Fl. 33035 Address Repair Oryanization P.O. No.,Job No.,etc
3. Work Performed by Florida Polfer 8 Li ht Type Code Symbol Stamp Authoritation No. N A Expiration Date N A 9760 SW 344 Street Florida Cit FL. 33D35
4. Identification of Systoe: Reactor Coolant S tee Systea ¹: 41 Duality Group: A
5. ( ~ ) Applicabt ~ Construction Code 831.1 1955 Edltltn,~oa Addenda,~NA Code Case (h> Appliaahle Edition of lection Rl util lead for Relnlrs or Repin:anent ~ 1929 Edition,~aaddenda,~atone case
6. Identification of Coaponents Repaired or Replaced and Replacement C~ts Name of Name of (Hanufacturer( National ( Other ('ear ( Repaired ( ASHE (

Cosponent Nanuf acturer (

Seri ~ l No. Board Ident I f ication (Built( Replaced or ( Code (

I ( Repiaceshent (Stafffp (

I I I it~as uo (RELIEF VALVE (CROSST IH51249 1362 INiA (UTC 407755 (UNX (Replacc&cflt (No

7. Description of Work: RENOVED VALVE RV-4-551A SERIAL ¹ 69877-01-009 AllO REPLACED IT WITH SPARE RELI F VALVE SERIAL ¹ H51249.1362.

. Tests Conducted: Hydrostatic: Pneunatict Nominal Operating Pressure

~

other VT.T VT.2 pressure~2291 TE Test Teaperature 540 F 99.026-4

FORH NIS 2 (Back)

9. Remarks: CHAMICAL COKNECT ION MO MELO I KG REOUIRED CERTIFICATE OF COHPLIAMCE Ne certify that the statements made in the report are correct and this replacement conforms to the rules of the ASHE Code, Section XI.

Type Code Symbol Stamp N A Certificate of uthorizat3 No. N A Expiration Date N A Signed Ouner or r's esignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid comalssion issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and eeployed by Arkuright Hutual Insurance Company of Noruood, Ha. have inspected the coaponents described in this ouners Report during the period 06/OC/9B to 04/09/99 and state that to the best of my knowledge and belief, the Owner ha>> performed examinations and taken corrective measures described in this OMnera Report in accordance Kith the requirements of the ASHE Code, Sect3cn XI.

By signing this certificate neither the Inspector nor his eapioyer makes any Marranty, expressed or Inplied, concerning the e~lnations and corrective measures described in this Ouner's Report. Furthermore, neither the Inspector nor his employer shall be liable in any vomer for any personal inJury or property damage or a loss of any kind arising from or connected Kith th3s inspection.

Coseissions MB 8230 N Inspect S3 ture National Board, State, Providence, and Endorsements Date 99.026-4

FORM NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACEMENTS As Required by the Provisions of the ASME Code Section XI Owner Florida Power 6d Ught Date 4/14/99 700 Universe Blvd. Juno Beach, FL 33408 Sheet of

2. Plant Turks Point Plant Unit WO¹: 98011407 01 CR¹:

9760 SW 344 Street Rorida City, FL 33035 Repair organlzs5on, p.o. rro, Job rro., ore,

3. Work Performed by Rorida Power ik U ht Type Code Symbol Stamp N/A Authorization Number NIA 9760 SW 344 Street Rorida City, FL 33035 Expiration Date NIA
4. Identification of System: Reactor Coolant S stem System ¹: 41 Quality Group
5. (s) Applicable Construction Code B31.1 1955 Edition, ///n Addenda, ///A Coda Caa (b) Applicable Edition of Section XI Utilized for Repairs or Replacements 1989 Edition, N/A Addenda, N/A Code Case
6. Identification of Components Repaired or Replaced and Replacement Components ASME Repaired, Code Name of Name of Manufacturer etio nal Other Year Replaced, or Stamp Component Manufacturer Serial Number Board Identification Built Replacememt Yes/No RELIEF VALVE CROSBY N69 8 77-00-0005 N/A STK CODE 6005063 UNK REPLACEMENT NO UTC 402804 NUT, HEAVY HEX NIA N/A STK CODE 27836 1 UNK REPLACEMENT NO (1) UTC 424347
7. Description of Work:

REMOVED VALVE RV-4-551B SERIAL ¹ 6987741-0008 AND REPLACED IT WITH SPARE RELIEF VALVE SERIAL ¹ N69877 0005. REPLACED (1) NUT ON VALVE CAP.

Pneumatic Nominal Operating Pressure X Other VT-1,VT-2 Pressure 2291 pslg Test Temperature 540 deg F 99.027-4

Sheet 2 of 2 FORM NIS-2 (Beck)

MECHANICALCONNECTION, NO WELDING REQUIRED.

CERTIFICATE OF COMPLIANCE We certifiy that the statements made in the report sre correct and this REPLACEMENT conforms to the rules of the ASME Code,Section XI.

Type Code Symbol Stamp NIA C ertificate of orization NIA Expiration Date: N/A Signed Owner or Owner's Designee, Title

~H(

CERTIRCATE OF INSERVICE INSPECTION I, the undersigned, holding a valid commission issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Dade County and employed by Arkwright Mutual Insurance Company of Norwood, Ma. have inspected the components described in this Owners Report during the period of 6/4/98 to 4/14/99 and state that to the bast of my knowledge and belief, the Owner hes performed examinations and taken corrective measures described in this Owners'eport in accordance with the requirements of ASME Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or implied, concerning the examinations and corrective measures described in this Owners'eport. Furthermore, neither the Inspector nor his employer shall be liable in any manner for any personal injury or property damage or a loss of any kind arising from or connected with this inspection.

Commissions NB 8230 {N)(l)

Ins ector'gnature National 8oard, State, Providence, and Endoraementa Date 99.027-4

FORN NIS-2 OMNERS REPORT FOR REPAIRS OR REPLACENENTS As Required by the Provisions of the ASHE Code Section Xl

1. oner Florida Pohfer B Li ht Date 04 14 99 7M Universe Blvd Jum Beach Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Unit PMO B: 64/7328 MO B: 98011409 01 97 r Florida Cit Fle 3303 Repair Organization P.O. No.,Job No.,etc
3. Mork Perforefed by Florida Pmer t Li ht Type Code Sysfbol StaJJJp N A Authorization No.

Expiration Date N A 9760 QJ 344 Street Florida Cit FL ~ 33035

4. Identification of System: Reactor Coolant S tefs Systcfa if: 41 Ouality Group: A
5. (a) Appl icabl ~ Construction Code 831.1 1555 Editicn,~ua Addenda,~sa Code Case (h) Applicahle Edition of cectlcn xi utllitad for Aapafrs or Aeptaceuante Tpgp Edttfcn,~ll A Addenda,~Nl code case
6. Identification of Coaponents Repaired or Replaced and ReplacesJent CosJponents Naee of Nme of JNanufactwer/ National / Other ]Year f Repaired J ASNE (

Coaponent Nanuf acturer Serial No. Board I dent 1 f ication ]guilt] Replaced or I Code )

(

J R~i~~t )St~ (

I J~Tes No I

IRELIEF VALVE JCROSBT [N51249 1361 JN/A ISTK COOE 53561 1 / UNK / Rap i ac scent / No UTC 407754

7. Description of Mork: R VALVE RV-4-551C SERIAL I H51249-1580 ANO REPLACE MITH SPARE RELIEF VALVE RIA 4 H51 4 .1 1

.~ Taste Conducted: Evdrostatic: Pneusatic: Nusinal operating pressure x VT-1 VT.2 Pressure~2291 ig Test Teaperature 540 'F Other 99-028-4

Sheet 2 of 2 FORK NIS.2 (Back)

9. Remarks: NECKANICAL CONNECTION .NO MELDING REDUIRED.

CERTIFICATE OF COIPLIANCE Me certify that the statements made in the report are correct and this replacement conferee to the ruLes of the ASNE Code, Section XI.

Type Code Symbol Staep N A Certificate of uthorization No. N A Expiration Date N A Signed Date x> +2 $ 9~

<~ Ower or r's esignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid cosisission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Caaty and eaployed by Arkuright Nutual Insurance Coapany of Norwood, Ha. have inspected the components described in this Owners Report during the period 06/04/98 to 04/14/99 and state that to the best of my knouledge and belief, the Ouner has performed examinations and taken corrective messwes described in this Owners Report in accordance Mith the requirements of the ASNE Code, Section Xl .

gy signing this certificate neither the Inspector nor his employer makes any uarranty, expressed or implied, concerning the examinations and corrective measures described in this Oewr's Report. Furthermore, neither the Inspector nor his employer shall be liable in any mcner for any personal inJury or property damage or ~ loss of any kind arising from 'or comected Nith this inspection.

Coca isa Iona NB 8230 N I Inspect rs tul e National Board, State, Providence, and Endorsements

( Date 99.028.4

FORN NIS-2 OWNERS REPORT FOR REPAlRS OR REPLACEHENTS As Required by the Provisions of the ASHE Code Section Xt

1. 055ner Florida Pouer t Li ht Date OC 14 99 NIMee 700 Universe Blvd. Jwa Beech Fl. 33CDB Sheet of 2 Address
2. Plant Turke Point Plant Unit 4 PWO ¹: 64/7626 WO ¹: 98012360 01 97 SW 344 Street Florida Cft Fl. 33035 Address Repafr Organfzatfon P.O. No.,Job No.,etc
3. Work Perfors5ed by Florfds Prier t Lf ht .

Type Code SY5ebot Ste55p Naia Authorftation No. N A Expiration Date N A 9760 SW 344 Street Florida Cft FL. 33035 Address

4. identification of Systea: Reactor Coolant S tefa Systers ¹I "

C1 Dual l ty Group: A

5. (a) Applicable Construction Code 831.1 1955 Edltf a~all A Addenda~INA ,ccdacasa (p) Appllcaul ~ Edltlcn of sectlcn kl utilized for kepafrs or keptaccnents 1999 Editfcn,~ks Addenda,~NA coda case
6. identification of Coaponents Repaired or Replaced and Reptaceeent Corponents N~ of N~ of IN~factu erl Natl' I Other IYear I Repaired I ASNE I Coiponent Nanuf acturer I 'Serial No. Board ldentff ication IBufttl Reptaced or I code I I I Reptaces5ent IStaep I I I I [T~res No ISNUBBERP PSA 10 I17899 IReptacee5ent INo ISPAR ISNUBBER PsA 10 IPsA I17900 IN/A IN/A IUNK IReptacement INo I SPAR
7. Description of Work: R PLACED SNUBBER 4-1054 SERIAl ¹ 15718 WlTH SERlAL ¹ 17899.

REPLACED SNUBBER 4.1055 R A ¹ WfTH SERlAL ¹ 17900.

. Tests Conducted: Hydrostatic: Pneeetf c: Nominal Operating Pressure

~

Other VT-3 Pressure~k A ik Test Tcepersture N A F 99-029.4

Sheet 2 of 2 FORN NIS-2 (Back)

9. Reaarksc NECHANICAL CONNECTION NO QELOING REQUIREO.

CERT IF I CATE OF CON9LI ANCE Ne certify that the statements made fn the rcport are correct and this replacement conforms to the rules of the ASNE Code, Section Xl.

Type Code Sy<<bol Steep Certf fiesta of Au rization No. N A Expiration Oate N A \

Signed

's

/~gr~ ~4~, 19 CNNNIr or Oesignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the csxfersfgned, holding a valid ctxaafssfon issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Oade CcxxIty and esployed by Arkurfght Mutual Insurance Company of Norwmd, Na. have inspected the cceyonents described fn this Ouners Report during the period 06/16/98 to 0/9/1/9/99 and state that to the beat of my knouledge and belief, the Ouner has performed examinations and taken corrective measures described in this Oeers Report fn accordance ufth the requirements of the ASNE Code,Section XI.

By sfgnfng this certificate neither the Inspector nor hfs employer makes any uarranty, expressed or fapl fed, concerning the examinations and corrective measures described fn this Ouner's Report. Further<<ore, neither the Inspector nor hfa eaployer shaLL be Liable in any manner for any personal fnjury or property damage or ~ Loss of any kind arising from or camected ufth this inspection.

9' Coeafssf one NB 8230 N I Inspect s Si ture National Board, State, Provfdence, and Endorsements Oa'te 99.029-19

FORH NIS-2 OUNERS REPORT FOR REPAlRS OR REPLACEHENTS As Required by the Provisions of the ASHE Code Section Xl

1. 055ner Florida Podder C Li ht Date 04 28 99 700 Universe Blvd. Jun Beach Fl. 33408 Sheet of 2 Address
2. Plant Turks Point Pl ant Unit 4 PMO ¹: 64/0988 IQ ¹: 99007993 01 9760 SU 344 Street Florida Cit Fl. 33035 Address Repair Organization P.O. No.,Job No.,etc
3. Uork Perfor555ed by Florida PoMer 8 Li ht Type Code Sy555bol St@ay Authorization No N A Expiration Date N A 9760 SM 344 Street Florida Cit FL. 33035 Address
4. 1denti f ication of System: C t Cool i Hater tm Systea ¹: 30 Ouality Grip: c 5~ (a) Applicable Cons'truct ion Code 831.1 1555 Edition,~es Addenda,p~stode toss (N) Applicable Edition of Neotltn Nl utl1 ised for Repairs or Replsoeeonts leep Editf<<,~NA Addenda,~sa Redo oooo
6. identification of Coaponents Repaired or Replaced and Replaceaent Caeponents N~ of JHanufecturerf National ( Other /Year f Repaired Coaponent Nanuf acturer ) Seri ~ l No. Board Ident i f 1 cat ion /Built/ Replaced or f Code R~l~~t J

I I ] istaep /

I I I I [~tes llo ISCREMP CAPP HEAVY NEX IN/A JN/A [ST@ CCOE 0027123 JUHX ]Replaceeent iNo UTC 383065

7. Description of Qorkt R P 1 T ON CCM HX CHANNEL HEAD COVEN Hydrostatic: patio: Ntuinal operettas pr<<sure e
8. Teste Conducted:

Pr<<sure~f5 Test Ttaperature 'F 99.030.4

Sheet 2 of FORN NtS-2 {Sack)

9. R~rkSI NECHANICAL CONNECTION NO IJELDING REQUIRED CERTIFICATE OF ~LlANCE Me certify that the stateeents aade in the repor t are correct and this repLaceeent conform to the rules of the ASNE Code, Section Xl.

Type Code SyeboL Steep N A Corti f1 A isa ion No. N A Expiration Date N A Signed Date 19+8 C~

CERT IF 1 CATE OF 1NSERVICE INSPECTI{NI 1, the undersigned, holding a vaLld comlssion issued by the National Qoard of Boiler and Pressure Vessel inspectors and the state or Province of Dade CoInty and asployed by Arkuright NutuaL 1nsurance cospany of Norwood, Na. haw inspected the cceponents described ln this {hewrs Report during the period 04/27/99 to 04/2S/99 and state that to the best of ay knowLedge end belief, the Ouner haa perforaed examinations and taken corrective asasures described ln this Oewrs Report ln accordance Nlth the requlr~ta of the ASNE Code, Section Xl.

Sy signing this certificate neither the inspector nor hia eapLoyer aakes any Narranty, expressed or lspLled, concerning the exmlnationa and corrective awswes described ln this {hawris Report. Furthereore, neither the inspector nor hla eaployer shaLL be Liable in any mceer for any personal injury or property daaage or ~ Loca of eny kind arising froa or comocted Nlth this inspection.

Cemissl ona NS 8230 N 1 lnspac rs S ture National Soard, State, Providence, and Endorseaents Date ie~F 99-030.4

FORN NIS-2 OWNERS REPORT FOR REPAIRS OR REPLACENENTS As Required by the Provisions of the ASNE Code Section Xt

1. 055ner Florida Po55er t Li ht Date 05 03 99 Name 700 Universe Stvd. Jum Reach Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Unit PIJO ¹: 64/5492 WO ¹: 97026342 01 9760 SW 344 Street Florida Cit Fl. 33035 Address Repair Organitetion P.O. No.,Job No.,etc
3. Work Perforefed by Florida Po55er S Li ht Type Code Symbol Staff@ N A Name Authorization No. N A Expiration Oats N A 9760 SW 344 Street Florida Cit FL. 33035 Address C. Identification of System: Intake Coolin Water S tern System ¹: 19 Quality Group: C
5. (a) Applicable Construction Code 831.1 1955 Edl tice,~NA Addenda,~NA Coda Case (b) Applicable Edltfcn of section xf Utilized for Repafra or Replecenenta 19R9 Editfcn.~sa Add<<xla,~na coda casa
6. Identification of Coaponents Repaired or Replaced and Replacement Ccaponents Name of Name of (Nanufacturer( National ( Other (Year ( Repaired ( ASNE (

Coefponent Nanuf acturer ( Serial No. Board Identi fication (Built( Reptaced or ( Code (

( Replacement (Staffp (

I ( /~rec No (PUNP CP98 (JOHNSTON (N/A (CP98 IST-8 (UNK (Replaced (No

(

(PIRIP CP98 (JOHNSTON IN/A IN/A (CP98 IST-4 (UNK (Replacement (No

(

(R(X)d THREADEO (N/A (N/A IN/A ISTK CODE 29507 1 JUNK (Replacement (No 13 STUDS FASRICATEO UTC 398175 I RODE THREADED (N/A (STK CODE 29507 1 (UNK (Replacement (No 7 STIR)S FASR I CATEO UTC C15470 (NUT, HEAVY HEX (40) (N/A IN/A (N/A (STK C(XIE 27861 1 (UNK (Reptacefffent (No I

UTC C20347

7. DescriPtion of Work) REPLACED THE 4B INTAKE COOLING WATER PUNP 20 STUDS ANO 40 NUTS ON THE PUNP DISCHARGE TO THE EXPANSION JOINT.

SYSTEN LEAKAGE TEST PERFORNED UNDER 04-ICW.1957-L.01.

8.~ Tests Conducted; Hydrostatic:I Pnewettct Nominal Operating Pressure Other VT-1 VT-2 pressure~f9 fs Test Teaperature 92 F 99-031-4

Sheet 2 of 2 FORN NIS-2 (Back)

9. Remarks: NECHANICAL CONNECTION NO MELDING REOUIRED CERTIFICATE OF COHPL lANCE Me certify that the statoaents made fn the report are correct and this replacement conforms to the rules of the ASNE Code, Section XI.

Type Code SymboL Stamp N A Certificate of Authorization No. N A Expiration Oate N A Signed Oats Ouner or oner's Oesfgnee, Tftle CERTIFICATE OF. INSERVICE INSPECTION I, the undersigned, haldfng ~ valid coaafssfon issued by the National board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and employed by Arkuright Nutual Insurance CaaTMny of Norwood, Na. have fnspected the components descrfbed ln thfs Owners Repart during the period 11/28/97 ta 05/03/99 and state that to the best of my knowledge and belief, the Ouner has performed exanfnatfons anct taken corrective measures described fn this (hears Report in accordance vfth the requirements of the ASNE Code,Section XI.

By signing this certificate neither the Inspectoc nor his enployer makes any uarranty, expressed or implied, concerning the examinations end corrective measures described fn this Orner's Report. Furthermore, neither the Inspector nor his employer shall be lfabL ~ ln any manner for any personal injury or property damage or a loss of any kind arising from or camected Nfth this inspection.

Cornel ssf ons NB 8230 N I Inspec ors gnature National Board, State, Providence, and Endorsements gate 99.031-4

FORN NIS 2 OWNERS REPORT FOR REPAIRS OR REPLACENENTS As Required by the Provisions of the ASNE Code Section XI

1. Ouner Florida Pohfer 8 Li ht Octa 05 03 99 700 Universe Blvd. Jam Beach Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Uni t PWO ¹: 64/5491 WO ¹: 97026341 01 9760 SW 344 Street Florida Cit Fl. 33035 Address Repair Organization P.O. No.,Job No.,etc
3. Work Performed by Florida PoMer 8 Li ht Type Code Syehol Stenp N A Authorltstion No N A Expiration Date N A 9760 SW 344 Street Florida Cit FL. 33035 Address
4. Identification of System: Intake Coolin Water S tern System ¹: 19 Quality Group: C
5. (a) Applicable Construction Code $ 31.1 1955 Edit fan,~NA Acklenda,s~aocde case (b) Appl icable Editicn of aectlcn Rl Utilized for Repairs or Replacenents 1989 Edftfcn,~sa Addenda,~sa code casa
6. Identif ication of Cosponents Repaired or Replaced and Replacement Components Name of Name of iNanufactureri National i Other iYear i Repaired i ASNE i Component Nanufacturer i Serial No. Board Identification iBuilti Replaced or i Code i i Replacement istaap i I I /~res No iVALVE, 24>>, CHECK i C0004665 iN/A iSTK CODE 52545 2 iUNK iRepiaccsoflt iNo UTC 423733 iR(X)9 THREADEO iN/A iN/A iN/A iSTK CIX)E 29507 1 iUNK i Replacement i No UTC 415400 I 18 STUDS FABRICATEO IN/A iN/A iSTK CODE 29507 iUNK iReplacement iNo i RM 9 THREADED 1

STUDS FABRICAT UTC 415470 I 2 iNUT, HEAVY HEX (23) iN/A IN/A iSTK CODE 27861 1 iUNK iReplscement i NO UTC 420347 I

iNUT, HEAVY HEX (17) IN/A iN/A iSTK CODE 27861 iUNK iReplacement iNo UTC 398174 I

7. Description of Work) REPLACED CHECK VALVE 4-50-321 20 STUDS AND 40 NUTS ON CHECK VALVE TO ELBOW FLANGE.

t SYSTEN LEAKAGE TEST PERFORNED UNDER

8. Testa Condzctad: Nydrostatic:

Other 04.ICWo1957-L-01.

VT-T VT-2 Pneunstlc:

Pressore~t7 TE Nominal Operating Pressure Test Temperature 92 99-032-4

Sheet 2 of FORN NIS.2 (Back)

9. Rerrerks: NECHANICAL CONNECTION NO MELDING REOUIRED.

CERTIFICATE OF CQIPLIANCE Me certify that the atatceenta rmde in the report are correct and this replaceeent conforrrra to the rules of the ASNE Code, Section XI.

Type Code Syrrrbol Starap N A Certificate of Au or)tati No. N A Expiration Date N A Signed Da'te Ovner or r's D ignee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid corrraiasion issued by the National Board of Boiler axt'Pressure Vessel inspectors and the state or Province of Dade Crxxrty and employed by Arkvright Nutual Insurance Company of Norvood, Na. have inspected the corrponents described in this Owers Report during the period 11/28/97 to 05/03/99 and state that to the best of rrry knovledge and belief, the Ower haa performed exarrr)nat)ons and taken corrective aeaaurea described in this Ovrera Report in accordance vith the requireaenta of the ASNE Code,Section XI.

gy signing this certificate neither the Inspector nor his err')oyer aekes any varranty9 expressed or implied, concern)ng the exm)nat)ons and corrective aeasurea described in this Ovrerra Report. Furtheraore, neither the Inspector nor hia errployer shall be liable in any rearer for any personal )njury or property daeage or ~ loss of any kind arising froa or comected vith this inspection.

Corrrrissiona NB 8230 N I lnapec rs gnature National Board, State, Providence, and Endoraeaenta Date 19~/

99.032.4

FORK NlS 2 OMNERS REPORT FOR REPALRS OR REPLACEMENTS Ae ReqNfred by the Provfeiane of the ASNE Code Section xi

1. Orrner Florida Parred S Li ht Date 05 03 99 700 Universe Blvd J~ Beach Fl. 3340LL Sheet of Addreaa
2. PLant Turk Point Plant Unf t 4 PMO 1r 64/5490 MO Nt 97026340 01 9760 SM 344 Stree Florida Cit Fl. 33035 Addreea Repair Oryenfzatian P.O. Ko.,Jab Ka.,etc
3. Mork Perfarreed by Fl ride Power S i h Type Code Syrffbol Starrfp N A Authorftatfon No. N A Exp l I'ation Date K A 9760 SM 344 Street Florida Cit FL. 33035 Addreaa
4. identification of Syetoar intake Cooli Meter S tee System Nr 19 Owl f ty Group: C S. (a) Applicable Conetructfon Code 831 1 1055 Edition,~NA Addenda,a~lends case (b) Appl fcabL ~ Editftn oi seotfan Nl utllltnl for Rslnlrs ar Repfealmllts 'less Edition,~ss Addenda,~ss code case Ldentf f fcatian of Caefpananta Repaired or Replaced and Replacoaent Caepcfnenta Nme of Naae of iNanufactureri National i Other iYear i Repaired i ASNE i Ccafponent ffanufacturer l Sel'f el ifo Saard fdentff fcatfon i8uilti Replaced or i Cade i I i Repleceaent istefrfp i I I I [T~ea No JOlNT, EXPANSION IN/A IN/A iN/A iSTK CNIE 14195 1 iUKK i Rap I ecoeent i Ko UTC 406703
7. Description of Morkc RE ANS Ol JOlNT XJ.4 1407.

SYSTELL LEAKA TEST PERFORNED UNDER 04 LCM-1957-L-0\.

L Tests conffntedf Ntdroststlo: pMlmtitr Noslnsl Operettas pressure Other VT-2 proeaure~ll fs Test Taesaereturs 92 'F 99-033-4

Sheet 2 of 2 FORM NIS-2 (Back)

9. Remarks: CHAMlCAL CONNECTlON NO MELDING REQUIRED.

CERT1FlCATE OF C(scPLfANCE Qe certify that the statements made in the report are correct and this replacement conforee to the rules of the AQK Code, Section Xl.

Type Code Symbol Stamp N A Certificate of Au+trfzatf No>> M A Expfratfon Oatt N A Signect Date ~W 5 Oeer or r's Oesfgnee, Tftle CERT1F1CATE OF LMSERVLCE 1NSPECTlON 1, the undersigned, holding a valid comfssfon issued by tht National Board of Boiler and Pressure vesseL inspectors and the state or Province of Dade Ccxaty and eeployed by ArkNrlght Mutual insurance ccepeny of Moruood, Ma. haw inspected the components described fn this ouners Report during the pet fod 11/28/97 to 05/03/99 and stett that to the best of my knowledge end belief. tht Ouner has performed examfnatfons and taken correctfve measures described in this ounars Report fn accoc dance Nf th the requirements of the ASME Code, Section Xl.

By signing thfa certff fcatt neither tht inspector nor his eeSILoyer makes any Narranty, eXPressed or isTILfed, concerning the examinations and corrective measures descrfbed fn this Ouner'S Report. Furthermore, neither the inspector nor his employer shaLL bt liabLe fn any marner for any personal fnjury or property damage or a Loss of any kind arising from or coceected Nfth this inspection.

C~fssfons MB 0 N inspect Sl ture Natfonal Board, State, Providence, end Endorscments I

Oat 99.033.

FORH NIS-2 OVNERS REPORT FOR REPAIRS OR REPLACEHENTS As Required by the Provisions of the ASNE Code Section XI

1. Owner Florida Pover 8 Li ht Date 05 2C 99 700 Universe Blvd. Jmm Beach Fl. 33C08 Sheet of 2 Address
2. Plant Turke Point Plant Unit PVO g: 64/0493 VO N: 99005668 01 CR N:99-0434 9760 SV 344 Street Florfda Cft Fl. 33035 Address Repair Organization P.O. No.,Job No.,etc
3. Vork Perforeed by Florida Pow.r 8 Lf ht Type Code Symbol Steep N A Authorization No.

Expiration Date N A 9760 SV 344 Street Florida Cft FL. 33035 Address

4. Identfffcatfon of System! Reefduel Neet Refnovat S tee System i/: 50 Oual I ty Group: B
5. (a) Applfcable Construction Code 831.1 f955 Edltlcn,~ua Addenda,I~IA Code Case (a) Appl locals Edltian of aectlcn xl Util ltcd for Repairs or Replaeeaenta 1989 Edl cion.~sa Act!ends,~aA cods case Identification of e'aae of Coeponent Coeponents Repaired or Replaced and Replacement Naae of Nanuf actursr (Kanufacturar( National

[ Serial No. Board Conponents

( Other Identif ication ty~

lguilt(

l Rep fred Replaced or i Code )

) R~iac~t )St~ i I I i~res ao 14".RHR 2401-10 (N/A IN/A (N/A (UNK tRepaired (No

7. Description of Vork: ARC STRIK S NOTED ON PIPING VERE REHOVED BY GRINDING AS REGUIRED BY CR 99-0434.
8. Tests Conducted: Hydrostatfc: Pneaet ice Nominal Operating Pressure Pressure~M A l9 Test Tceparsture 99-034-C

Sheet 2 of 2 FORK NIS.2 (Back)

9. RemarkS: NO VIOLATION OF NINIlRSI NALL THICKNESS.

CERTIFICATE OF CQIPLIANCE lie certify that the statements made in the report are correct and this repair conforms to the rules of the ASNE Code, Section XI.

Type Code Symbol Stamp Certific e of Aut ori\ I No. N A Expiration Date K A Signed 595. O.t.

r or Ouner's Designee, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding ~ valid comalsslon issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and esployed by Arkuright Nutual Insurance Company of NorMood, Na. have inspected the components described in this Owners Report during the period 03/24/99 to 05/24/99 and state that to the best of my knowledge and belief, the Ouner has performed examinations and taken corrective measures described in this Ouners Report in accordance Kith the requirements of the ASNE Code,Section XI.

By signing this certificate neither the inspector nor his espioyer makes any uarranty, expressed or implied, concerning the examinations and corrective measures described in this Ouner's Report. Furthermore, neither the Inspector nor his employer shall be Liable ln any manner for any personal injury or property damage or a Loss of any kind arising from or corrected Kith this inspection.

Coamissiona NB 8230 N I Inspectors Signet e National Board/ State, Providence, and Endorsements Date 5 99-034.4

FORH NIS-2 OMNERS REPORT FOR REPAIRS OR REPLACENENTS As Required by the Provisions of the ASNE Code Section XI

1. Oner Florida Poser t Li ht Date 05 2C 99 700 Universe Blvd. Juno Beach Fl. 33408 Sheet of 2 Address
2. Plant Turks Point Plant Uni t PMO ¹: 64/0490 MO ¹: 99005667 01 CR ¹:99 0425 9760 SM 344 Street Florida Cit Fl. 33035 Address Repair Organization P.O. No.,Job No.,etc 3o QOrk PerfOrS5ed by Florida Po5der t Li ht Type Code Symbol Stss5p N A Authorization No. N A Expiration Date N A 9760 SU Street Florida Cit FL. 33035 Address
4. Identification of System: CVCS Cher I t Letdo5n S tefs Systos ¹: C7 Quality Gru~: A
5. Is) Applicable Construction Code B31.1 f555 Edftl ~cNnA Addanda~ll A Code Caco (8> Apptlcast ~ Edltlcn of section xl utllited for Repairs or Raplacsaents Ioap Edict ~sana Addenda,s~a
6. Identification of Cosyonents Repaired or Replaced and Replaces5ent Coayonents Name of Name of (Hsnufactwer( National ( Other (Year ( Repaired ( ASNE (

Cosponent Nanufacturer (

Serial No. Board Ident ification (Built( Replaced or (

cod (

I ( Replacement (Sta555p (

I I I i~roc ao (3-CH-1401-4 N/A (N/A (N/A (UNK (Repaired (No

7. Description of llork: LI INOICATION NOTED ON PIPING VERE RENOYEO BY GRINOING AS REOUIRED BY CR 99-0426.
8. Tests ccrcsrcted prdroctatfct Ipnencstlc: Nominal Operating Pressure Other PT 99.035.4

Sheet 2 of 2 FORN NIS-2 (Back)

9. Remarksc V ATI OF NINIIRN MALL THICKNESS.

CERTIFICATE OF CONPLIANCE Me certify that the statute made In the report are correct and this repair conforms to the rules of the ASIDE Code, Section Xl.

Type Code Sy<<bol Steep N A Certif ica f ut Iz on o. Expiration Date N A Signed 19+

Oaw Ovner9a Desiywe, Title CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid coaatisaion issued by the National Board of Boiler and Pressure Vessel Inspectors and the state or Province of Dade Ctxslty and eaployed by Arkuright Nutual Insurance Cospany of Norltood9 Na. have 3napected the cceponents described In this Oawrs Report dur3ng the period 03/25/99 to 05/2C/99 and state that to the beat of tay knottledge and belief, the Oawr haa performed examinations and taken corrective <<assures described In this Oawrs Report In accordance ltlth the requirements of the AsNE Code,Section XI.

By signing this certificate neither the Inspector nor his eeployer makes any uarranty, expressed or laplled, concerning the examinations <<nd corrective measures described In th3a Orner9s Report. Furthermore, neither the Inspector nor hia eaployer ahaLL be Liable In any m<<rswr for any peraonaL Injury or property damage or ~ Loss of any kind ar3sing fro<<or cotaected ltith this inspection.

Ccxaaissiona NB 8230 N I lnspec ra Si ture National Board, State, Providence, and Endorsements I

Date 99-035.C

FORN NIS.2 OUNERS REPORT FOR REPAIRS OR REPLACENENTS As Required by the Provisions of the ASNE Code Section XI

1. Oner Florida Po55er C Li ht Date 05 25 99 700 iverse lvd. Jam Beech Fl. 33408 Sheet of 2 Address
2. Plant Turke Point Plant Uni t PMO ¹: 64/0494 QO ¹: 9900566'9 01 CR ¹:99.0426 9760 Su 344 Str t Florida Cit Fl. 33035 Address Repair OrBanization P.O. No.,Job No.,etc
3. lJor k Perforised by Florida Pouer S I ht Type Code Symbol Staap N A Authorization No. N A Expiration Date N A 9760 SM 344 Street Florida Cit FL. 33035 Address
4. Identification of System: CVCS Cher i S Letdo5n S tefe Systefe ¹: 47 Duality Oroup: A
5. (a) Applicabl ~ Construction Code B31.1 1955 Edition,~ea Addenda,~ea Coda Case lu) Appllosul ~ Edition of soutien Rl utilized for Repairs or Replaoenents 1999 Edftftn,~ua Addenda,~ua Rode ossa
6. Ident i f lest i on of Coaponents Repaired or Replaced and Repiacoeent Coeponents Naae of N~ of iNanufactureri National i Other iYear J Repaired i ASNE i Coaponent Nanufacturer i Serial No. Board identi f ication IBullt) Replaced or J Code )

I i Replaceeent istawp i I i~Yes ifo i SR.934 N/A IN/A iN/A IN/A JUNK )Repaired iNo

7. Description of Work: LINEAR INDICATION NOTED ON PIPINO. INDICATION MAS RENWED TO AN ACCEPTABLE SIZE PER CR 99-0426.
8. Tests Conducted: Hydrostatic! Pnese t I c I Nasinal Operating Pressure Other PT Pressure~N A 19 Tost Tespersture 99-036-4

Sheet 2 of 2 FORN NIS-2 (Back)

9. Remarkst NO VIOLATION OF NININN MALL THICKNESS.

CERTIFICATE OF CONPLIANCE Me certify that the statements made in the report are correct and this repair conforms to the rules of the ASNE Code, Section XI.

Type Code Sysbol Stamp Certific of ut riz i No. N A ExpiI'at'ion 0ate N A Signed Date 19+~

r or Owner's Designee, Title cI~

CERTIFICATE OF INSERVICE INSPECTION I, the undersigned, holding a valid coaaission issued by the National Board of Boiler and Pressure Vessel inspectors and the state or Province of Dade Catty and esyioyed by Arkwright Nutual Insurance Cospany of Norwood, Na. have Inspected the cosyonents described in this Owners Report during the period 03/25/99 to 05/24/99 and state that to the best of my knowledge and belief, the Owner has performed examinations and taken corrective measures described in this Owners Report in accordance with the requirements of the ASNE Code,Section XI.

By signing this certificate neither the Inspector nor his employer makes any warranty, expressed or Iaplied, concerning the examinations and corrective measures described in this Owner's Report. Furthermore, neither the Inspector nor his esployer shall be liable In any aamer for any personal injury or property damage or ~ loss of any kind arising from or comected with this inspection.

Comi as I ons NB 8230 N I lnspec ora Si ture National Board, State, Providence, and Endorsements Date 99-036-4

TURKEY POINT UNIT 4 1999 REFUELING OUTAGE Summary of Visual Examinations and Functional Testing of Snubbers

t h

t

Abstract The attached report details the snubber inspection/testing performed for Florida Power and Light Company, Turkey Point Unit 4. These tests and inspections were performed during the Spring 1999 refueling outage, between the dates of March 15, 1999 and April 7, 1999.

Snubber inspection/testing was conducted in accordance with Plant Technical Specifications as allowed under Relief Request 4 of the Third Ten Year Interval ISI Program.

TURKEY POINT NUCLEAR PLANT UNIT 4 CYCI E 18 MECHANICALSHOCK ARRESTOR FINA! REPORT Mechanical shock arrestors (snubbers) were visually inspected/handstroked and functionally tested under purchase order ¹00032190 by Basic-PSA personnel in accordance with the following plant/vendor procedures:

0-CMM-1 05.1, "Snubber Removal and Replacement" O-OSP-105.1, "Visual Inspection of IVlechanical Shock Arrestors" O-OSP-105.2, "Functional Testing for Mechanical Shock Arrestors" Technical Specification 3/4.7.6 A technical specification visual inspection, ASME Section XI VT-3 and a hand stroking was performed at the following tag locations:

4-1 000 4-1 001 4-1002 4-1 004 4-1011 4-1012 4-1013 4-1 014 4-1 015 4-1 016 4-1 017 4-1 018 4-1019 4-1020. 4-1021 4-1022 4-1086 4-1087 4-1088 4-1 089 4-1090 4-1091 4-1092 4-1 094 4-1095 4-1096 4-1097 4-1098 4-1099 A technical specification visual inspection, ASME Section XI VT-3, NO HAND STROKE, and a functional test was performed at the following tag locations:

italics indicates Safety Related (SR) Sample snubbers Bold indicates Quality Related (QR) Sample snubbers Underline indicates revious rebuilds 4-1003 4-1007 4-1008 4-1009 4-1010 4-1037 4-1042 4-1043 4-1049 4-1061 4-1093 4-1100 A technical specification visual inspection, ASME Section XI VT-3, and a hand stroking was performed at the following tag locations:

4-1 005 4-1 006 A technical specification visual inspection, ASME Section XI VT-3 and a hand stroking was performed at the following tag locations. Upon completion of the technical specification visual inspection, ASME Section XI VT-3 and the hand stroking, the snubbers were changed out with previously rebuilt and functionally tested snubbers. The removed snubbers were rebuilt and functionally tested and will be utilized as spares for future outages.

4-1052 4-1 054 4-1055 4-1 056 COMhlON/TECHASVSNVBBERSV4C18RPfCVR. DOC

0 ~ ~ ~

~

~ ~

P ~ ~

~ ~

~ 'll el I ~ ~ ~ o e ~ I ~ I

~ ~ ~

) ~ ~ I~ I

~ ~ ~ ~ ~ ~

'I ~ ~

I I ~ ' ~ ~ I

~ ~ ~ ~ ~ ~

~ ~ I '

~ ~ ' ~ ~ ~

~ ~ ~ ~ I ~ I

~ ~ ~ '

I

~ ~ ~ ~ II

~ ~ ~ ~ '

~

' ~

~

~ + ~

~

<< ~ ~

<< ~

~ ~

~ '<< I ~ I

~ ~ ~ ~

~ ~ ~ ~

I

~ ~ ' I~I

~ ~ ~ ~ '

~ I ~ ~

~ ~ ~ '

I I ~ ' ~ I

~ ~

~ ~ '

l ~ '

0

~ l ~ ~ ~ ~

~ ~ ~ ~

~ ~

~ 0 ~ ~ <<<< ~ I ~

~ ~ ~

~ I l ~ I

TURKEY POI CLEAR PLANT OUTAGE

SUMMARY

REPORT UNIT 4 1999 CYCLE 18 REFUELING OUTAGE WO 0 98012360 S S S S FUNCTIONAL T HAND- T REPLACE INSPECT INSPECT A A STROKE A TAG¹ SERIAL¹ NT /N DATE LDIMEN T  ? T VISUALSUMMARy FUNCTIONALTEST SUMMARy 4-1016 17872 N/A 3/2499 PASS PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED? No HANDSTROKED AND REINSTALLED.

LUBRICATED SPHERICAL BEARING AND LOAD PIN WITH NEOLUBE (24982').

4-1016 122 PASS 20.125 PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED?

HANDSTROKED AND REINSTALLED.

LUBRICATED SPHERICAL BEARING AND LOAD PIN WITH N-5000 (249743).

4-1017 118 PASS 20.125 PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED?

HANDSTROKED AND REINSTALLED.

LUBRICATED SPHERICAL BEARING AND LOAD PIN WITH N-5000 (24974-3).

4-1018 17420 N/A 3/2499 PASS 18 PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED? No HANDSTROKED AND REINSTALLED.

LUBRICATEDSPHERICAL BEARING AND LOAD PIN WITH NEOLUBE (24982').

~ ~

~ ~

I ~ ~

~ ~

~ 'II ~ I I ~ ~

I ~ ~ '

~ ~ ~

~ ~

~ 0 ~ '

~ ~ '

~ ~ ~ ~

~ ~ ~ '

~ ~ ~

~ I ~ ~

~ ~ I ~

~ ~ ~ I~ I

0 TURKEY PO CLEAR PLANT OUTAGE

SUMMARY

REPORT UNIT 4 1999 CYCLE 18 REFUELING OUTAGE WO ¹ 98012360 S S S S T FUNCTIONAL T HAND- T REPLACE. IN'ECT A INSPECT A A STROKE A DATE TAG g SERIAL ¹ MENT S/N DATE T T L DIMEN T  ? T VISUAL

SUMMARY

FUNCTIONALTEST

SUMMARY

~~ ~ Wl ~~

4-1086 12993 N/A PASS 27.5 PASS Yes PASS INITIALINSPECTION OF SNUBBER FUNCTIONALTEST PERFORMED? No FOUND LOAD PIN MISSING FROM STRUT END. CR 994357 ISSUED TO ADDRESS CORRECTIVE ACTIONS.

PIN WAS REINSTALLED WITH NEW COTTER PINS. SPHERICAL BEARING AND LOAD PIN LUBRICATEDWITH N-5000 (249743).

4-1087 12994 N/A PASS PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED? No HANDSTROKED AND REINSTALLED.

LUBRICATED SPHERICAL BEARING AND LOAD PIN WITH N-5000 (249743).

4-1088 12995 N/A 'PASS PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED?

HANDSTROKED AND REINSTALLED.

LUBRICATEDSPHERICAL BEARING AND LOAD PIN WITH N4000 (249743).

4-1089 12996 N/A PASS 26.625 PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED?

HANDSTROKED AND REINSTALLED.

LUBRICATEDSPHERICAL BEARING AND LOAD PIN WITH N4000 (249743).

TURKEY POI CLEAR PLANT OUTAGE

SUMMARY

REPORT UNIT 4 1999 CYCLE 18 REFUELING OUTAGE WO ¹ 98012360 S S S S FUNCTIONAL T T HAND- T A A STROKE A TAG ¹ SERIAL g MENT S/N PATE T L DIMEN T  ? T VISUAL

SUMMARY

FUNCTIONALTEST

SUMMARY

4-1090 12997 N/A PASS 27.25 PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED? No HANDSTROKED AND REINSTALLED.

LUBRICATEDSPHERICAL BEARING AND LOAD PIN WITH N4000 (249743).

4-1091 12998 N/A PASS PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED? No HANDSTROKED AND REINSTALLED.

LUBRICATEDSPHERICAL BEARING AND LOAD PIN WITH N-5000 (249743).

4-1082 12999 N/A PASS 16.5 PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED? No HANDSTROKED AND REINSTALLED.

LUBRICATED SPHERICAL BEARING AND LOAD PIN WITH N4000 (249743).

4-1094 17669 N/A 3/17/99 PASS 19.3125 PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED?

HANDSTROKED AND REINSTALLED.

LUBRICATEDSPHERICAL BEARING AND LOAD PIN WITH N4000 (24974-3).

~

~ ~

~ ~ ~

~ I ~ 'el ~ I

~ ~ ~ ~ ~ ~

~ ~ ~ ~

0 ~ '

~ ~ ~ ~ ~ ~

0 I

~ ~ I I ~ ' I~ I

~ I ~ ~

~ ~ I . ~

~ ~ ' I~ I j ~ ~ ~

~ I ~ ~

~ IC

~ ~

TURKEY POINT EAR PLANT OUTAGE

SUMMARY

REPORT UNIT 4 1999 CYCLE 18 REFUELING OUTAGE INO ¹ 98012360 S S S S T FUNCTIONAL T T HAND- T SERIAL¹ REPLACE- INSPECT A A A STROKE A TAG ¹ MENT S/N DATE T

" T L DIMEN T  ? T VISUAL

SUMMARY

FUNCTIONALTEST

SUMMARY

4-1093 17868 N/A 3/17/99 PASS 3/19/99 PASS 19.5 PASS REMOVED SNUBBER FOR FUNCTIONALTEST PERFORMED?

FUNCTIONALTESTING.

REINSTALLED, LUBRICATED STATUS PASS SPHERICAL BEARING AND LOAD PIN WITH NEOLUBE (249824) TENSION COMPRESSION CRITERIA TEST 1 72.66 89A5 TEST 2 69.04 75.82 TEST 3 0.005 0.008 .029 TEST 4 56.98 34.31 750.00 TEST SAMPLE? Yes SAMPLE CLASS NSR DATEREINSTALLED:

4-1100 29498 N/A PASS 3/23/99 PASS 10.8125 PASS REMOVED SNUBBER FOR FUNCTIONALTEST PERFORMED?

FUNCTIONALTESTING.

REINSTALLED, LUBRICATED STATUS PASS SPHERICAL BEARING AND LOAD PIN WITH N~ (249743). TENSION COMPRESSION CRITERIA TEST 1 4.95 5.13 17.5 TEST 2 4.10 2.66 17.5 TEST 3 0.010 0.011 TEST 4 5.81 17.5 TEST SAMPLE? Yes SAMPLE CLASS SR DATE REINSTALLED:

TURKEY PO UCLEAR PLANT OUTAGE

SUMMARY

REPORT UNIT 4 1999 CYCLE 18 REFUELING OUTAGE WO ¹ 98012360 S S S S VISUAL V UAL T FUNCTIONA T HAND- T REPLACE INSPECT A INSPE T A A STROKE A SERIALS MENTS/N PATE T T T  ? T VISUAL

SUMMARY

FUNCTIONALTEST

SUMMARY

L DIMEN 4-1099 17423 N/A 3/19/99 PASS 16.625 PASS Yes PASS REMOVED PIN FROM ONE END, FUNCTIONALTEST PERFORMED? No HANDSTROKED AND REINSTALLED.

LUBRICATED SPHERICAL BEARING AND LOAD PIN WITH N-5000 (249743).

~ ~

~ ~

~ r ~

~ ~

~ 'rl sl r~ ~ I ~ ' ~ I

~ ' I

~ ~ ' I~ I II II II I ~

I II' II' ~

II II

~ ~ \ ~ ~ ~ ~ ~ I

~ ' ~ ~ ~ ~ ' ~ ' I

~ ~ I I~I I II ~

l

~ ~

~ ~ I ~ ~ I I ~ ~ ~ I ~ '

I

~ ~ ' ~

I~ I I ~

I ~

I I

~ ~ ~ ~

I . I ~ ~ I ~ '

~ ~

I ~

I ~ I

~ '

~

~ ~ ~

'll

~ ~

~ ~ ~

~ ~ ~ ol

~ ~ ~ ~ ~ ~

) ~

I ~ '

I ~

4 ~ ~ I

~

' ~

~ ~ '

II ~ I II I~

I II ~ I INC I ~

~ I II

~ ' ~

~ ~ ~

~

~

~ ~

~ ~ I . I

~ I ~ ~

I ~ ~ ' ~ ~

~ ~ '

~ II I ~ ~ I ~ ~ '

~ ~

~ ~ ~

~ ' ~

~

~ ~ ~ I

~

~

~ ~

~ ~ ~ ' I ~ I

~ ~ I ~ ~ ~

~ ~ ~

~ ' I

~ ~

~ 4 I ~

~ ~

~ ~ I I I ~ ~

~ ' I I ~ ~

I~~

I II I I I I ~

~ ' ~

0 TURKEY POI CLEAR PLANT OUTAGE

SUMMARY

REPORT UNIT 4 1999 CYCLE 18 REFUELING OUTAGE WO 0 98012360 S S S S FUN TIO AL T T HAND- T VISUAL T "

SERIAL// REPLACE- INSPECT A A A STROKE A TAG // MENT S/N T T L PIMEN T  ? T VISUAL

SUMMARY

DATE a t t a \ t a t t a t t aTEST FUNCTIONAL t t a ~

SUMMARY

~ \ t a t t a t t a t \ a t t a t t a t t a t t a t t a ~ t a a a t t a t t a t t a t t a t t a t t a t t a t t a t t a t t a t t a t t a tt a t t a \ t a tt a t t a tt a t t a tt a tt a t t a t t a a a a a a a t t tt ~ \ a t \ a t t a t \ a \ t a \\ a t t a t t a \t a t t tt ~ t attattattattattattattattattattattat SPARE 15718 N/A 3/21/99 PASS 3/22/99 PASS Yes PASS REMOVED FROM 4-1054 FOR FUNCTIONALTEST PERFORMED? Yes HANDSTROKE AND FUNCTIONAL TESTING. WILLBE PlACED IN DRY STATUS PASS STORAGE FOR FUTURE USE.

~ TENSION COMPRESSION CRITERIA TEST 1 47.85 38.67 300.00 TEST 2 47.29 22.26 '00.00 TEST 3 0.006 0.007 .029 TEST 4 42.01 17.62 300.00 TEST SAMPLE? No SAMPLE CLASS N/A DATE REINSTALLED:

SPARE 7782 N/A 3/21/99 PASS 3/2289 PASS Yes PASS REMOVED FROM 41055 FOR FUNCTIONALTEST PERFORMED? Yes HANDSTROKE AND FUNCTIONAL TESTING. WILLBE PLACED IN DRY STATUS PASS STORAGE FOR FUTURE USE.

TENSION COMPRESSION CRITERIA TEST 1 35.30 49.05 TEST 2 27.36 19.01 TEST 3 0.006 0.006 TEST 4 22.32 16.76 TEST SAMPLE? No SAMPLE CLASS N/A DATE REINSTALLED:

~ ~

~

I

~ ~ ~ . ': I ~ I

~ ) I I ~ ~

~ '

~ ~

r ~ ~

~ ~

~ ~ ~ . I ~ I

~ ~

~ ~

~ I I ~ I~

TURKEY POINT UNIT 4 1999 REFUELING OUTAGE Summary of Inservice Inspection Examinations

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page:

INSERVICE INSPECI'ION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RP)

Class 1 CBEA STATUS Components EACTOR PRESSURE VESSEL N I 0 Zone Number: 4-001 S ON GT SEC. XZ T RSEH Summary Examination Area Catgy Exam A E Z 0 E Remarks Number Identification Item Ho Method Procedure T C G M R ~~ Calibration Block ~+

REF. DWG. 'O. 5614 M-4000 010000 VESSEL INTERIOR B-N-1 VT-3 NDE 4.3-24 C X - - - 03/24/1999 - VT-3 complete, NRZ.

ACCESSIBLE AREAS B13. 10 011793 VESSEL TO CLOSURE HEAD MATING B-N-1 VT-3 NDE 4.3-24 C X - - - 03/24/1999 - VT-3 complete, NRI.

SURFACE ON VESSEL B13. 10

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 2 INSERVICE INSPECTION

SUMMARY

THZRD INTERVAL, SECOND PERIOD, SECOND OUI'AGE (99RP)

Class 1 CSEA STATUS Components EACTOR COOLANT SYSTEM PRESSURIZER SURGE LINE N I 0 Zone Number: 4-016 S ON GT SEC. XZ T RSEH Summary Examination Area Catgy Exam A E Z 0 E Remarks Number Identification Item No Method Procedure T C G M R ~~ Calibration Block **

REF. DWG, NO. 5614-P-766-S SH. 2 062710 SR 400 P A VT-3 NDE 4.3-7 C - - - X 03/18/1999 - VT-3 complete, RZ (CRN Spring Hanger P1.10C VT-3 NDE 4.3-22 X - - 359), follow-up examination per CRE 97-1560. 03/28/99 - VT-3 complete, NRI following corrective action.

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 3 INSERVICE INSPECTION SULTRY THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE {99RP)

Class 1 CSEA STATUS Components EACTOR COOLANT SYSTEM PRESSURIZER SPRAY TO PRZ.

N I 0 Zone Number: 4-020 S ONGT SEC. XI T R S E H Summary Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R ** Calibration Block <<~

REP. DWG. NO. 5614 P 566 S SH 1 067700 4"-RC-1404-12 B-J PT NDE 3.3-12 C - X - - 03/21/1999 - PT complete, one acceptable PIPE TO VALVE 4-573 B9 11

~ UT-60AX NDE 5.4-10 - X - rounded indication.03/24/1999 - UT UT-70AX NDE 5.4-10 X - - - complete, geometry.

UT-38CIRC NDE 5.4-10 X-ea UT-45 N "*

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page:

INSERVICE INSPECTION SUNDRY THZRD INTERVAL, SECOND PERIOD, SECOND OUTAGE t99RP)

Class 1 CBEA STATUS Componeuts EACTOR COOLANT SYSTEM PRESSURIZER SPRAY I INE N I 0 Zone Number: 4-021 S ONGT SEC. XI T RS EH Summary Examination Area Catgy Exam A E I 0 E Remarks Number Identificat ion Item No Method Procedure T C G M R <<<<Calibration

¹ Block <<<<

REP. DWG. NO. 5614-P-566-S SH. 2 072200 4" RC 1405 11 B-J PT NDE 3.3-19 C X 03/22/1999 - PT complete, NRZ.

PIPE TO VALVE 4 572 B9. 11 UT-60AX NDE 5.4 9 X 03/23/1999 - UT complete, geometry.

UT-70AX NDE 5.4-9 X-UT-38CIRC NDE 5.4-9 X-

<<* UT-45 N <<<<

072600 4" RC 1405-15 B-J PT NDE 3.3-11 C X - - - 03/21/1999 - PT complete, NRZ.

PIPE TO ELBOW B9. 11 UT-60AX NDE 5.4-9 X - - - 03/23/1999 - UT complete, NRZ.

UT-70AX NDE 5.4-9 X-UT-38CIRC NDE 5.4-9 X

<<* UT-45 N **

120 4-RCH-36X F-A VT-3 NDE 4.3-10 C X - - - 03/20/1999 - VT-3 complete, NRZ.

SPRING HANGER F1. 10C 073200 4"-RC-1405-2) B-J PT NDE 3.3-20 C X - - - 03/23/1999 - PT complete, NRI.

PIPE TO ELBOW B9.11 UT-60AX NDE 5.4-9 - - X - 03/23/1999 - UT complete, geometry.

UT-70AX NDE 5.4-9 X UT-38CIRC NDE 5.4-9 X

    • UT-45 N **

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 5 INSERVICE INSPECTION SUYMARY THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RP)

Class 1 CSEA STATUS Components hemical and Volume Control Auxilia S ra Line N I 0 Zone Number: 4-035 S 0 N G T SEC. XI T R S E H SummarY Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R ** Calibration Block *+

REF. DWG. NO. 5614-P-782 S SH. 1 110600 2i RC 1410 24 B-J PT NDE 3.3-16 C X - - - 03/22/1999 PT complete, NRZ.

PIPE TO ELBOW B9.40 110700 2 5 -RC-14 10 25 B-J PT NDE 3.3-16 C X - - - 03/22/1999 - PT complete, NRZ.

ELBOW TO PIPE B9.40 110750 779D F-A VT-3 NDE 4.3-15 C - - - X 03/21/1999 - VT-3 complete, RZ (CRN DOUBLE ACTING RESTRAINT P1.10B VT 3 NDE 4.3-23 X - - -,99-427). 03/27/1999 - VT-3 complete, NRZ following corrective action.

k Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 6 INSERVICE INSPECTION S~~Y THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RF)

Class 1 CBEA STATUS Components RESIDUAL HEAT REMOVAL TO RC LOOP A COLD LEG N I 0 Zone Number: 4-037 S ON GT SEC. XI T RSEH Summary Examination Area Catgy Exam A E I 0 E Remarks Number Ident' ication Item No Method Procedure T C G M R ~~ Calibration Block ~~

REP. DWG. NO. 5614-P-509-S SH. 1 117350 SR-450D P-A VT-3 NDE 4.3-16 C - - - X 03/22/1999 - VT-3 complete, NRI DOUBLE ACTING RESTRAINT Pl. 10B <conditions noted were previously acceptable per NCR-86-10, NCR-215-86, NCR-360 86) .

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page:

INSERVZCE INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE {99RP)

Class 1 CSEA STATUS Components RESIDUAL HEAT REMOVAL TO RC LOOP B COLD LEG N I 0 Zone Number: 4-038 S ON GT SEC. XZ T RSEH Summary Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R ~~ Calibration Block ~~

REP. DWG. NO. 5614-P-509-$ SH. 3 121500 10%-51-1402-1 B J PT NDE 3.3-18 C X 03/22/1999 - PT complete, NRI.

VALVE 4-875E TO ELBOW B9.11 UT-60 AX NDE 5.4 2 -X- 03/24/1999 - UT complete, geometry.

UT-45LAX NDE 5.4-2 X-UT-45 CIRC NDE 5.4 2 X-

~~ UT 27 <<*

121800 10"-SZ-1402-4 B-J PT NDE 3.3-18 C X - - - 03/22/1999 - PT complete, NRI.

ELBOW TO TEE B9.11 UT-60 AX NDE 5.4-2 - - X - 03/24/1999 - UT complete, geometry.

UZ-45LAX NDE 5.4-2 X-UT-45 CIRC NDE 5.4 2 X-

    • UT-27 ++

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 8 INSERVICE INSPECTION SUGARY THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE t99RP)

Class 1 CBEA STATUS Components ESIDUAL HEAT REMOVAL TO RC LOOP C COLD LEG N I 0 Zone Number: 4-039 S ON GT SEC. XI T RSEH Summary Examination Area Catgy Exam A E I0 E Remarks Number Identification Item No Method Procedure T C G M R ~* Calibration Block ~~

REP. DWG. NO. 5614-P-509-S SH. 4 125870 8073-H-810-01 P-A VT-3 NDE 4.3-6 C - - - X 03/17/1999 - VT-3 complete, RI (no CR-DOUBLE ACTING RESTRAINT F1.10B VT-3 NDE 4.3-21 X - - - lubricate and re-exam per STD-C-011).

03/27/1999 - VT-3 complete, NRI following corrective action.

f, Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 9 INSERVICE INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RF)

Class 1 CSEA STATUS Components HEMICAL a VOLUME CONTROL TO RC LOOP C HOT LEG N I 0 Zone Number: 4-045 S 0 N G T SEC. XI T R S E H Summary Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R <<* Calibration Block ~~

REF. DWG. NO. 5614-P-782-S SH. 2 151900 3"-CH-1401-4 B-J PT NDE 3.3-13 C - - - X 03/22/1999 - PT complete, RZ PIPE TO TEE B9. 21 PT NDE 3.3-27 X - - - (CR¹99-425).03/24/1999 - PT complete, NRZ following corrective action.

151940 SR-934 P-A VT-3 NDE 4.3-11 C X - - - 03/20/1999 - VT-3 complete, NRZ.

SPRING HANGER P1.10C 151980 SR 934 IA B-K PT NDE 3.3-14 C - - - X 03/22/1999 - PT complete, RZ INTEGRAL ATTACHMENT B10.10 PT NDE 3.3-28 - X - - (CR¹99-426). 03/24/1999 - PT complete following corrective action, reduced to two acceptable linear indications.

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 10 INSERVICE INSPECTION SUaaRY THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RP)

Class 1 CSEA STATUS Components HEMICAL & VOLUME CONTROL TO RC LOOP A COLD LEG N I 0 Zone Number: 4-046 S ON GT SEC. XZ T RSEH Summary Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R ~~ Calibration Block **

REP. DWG. NO. 5614-P-782-S SH. 3 161350 SR 942 P A VT-3 NDE 4.3 12 C X - - - 03/21/1999 - VT-3 complete, NRZ.

DOUBLE ACTING RESTRAINT P1.10B (drawing discrepency).

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 11 ZNSERVICE INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RP)

Class 1 CBEA STATUS Components ICAL AND VOLUME CONTROL TO REGENERATIVE HX N I 0 Zone Number: 4-047 S ONGT SEC. XZ T RSEH Sugary Examination Area Catgy Exam A E I0 E Remarks Number Zdentiiication Item No Method Procedure T C G M R <<* Calibration Block **

REF. DWG. NO. 5624 P-551-S SH. 1 163050 4-VCH-63 P-A VT-3 NDE 4.3-20 C - - - X 03%2411999 - VT-3 complete, RZ DOUBLE ACTING RESTRAINT F1. 108 (CR¹99-444 - evaluated "use as is~)

163860 SR-491 P-A VT-3 NDE 4.3 9 C X - - - 03/19/1999 - VT-3 complete, NRZ.

DOUBLE ACTING RESTRAINT F1. 10B

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 12 INSERVICE INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RP)

Class 1 CBEA STATUS Components CHEMICAL & VOLUME CONTROL FROM THE REGENERATIVE HX N I 0 Zone Number: 4-049 S ONGT SEC. XZ T RSEH Summary Examination Area Catgy Exam A E I0 B Remarks Number Identification Item No Method Procedure T C G M R *~ Calibration Block ~~

REP. D'WG. NO. 5614 P-553-S SH. 3 170500 2"-CH-1402-20 B-J PT NDE 3.3-10 C X - - - 03/21/1999 - PT complete, NRI.

PIPE TO TEE B9.40 170600 2" CH 1402 21 B-J PT NDE 3.3-10 C X - - - 03/21/1999 - PT complete, NRZ.

TEE TO PIPE B9.40 170700 2"-CH-1402-22 B-J PT NDE 3.3-8 C X - - - 03/21/1999 - PT complete, NRZ.

PIPE TO RO-4-3436 B9.40 1000 2" CH-1402-25 B-J PT NDE 3.3-10 C X - - - 03/21/1999 - PT complete, NRZ.

TEE TO PIPE B9.40 171200 2"-CH-1402-27 B-J PT NDE 3.3-9 C - X - - 03/21/1999 - PT complete, two acceptable ELBOW TO PIPE B9.40 rounded indications.

171300 2~-CH-1402-28 B-J PT NDE 3.3-7 C X - - - 03/21/1999 - PT complete, NRI.

PIPE TO RO-4-3435 B9.40

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 13 INSERVICE INSPECTION SUÃ4ARY THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RP)

Class 1 CBEA STATUS Components CHEMICAL 6 VOLUME CONTROL REGENERATIVE HEAT EXCH N I 0 Zone Number: 4-059 S ONGT SEC. XI T RSEH Summary Examination Area Catgy Exam A E I0 E Remarks Number Identification Item No Method Procedure T C G M R ** Calibration Block +*

REF. DWG. NO. 5614-M-4009 199290 RGX 4E200 VT-2 NDE 4.2 1 C X - - - 03/17/1999 - VT-3 complete, NRI {exam VISUAL FOR LEAKAGE VT-3 NDE 4.3-8 X - - - per relief request N3). 04/6-1999 - VT-2 complete (OP-1004.1) .

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 14 INSERVICB INSPECTION SUK4IARY THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RF)

Class 2 CBBA STATUS Components BSIDUAL HEAT REMOVAL TO RESID.HEAT REMOVAL PUMP A N I 0 Zone Number: 4-063 S ON GT SEC. XZ T RSBH Summary Examination Area Catgy Exam A B I 0 B Remarks Number Identification Ztem No Method Procedure T C G M R ~~ Calibration Block ++

REF. DWG. NO. 5614-P 503-S SH. 1 209300 14"-RHR-2401-9 C F-1 PT NDE 3.3-6 C X - - - 03/20/1999 - PT complete, NRZ.

PIPE TO ELBOW C5.11 UT-60 AX NDE 5.4 6 X - - - 03/25/1999 - UT complete, NRZ.

UT-70 AX NDE 5.4-6 X-UT-45 CIRC NDE 5 '-6 X-

~e UT-33 **

209350 14"-RHR 2401-9LD C-F-1 PT NDE 3.3-6 C X - - - 03/20/1999 - PT complete, NRI.

LONGITUDINAL SEAM WBLD CS. 12 UT-45AX NDE 5.4-7 X - - - 03/25/1999 - UT complete, NRZ.

DOWNSTREAM UT-60CIRC NDE 5.4 7 X-UT-70CIRC NDE 5.4-7 X 0* UT 33 **

400 14"-RHR-2401-10 C-F-1 PT NDE 3.3-26 C - X - - 03/24/1999 - PT complete, acceptable ELBOW TO PIPE C5.11 UT-60 AX NDE 5.4-6 X - - - rounded indication. 03/25/1999 - UT UT-70 AX NDB 5.4-6 X - - - complete, NRI.

UT 45 CIRC NDB 5.4-6 X-UT 33 4*

209450 14"-RHR-2401-10LD C-F-1 PT NDE 3.3-26 C X - - - 03/24/1999 - PT complete, NRI.

LONGITUDINAL SEAN WELD CS. 12 UT-45AX NDE 5.4-7 X - - - 03/25/1999 - UT complete, NRI.

DOWNSTREAM UT-60CIRC NDE 5.4-7 X-UT-70CIRC NDE 5.4-7 X-

  • ~ UT-33 **

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 15 INSERVICB INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RP)

Class 2 CBEA STATUS Components RESIDUAL HEAT REMOVAL TO RESID. HEAT REMOVAL PUMPS N I 0 Zone Number: 4-065 S ONGT SEC. XI T RSEH Summary Examination Area Catgy Exam A B I 0 B Remarks Number Ident ification Item No Method Procedure T C G M R *>> Calibration Block ~~

RBF. DWG. NO. 5614-P 503-S SH. 1 214600 14'HR 2404 16 C-F-1 PT NDE 3.3-21 C X- 03/23/1999 - PT complete, NRI.

ELBOH TO PIPE C5.11 UT-60 AX NDE 5.4-4 - X 03/24/1999 - UT complete, geometry.

UT-70 AX NDE 5.4-4 -X-UT 45 CIRC NDE 5.4-4 X

~~ UT-33 *~

214700 14" RHR 2404 17 C-F 1 PT NDE 3.3-21 C -X- 03/23/1999 - PT complete, non-relevant PIPB TO TEB C5.11 UT-60 AX NDE 5.4-4 X indications (undercut) .03/24/1999 - UT UT-70 AX NDE 5.4-4 -X- complete, geometry.

UT-45 CIRC NDE 5.4-4 X-

~* UT 33 ea

Date> 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 16 INSERVICE INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RF)

Class 2 CBEA STATUS Components RESIDUAL HEAT REMOVAL FROM CONTAINMENT SUMP B N I 0 Zone Number: 4-067 S ONGT SEC. XI T RSEH Summary Examination Area Catgy Exam A E I0 E Remarks Number Identification Item No Method Procedure T C G M R ** Calibration Block ~~

REF. DWG. NO. 5614-P-503-S SH, 2 216500 14'-RHR-2406-4 C-F-1 PT NDE 3.3-5 C X- 03/20/1999 - PT complete, NRI.

ELBOW TO PIPE C5.11 UT 60 AX NDE 5.4-3 X 03/24/1999 - UT complete,, geometry.

UT-70 AX NDE 5.4 3 X UT 45 CIRC NDE 5.4-3 X 4* UT 33

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 17 INSERVZCE INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RF)

Class 2 CBEA STATUS Components RESIDUAL HEAT REMOVAL DISCHARGE OUTSIDE CONTAINMEN N I 0 Zone Number: 4-068 S ONGT SEC. XI T RSEH Summary Examination Area Catgy Exam A E I0 E Remarks Number Identification Item No Method Procedure T C G M R ** Calibration Block <<~

RBP. DMG. NO. 5614-P-505-S SH. 1 218500 12<<-RHR-2401-2 CP1 PT NDE 3.3 24 C X 03/24/1999 - PT complete, NRI.

REDUCER TO TEE CS. 11 UT-60AX NDE 5 '-8 X 03/25/1999 - UT complete, NRZ.

UT-45CZRC NDE 5.4 8 X-

    • UT 35 <<<<

REF. DWG. NO. 5614-P-505 S SH. 3 219550 SR 635 P-A VT-3 NDE 4.3-2 C X - - - 03/15/1999 - VT-3 complete - NRI.

SPRING HANGER Pl. 20C

1 l

I

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 18 INSBRVICE INSPECTION SUiiRY THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE {99RP)

, Class 2 CBEA STATUS Components BSIDUAL BRAT REMOVAL INSIDB & OUTSIDE CONTAINMENT N I 0 Zone Number: 4-069 S ONGT SEC. XI T RSEH Summary Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R ~~ Calibration Block ~*

RBF. DWG. NO. 5614-P 505-S SH. 3 222600 12'-RHR-2402-26 C-F-1 PT NDE 3.3 4 C X - - - 03/15/1999 - PT complete - NRI.

ELBOW TO PIPE C5. 11 UT-60AX NDE 5.4-14 - - X - 03/25/1999 - UT complete, geometry.

UT 70AX NDE 5.4-14 -X-UT 45CIRC NDB 5.4-14 X-35 14 222655 CONTAINMENT PEN. P-2 P-A VT-3 NDE 4.3 3 C X - - - 03/15/1999 - VT-3 complete - NRI.

ANCHOR P1.20D

Date: 04/15/1999 TURXEY POINT NUCLEAR PLA3rr UNIT 4 Page: 19 INSERVZCE INSPECTION SUiitY THIRD INTERVAL, SECOND PERZOD, SECOND OUTAGB (99RF)

Class 2 CBEA STATVS Components ESIDUAL HEAT REMOVAL SYSTEM INSIDE CONTAINMENT N I 0 Zone Number: 4-081 S ON GT SEC. XI T RSEH Summary Examination Area Catgy Exam A B I 0 E Remarks Number Identification Item No Method Procedure T C G M R i'alibration Block ~ i REF. DWG. NO. 5614-P-509-S SH. 2 233490 10"-SZ 2407 4 C-P-1 PT NDE 3.3-17 C - X - - 03/22/1999 - PT complete, acceptable PIPE TO VALVB 4-885 C5.11 UT 60 AX NDE 5.4 5 - - X - linear indication. 03/24/1999 - UT UT 45L AX NDE 5.4-5 X - - - complete, geometry.

UT-70 AX NDE 5.4-5 X-UT-45 CIRC NDE 5.4-5 X - - - ~* VT-27 233500 10'-SZ-2407-5 C-P-1 PT NDB 3.3-23 C X - - - 03/23/1999 - PT complete, NRI.

VALVB 4-885 TO ELBOW C5.11 UT 60 AX NDB 5.4-5 - - X - 03/24/1999 - UT complete, geometry.

UT-4 SLAX NDE 5.4-5 X-UT 70 AX NDB 5.4-5 X-UT-45 CIRC NDE 5.4 5 X - - - ++ UT 27 **

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 20 INSERVICE INSPECTION

SUMMARY

THZRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RP)

Class 2 CBEA STATUS Components BSIDUAL HEAT REMOVAL SYSTEM INSIDE CONTAINMENT N I 0 Zone Number: 4-084 S ONGT SEC. XI T RSEH Summary Examination Area Catgy Exam A E I 0 E Remarks Number Zdenti fication Item Ho Method Procedure T C G M R ** Calibration Block ~*

RBF, DWG. NO, 5614-P-509-8 SH. 4 234680 8"-SZ-2402-14 C-F-1 PT NDE 3.3 25 C X- 03/24/1999 - PT complete, NRI.

PIPE TO ELBOW CS. 11 UT-60LAX NDE 5. 4-13 -X- 03/24/1999 - UT complete, geometry.

UT-45LAX NDE 5. 4-13 - X UT-45LCIRC NDE 5. 4-13 X-

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 ~ '" Page: 21 INSERVZCB INSPECTION SUI4ARY THIRD INTERVAL, SECOND PERIOD, SECOND OUI'AGE (99RP)

Class 2 CBEA STATUS Components ESIDUAL HEAT REMOVAL SYSTEM INSIDE CONTAINMENT N I 0 Zone Number: 4-086 S ONGT SEC. XZ T RS EH Summary Examination Area Catgy Exam A B I0 B Remarks Number Identification Ztem No Method Procedure T C G M R ~~ Calibration Block ~~

REP. DWG. NO. 5614-P-509-S SH. 1 236500 8" SI 2404 2 CP1 PT NDE 3.3-22 C - X - - 03/23/1999 - PT complete, acceptable PIPB TO VALVE 4 876A C5.11 UT 60LAX NDE 5 ~ 4 11 - - X - rounded indication. 03/23/1999 - UT UT-45LAX NDB 5.4-11 X - - - complete, geometry.

UT-45LCZRC NDE 5 ~ 4-11 X-

i Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 22 INSERVICE ZNSPECTZON SUGARY THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE {99RF)

Class 2 CSEA STATUS Components SAFETY INJECI'ZON TO CONTAINMENT SPRAY PUMP B N I 0 Zone Number: 4-087 S ONGT SEC. XI T RSEH Summary Examination Area Catgy Exam A E I0 E Remarks Number Identif'ication Item No Method Procedure T C G M R ~~ Calibration Block ~

'EF.

DWG. NO. 5614-P-502-S SH. 1 237140 H-218A F-A VT-3 NDE 4.3-1 C X - - - 03/15/1999 - VT-3 complete - NRZ ANCHOR F1. 20D

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 ~ re Page: 23 INSERVZCB INSPBCTION

SUMMARY

THIRD INTERVAL, SECOND PBRIOD, SECOND OUTAGB (99RF) l Class 2 CSEA STATUS Components ESIDUAL HEAT REMOVAL SYSTEM INSIDE CONTAINMENT N I 0 Zone Numberr 4-089 S 0NGT SEC. XI T RS EH Summary Examination Area Catgy Exam A E I0 E Remarks Number Identification Item No Method Procedure T C G M R ** Calibration Block *"

RBF. Dry. NO. 5614-P-509-S SH. 1 240600 85-SI-2407-8 C-F-1 PT NDB 3.3 15 C -X- 03/22/1999 - PT complete, three TEE TO PIPE C5. 11 UT-60LAX NDE 5.4-12 - X acceptable rounded UT-4 5 LAX NDE 5.4-12 -X- indications.03/24/1999 - UI'omplete, UT-45LAX NDB 5.4 12 X- geometry.

  • 0 UT 41 **

241250 SR-450E VT-3 NDE 4.3-18 C X - - - 03/23/1999 - VT-3 complete, NRZ.

SINGLE ACTING RESTRAINT 241350 SR-445 VT 3 NDE 4.3-11 C X - - - 03/23/1999 - VT-3 complete, NRI.

DOUBLE ACTING RESTRAINT

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 24 INSERVICE INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE t99RP)

Class 2 CSEA STATUS Components IGH BEAD SAPETY INJECTION OUTSIDE CONTAINMENT N I 0 Zone Number: 4-097 S ONGT SEC. XI T RSEH Summary Examination Area Catgy Exam A E Z 0 E Remarks Number Ident ification Ztem No Method Procedure T C G M R ~* Calibration Block *>>

REF. DWG. NO. 5614-P 571-S SH. 1 257644 3"-SZ-2403-35 C-P-1 PT NDE 3.3 1 C X - - - 03/15/1999 - PT complete - NRZ.

PIPE TO ELBOW C5.21 UT-60 AX NDE 5.4-1 X - - - 03/22/1999 - UT complete,- NRZ.

UT-70 AX NDE 5.4 1 X UT-38 CIRC NDE 5.4-1 X-UT-47 257648 3"-SI-2403-36 C-P-1 PT NDE 3.3-2 C X - - - 03/15/1999 - PT complete - NRZ {welded ELBOW TO PIPE C5.21 UT-60AX NDE 5.4 1 X - - - obstruction but >90% CRS).03/22/1999-UT-70AX NDE 5.4 1 X - - - UT complete - NRZ.

UT-38CIRC NDE 5.4-1 X

f Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 25 INSERVZCE ZNSPECI'ION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE {99RF)

Class 2 CBEA STATUS Components IGH HEAD SAFETY INJECTION N I 0 Zone Number: 4-098 S 0 N G T SEC. XI T R S E H Summary Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R ** Calibration Block **

REF. DWG. NO. 5614-P-783-S SH. 3 257885 2"-SI-2408 10 CF1 PT NDE 3.3 3 C X - - - 03/15/1999 - PT complete - NRZ.

PIPE TO ELBOW C5.30 257888 2"-SZ-2408-11 C-F-1 PT NDE 3.3-3 C X - - - 03/15/1999 - PT complete - NRI.

ELBOW TO PIPE C5. 30

t Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 26 INSERVICE INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE {99RP)

Class 2 CBEA STATUS Components TEAM GENERATOR A BLOWDOHN INSIDE CONTAINMENT N I 0 Zone Number: 4-105 S ONGT SEC. XZ T RSEH Summary Examination Area Catgy Exam A E I0 E Remarks Number Identification Item No Method Procedure T C G M R +~ Calibration Block ~~

REF. DHG. NO. 5614-P-790-S SH. 1 270440 78102B-H-420-03 P-A VT-3 NDE 4.3 13 C X' - - 03/21/1999 - VT-3 complete, NRI (drawing DOUBLE ACTING RESTRAINT P1.20B discrepency).

270460 78102B-H-420-03 IA CC MT NDE 2.2-2 C X - - - 03/21/1999 - MT complete, NRZ.

INTEGRAL ATTACHMENT C3.20

II 1

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 27 INSERVICE INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RF)

Class 2 CBEA STATUS Components EAM GENERATOR C BLOWDOWN INSIDE CONTAINMENT N I 0 Zone Number: 4-107 S ONGT SEC. XI T RSEH Surnmry Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R +* Calibration Block +~

REP. DWG. NO. 5614-P-785-S SH. 1 276450 78102B H 422-03 P A VT-3 NDE 4.3-14 C X - - - 03/21/1999 - VT-3 complete, NRI.

DOUBLE ACTING RESTRAINT P1.20B 276460 78102B H-422-03 IA C-C MT NDE 2.2-1 C - X - - 03/21/1999 - MT complete, acceptable INTEGRAL ATTACHMENT C3.20 linear indication.

r Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 28 INSERVICE INSPECTION

SUMMARY

THIRD INTERVAI, SECOND PERIOD, SECOND OUTAGE t 99RP)

Class 2 CSEA STATUS ComPonents IN PEEDWATER SYSTFM LOOP A N I 0 Zone Number: 4-111 S ONGT SEC. XZ T RSEH Summary Examination Area Catgy Exam A E I 0 E Remarks Humber Ident ification Item No Method Procedure T C G M R +~ Calibration Block ++

REF. DWG. NO. 5614 P 557 S SH. 1 284460 Augmented Exam AUG UT-60AX NDE 5.16-2 A - - X - 03/20/1999 - UT complete, geometry.

PROM NOZZLE RAMP TO 1 PIPE DIA. ON ELBOW e* UT 20~ UT 29 sa

l l

I I

N

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 29 INSERVICE INSPECTION S~~Y THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RF)

Class 2 CBEA STATUS Components IN FEEDWATER SYSTEM LOOP B N I 0 Zone Number: 4-112 S ONGT SEC. XI T RSEH Summary Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R ** Calibration Block ~~

REF. DWG. NO. 5614-P-558-S SH. 1 286980 Augmented Exam AUG UT-60AX NDE 5.16-3 A - - X - 03/21/1999 - UI'omplete, geometry.

FROM NOZZLE RAMP TO 1 PIPE DIA. ON ELBOW

~~ UT 20, UT-29

0 Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNZT 4 Page: 30 INSERVICE INSPECTION SI04ARY THIRD INTERVAL, SECOND PERIOD, SECOND OUI'AGB (99RP)

Class 2 CBEA STATUS Components IN FBBDWATER SYSTEM LOOP C N I 0 Zone Number: 4-113 S ONGT SEC. XZ T RSEH Summary Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R *>> Calibration Block ~~

~l REP. DWG. NO. 5614 P 789 S SH. 1 289650 Augmented Exam AUG UZ-60AX NDE 5.16-1 A - - X - 03/19/1999 - UT complete, geometry.

PROM NOZZLE RAMP TO 1 DIA. ON BLBOW

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 31 INSERVICE INSPECTION SU)0(ARY THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGB (99RF)

Class 3 CBEA STATUS Components MPONENT COOLING WATER FROM RHR HEAT EXCHANGER A N I 0 Zone Number: 4-126 S ONGT SEC. XZ T RSBH Summary Examination Area Catgy Bxam A B I 0 E Remarks Number Identification Ztem No Method Procedure T C G M R ** Calibration Block ~~

REF. DWG. NO. 5614-P-518-S SH. 4 298000 SR-688 P-A VT-3 NDE 4.3-5 C - - - X 03/15/1999 - VT-3 complete, RI ANCHOR F1.30D (CR¹99-351 - evaluated "use as is' 298050 SR-688 IA D-A VT-1 NDE 4.1-2 C X - - - 03/15/1999 - VT-1 complete, NRZ.

INTEGRAL ATTACHMENT D1.20

Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 32 INSERVICE INSPECTION

SUMMARY

THIRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RP)

Class 3 CBEA STATUS Components COMPONENT COOLING WATER SYSTEM OUTSIDE CONTAINMENT N I 0 Zone Number: 4-139 S ONGT SEC. XZ T RSEH SummarY Examination Area Catgy Exam A E I 0 E Remarks Number Identification Item No Method Procedure T C G M R ** Calibration Block ~~

REF. DWG. NO. 5614 P 506 S SH. 2 305500 SR 708 P-A VT-3 NDE 4.3 4 C - - - X 03/15/1999 - VT-3 complete, RZ DOUBLE ACTING RESTRAINT P1.30B (CRN99-349 - evaluated <<use as is~).

305600 SR 708 IA D-A VT-1 NDE 4.1 1 C X - - - 03/15/1999 - VT-1 complete, NRZ.

INTEGRAL ATTACHMENTS D1.20

II Date: 04/15/1999 TURKEY POINT NUCLEAR PLANT UNIT 4 Page: 33 INSERVZCE INSPECTION

SUMMARY

THZRD INTERVAL, SECOND PERIOD, SECOND OUTAGE (99RF)

Class 3 CBEA STATUS Components COMPONENT COOLING WATER TO RHR HEAT EXCHANGER A N I 0 Zone Number: 4-140 S ON GT SEC. XZ T RS EH Summary Examination Area Catgy Exam A E I 0 E Remarks Number Identification Ztem No Method Procedure T C G M R *'alibration Block **

REF. DWG. NO. 5614-M-4010 306550 4-RHE-A-UPPER Support F-A VT-3 NDE 4.3-19 C X - - - 03/24/1999 - VT-3 complete, NRI.

HEAT EXCHANGER UPPER SUPPORT F1.40H 306560 4-RHE-A-UPPER Support IA D-A VT 1 NDE 4.1 3 C X - - - 03/24/1999 - VT-1 complete, NRZ.

INTEGRAL ATTACHMENT D1. 10

TURKEY POINT UNIT 4 1999 REFUELING OUTAGE Summary of System Pressure Testing

Abstract This report details the pressure testing of selected class 1, 2 and 3 piping and components of the Florida Power and Light Company Turkey Point Unit 4 cycle 18 which were performed during the spring 1999 refueling outage. This outage occurred between the dates of March 15, 1999 and April 7, 1999, and covers the dates from November 1, 1997 through April 9, 1999. This pressure testing is being reported following the second outage of the second period for 3'" ten year interval for Turkey Point Unit 4.

Piping and components were selected and tested in accordance with Section XI of the American Society of Mechanical Engineers (ASME) Boiler and Pressure Vessel Code "Rules for Inservice Inspection of Nuclear Power Components", 1989 Edition with no addenda with specific relief as granted under 10 CFR 50.55a.

0 Procedures The following Florida Power and Light (FPL) procedures and documents have been ~

implemented to provide instructional guidance for the performance of the required ASME XI pressure testing and subsequent inspections.

OP-1004.1 Reactor Coolant System-System Leak Test Following RCS Opening.

4-OSP-45.1 ASME Section XI Quality Group A Bolting Examination*

4-OSP-45.2 ASME Section XI Quality Group B Bolting Examination*

0-ADM-523 ASME Section XI Pressure Tests for Quality Group A, B, C Systems/Components.

4-OSP-041.2 Reactor Coolant System Visual Leak Inspection and Leak Evaluation.

NDE-4.2 Visual Examination VT-2 Conducted During System Pressure Tests.

0 S stem Summa The following safety related Class 1, 2, and 3 systems, or sections thereof were pressure tested in accordance with the requirements of the 1989 ASME Section XI Code.

System Name System Number Component Cooling Water 30 Reactor Coolant 41 Chemical and Volume Control 47 Residual Heat Removal 50 Safety Injection 62 Safety Injection (Accumulator) 64 Main Steam 72 Feedwater 74 Auxiliary Feedwater 75

~Acron ms ADM: Administrative ASME: American Society of Mechanical Engineers CSS: Containment Spray System CCW: Component Cooling Water CVCS: Chemical Volume Control System ECC: Emergency Containment Cooler FW: Feedwater Heat Exchanger ICW: . Intake Cooling Water Non Destructive Examination PWO: Plant Work Order PZR: Pressurizer RCP: Reactor Coolant Pump Residual Heat Removal RO: Restricting Orifice RV: Relief Valve RX: Reactor SFPC: Spent Fuel Pool Cooling SG: Steam Generator WO: Work Order

0 Test Packa e Develo ment The specific pressure test boundaries were selected after review of the applicable plant Operating diagram/code boundary drawings. The piping systems were broken into sub systems. The sub-systems were selected based on Technical Specifications operability requirements, acceptable isolation points and availability of test connections and vent valves. The sub-systems were then assigned test package numbers, which could be tested in entirety, or based on availability could be broken down further into numerous tests within the specific sub-system.

The pressure test package numbers contain six (6) segments of information, Sample: 04-CCW-30110-I-01 A A A A A A 1 2 3 4 5 6 Unit Number (00) common to both units 3 and 4. (03) Unit specific. (04)

Unit specific.

System abbreviation System number [First (2) digits].

Sub-system number [(2) or (3) digits].

. Type of test (H) Hydrostatic, (P) Pneumatic, (L) Leakage, (F) Functional, (I) Inservice, (S) Static head.

Number of test performed within the specific sub-system.

COMPONENT COOLING WATER SYSTEM 30 04-CCW-30315-L-01 Test Date: 04/01/99 This test was performed due to the replacement of valve 4-721C under WO ¹ 98005483 and Condition Report 97-1377. No leakage was observed during this test.

04-CCW-30316-L-01 Test Date: 04/01/99 This test was performed due to the replacement of valve 4-721B under WO ¹ 98005482 and Condition Report 97-1377. No leakage was observed during this test.

04-CCW-30317-L-01 Test Date: 04/01/99 This test was performed due to the replacement of valve 4-721A under WO ¹ 98005479 and Condition Report 97-1377. No leakage was observed during this test.

04-CCW-30318-L-01 Test Date: 04/01/99 This test was performed due to the replacement of valve RV-4-1427 under WO ¹ 98022097. No leakage was observed during this test.

04-CCW-30319-L-01 Test Date: 04/01/99 This test was performed due to the replacement of valve RV-4-1426 under WO ¹ 98022142. No leakage was observed during this test.

04-CCW-30320-L-01 Test Date: 03/17/99 This test was performed due to the installation of PCV-4-832 for the CCW Head

¹ Tank per PC/M 96-093 and WO 98022379. No leakage was noted during this test.

04-CCW-30321-L-01 Test Date: 04/01/99 This test was performed due to the replacement of valve RV-4-1428 under WO ¹ 99005330. No leakage was observed during this test.

04-CCW-30322-L-01 Test Date: 04/01/99 This test was performed due to the replacement of valve RV-4-1429 under WO ¹ 99005331. No leakage was observed during this test.

COMPONENT COOLING WATER SYSTEM 30 CONTINUED 04-CCW-30216-I-02 Test Date 03/17/99 This test was performed to meet the 1989 Edition of ASME Section XI periodic pressure test requirements. No leakage was noted during this test.

04-CCW-30217-I-02 Test Date 03/15/99 This test was performed to meet the 1989 Edition of ASME Section XI periodic pressure test requirements. No leakage was noted during this test.

04-CCW-30218-I-02 Test Date 03/15/99 This test was performed to meet the 1989 Edition of ASME Section XI periodic pressure test requirements. No leakage was noted during this test.

04-CCW-30221-I-02 Test Date 03/15/99 This test was performed to meet the 1989 Edition of ASME Section Xl periodic pressure test requirements. No leakage was noted during this test.

04-CCW-30222-I-02 Test Date 03/15/99 This test was performed to meet the 1989 Edition of ASME Section XI periodic pressure test requirements. No leakage was noted during this test.

04-CCW-30223-I-02 Test Date 03/15/99 This test was performed to meet the 1989 Edition of ASME Section XI periodic pressure test requirements. No leakage was noted during this test.

04-CCW-30235-I-01 Test Date: 12/04/98 This test was performed due to replacement of the bonnet for valve 4-1173 under WO 8 98023845. No leakage was noted during this test.

REACTOR COOLANT SYSTEM 41 04-RCS-4111-L-03 Test Date 04/06/99 This test involved the leakage test of the Reactor Coolant System piping inside containment following the Unit 4 Cycle 18 Refueling Outage. This leakage test addressed the following replacements.

Component WO8 Replaced RV-4-551A 98011405 Remove, install spare RV-4-551B 98011407 Remove, install spare RV-4-551C 98011409 Remove, install spare

0 CHEMICALAND VOLUME CONTROL CHARGING AND LETDOWN SYSTEM 47 04-CVCS-4764-L-01 Test date: 04/06/99 This leakage test is being performed due to replacement of valve 4-293B under

¹ WO 98011738. No leakage was observed during this test.

04-CVCS-4765-L-01 Test date: 02/12/99 This leakage test is being performed due to replacement of the 4B charging pump block under WO ¹ 98021775. No leakage was observed during this leakage test.

04-CVCS-4766-I 01 Test date: 04/06/99 This leakage test is being performed due to replacement of valve 4-293A under

¹ WO 98021632. No leakage was observed during this test.

04-CVCS-4767-L-01 Test date: 04/06/99 This leakage test is being performed due to replacement of valve RV-4-203 with a spare valve under WO ¹ 98009247. No leakage was observed during this test.

04-CVCS-4757-I-02 Test date: 03/15/99 This Inservice test was performed to meet the ASME Section XI 1989 Edition periodic pressure test requirements. No through wall leakage was observed.

04-CVCS-4758-I-02 Test date: 03/15/99 This Inservice test was performed to meet the ASME Section XI 1989 Edition periodic pressure test requirements. No leakage was observed during test.

04-CVCS-4759-I-02 Test date: 03/15/99 This Inservice test was performed to meet the ASME Section XI 1989 Edition periodic pressure test requirements. No leakage was observed during test.

RESIDUAL HEAT REMOVALSYSTEM 50 04-RHR-5014-F-02 Test Date: 03/20/99 This Functional pressure test was performed to meet ASME Section XI 1989 Edition periodic pressure test requirements.

04-RHR-5017-F-02 Test Date: 03/27/99 This Functional pressure test was performed to meet ASME Section XI 1989 Edition periodic pressure test requirements. No leakage was observed during this functional test.

f>>

SAFETY INJECTION SYSTEM 62 04-SIS-6224-F-01 Test Date: 04/01/99 This test was performed to meet ASME Section XI 1989 Edition periodic pressure test requirements. No leakage was observed'during this functional test.

SAFETY INJECTION ACCUMULATORS SYSTEM 64 04-SIS-6402-F-03 Test date: 03/15/99 This functional test was performed to meet ASME Section XI 1989 Edition periodic pressure test requirements. No through wall leakage was observed.

1 1

tt

MAINSTEAM SYSTEM 72 04-MS-7217-I-02 Test Date: 03/15/99 This Inser vice test was performed to meet ASME Section XI 1989 Edition periodic pressure test requirements. No leakage observed during this test.

04-MS-7218-I-02 Test Date: 03/15/99 This Inservice test was performed to meet ASME Section XI 1989 Edition periodic pressure test requirements. No leakage observed during this test.

04-MS-7219-I-02 Test Date: 03/15/99 This Inservice test was performed to meet ASME Section XI 1989 Edition periodic pressure test requirements. No leakage observed during this test.

04-SG-7222-L-01 Test Date: 04/06/99 This test was performed due to replacement of the manway for 4A steam generator secondary side under WO 8 98011891. No leakage was observed during this test.

FEEDWATER SYSTEM 74 04-FW-7434-L-01 Test Date: 04/06/99 This leakage was performed due to replacement of the stuEing box cover for valve CV 2902 under WO 8 98003506. No leakage was observed during this test.

AUX FEEDWATER SYSTEM 75 04-AFW-7557-L-01 Test Date: 03/16/99 This leakage test was performed due to addition of valve AFSS-4-010 under PC/M 99-001 and WO 8 99003180. No leakage was observed during this test.

04-AFW-7504-L-01 Test Date: 04/07/99 This leakage test was performed due to replacement of piping downstream of valve AFSS-4-004 under WO 8 98010491 and Condition Report 98-0276. This test also covered the Unit 4 portion of valve AFSS-4-010 which was added under PC/M 99-001 and WO 8 99003180. No leakage was noted during this test.

0