Special Rept Re Breached Fire Barriers & Other Fire Protection Sys Impairments.Fire Protection Impairment 2458, Opened 890420,to Repair Penetration Seal,Still Being Worked. Plant Continues to Implement Compensatory Measures
ML17345A716
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 05/31/1989
From: Woody C
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
L-89-195, NUDOCS 8906070222
Download: ML17345A716 (3)


Text

QI I f LLAAlLL) LlldlALPVllVl> QE KV'WZJA8,llV'l 3l 0 ILL REGULAT INFORMATION DISTRIBUTIO YSTEM:(RIDS):-

ACCESSION NBR:8906070222 DOC.DATE: 89/05/31 NOTARIZED: NO DOCKET FACIL:50-250 Turkey Point Plant, Unit 3, Florida Power and Light C 05000250 50-251 Turkey Point Plant, Unit 4, Florida Power and Light C 05000251 AUTH. NAME AUTHOR AFFILIATION WOODY,C.O. Florida Power & Light Co.

RECIP.NAME RECIPiENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Special rept re breached fire barriers & other fire protection sys impairments.

DISTRIEOT:ON CODE: :E22D COPIES RECEIVED:LTR l ENCL I SIZE:

TITLE: 50.73/50.9 icensee =vent Report (LER), incident Rpt, etc.-

NOTES:

RECIPIENT COPIES RECIPIENT COPI" S ZD CODE/NAME LTTR ENCL ID CODF/NAME LTTR "'NCL PD2-2 LA 1 1 PD2-2 PD 1 1 "DZSON,G 1 1 INTERNAL: ACRS MICHELSON 1 ACRS MOELLER 2 2 ACRS WYLIE 1 AEOD/DOA 1 1 ~

AEOD/DSP/TPAB 1 1 AEOD/ROAB/DSP 2 2 DEDRO 1 ZRM/DCTS/DAB 1 1 NRR/DEST/AD" SH 1 NRR/DEST/ADS 7E 1 0 NRR/DEST/CEB SH 1 1 NRR/DFST/ESB SD 1 NRR/DEST/ICSB 7 1 1 NRR/DEST/MEB 9H 1 '1 NRR/DEST/MTB 9H 1 1 NRR/DEST/PSB SD 1 1 NRR/DES /RSB 8E 1 1 iVRR/DEST/SGB SD 1 1 NRR/DLPQ/HFB 10 NRR/DOEA/EAB NUDOCS-ABSTRACT ll 1 1

1 1

1 1

NRR/DLPQ/PEB REG FI>E RPB 10 10 02 1

2 1

1 2

1 RES/DSZR/EZB 1 1 PfD PRAB 1 1 RGN2 riLE 01 1 1 R

EXTERNAL: EG&G WILLIAMS,S 4 4 FORD BLDG HOYIA 1 1 L ST LOBBY WARD 1 1 LPDR 1 1 NRC PDR 1 1 NSIC MAYS IG 1 1 NSIC MURPHY,G.A 1 1 D S

NOTE 'Z0 ALL 'KIDS" RECIPZERIS:

PIEASE HELP US ZO REDUCE HASTE! CXNI'ACT 'ZHE DOCUMENT CXÃZBDL DESK, RXN Pl-37 (EXT. 20079) K) ELIKBRTB ACR NAME FKN DIBTRIBUTIGN LISTS POR DOCl2KNZS YOU DOH~T NEED!

TOTAL NUMBER OF COPlES REQUiRED: LTTR 43 ENCL 42 I'

~.0 Box 140iiii Sono Sooch, Fi, 33408-0420

.MP.Y. 3 f 8LL L-89-195 U. S. -Nuclear Regulatory Commission Attn: Document Control Desk

.Washington, D. C. 20555 Gentlemen:

Re: Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 Special Report Breached Fire Barriers and Other Fire Protection S stem Im airments In accordance with Technical Specification 6.9.3.c, the attached Special Report is provided for your information.

Should there be any questions on this information, please contact us ~

Very truly yours, Acting Senior Vice President Nuclear COW/JRH/cm Attachment cc: Stewart D. Ebneter, Regional Administrator, Region II, USNRC Senior Resident Inspector, USNRC, Turkey Point Plant 8906070222 890531 PDR ADQCK 05000250 S PNU Qg22-

Attachment:

SPECIAL REPORT FIRE PROTECTION SYSTEM IMPAZRMENTS REQUIRING NRC NOTIFICATION PURPOSE:

Technical Specification (TS) 3.14.5.b requires the submission of a report to the NRC if a non-functional fire barrier penetration is not returned to functional status within 7 days. TS 3.14 also states that certain other conditions require NRC notification. In accordance with the above requirements, this special report is being submitted in order to notify the NRC.

EVENT:

Fire Protection Impairment (FPI) 2458 was opened for penetration 025W-E016.

CAUSE AND CORRECTIVE ACTIONS:

e FPI 2458, opened April 20, 1989 to repair a penetration seal, is still being measures as worked. The plant continues applicable.

to implement the compensatory STATUS UPDATE:

FPI 1778, reported open in FPL letter L-88-331, dated August 2, 1988, was closed on April 14, 1989. FPI 2059, reported open in FPL letter L-88-501, dated November 18, 1988, was closed on April 18, 1989.

FPI 2137, reported open in FPL letter L-88-535, dated December 16, 1988, was closed on April 19, 1989. FPIs 2301 and 2302, reported open in FPL letter L-89-114, dated March 23, 1989, were closed on May 3, 1989. FPI 2365, reported open in FPL letter L-89-154, dated April 21, 1989, was closed on April 18, 1989.