Attachment to L-98-260 Page 1 of 4 RF PFR TI LIMIT KP RT IT Y IK1 The Technical Specifications (TS) affected by this report are:

3.1.3.2 Analog Rod Position Indication System 3.1.3.6 Control Rod Insertion Limits 3.2.1 Axial Flux Difference (AFD) 3.2.2 Heat Flux Hot Channel Factor - Fp(Z) 3.2.3 Nuclear Enthalpy Rise Hot Channel Factor - FgH The Control Rod Insertion Limits, AFD, Fq(Z), K(Z), and FgH have been developed using the NRC approved methodology specified in Technical Specification 6.9.1.7.

TS 3.1.3.2 Analog Rod Position Indication System The All Rods Out position for all Shutdown Banks and Control Banks is defined to be 230 steps withdrawn.

TS 3.1.3.6 Control Rod Insertion Limits The control rod banks shall be limited in physical insertion as shown on page 2 for All Rods Out = 230 steps withdrawn.

TS 3.2.1 Axial Flux Difference The AFD limits are provided on page 3.

TS 3.2.2 Heat Flux Hot Channel Factor - Fq(Z)

[Fgj = 2.50 K(Z) is provided on page 4.

TS 3.2.3 Nuclear Enthalpy Rise Hot Channel Factor RTP =

FgH 1.70 PFgH = 0.3 98i0300220 98i023 PDR, ADOCK 05000250 P PDR

~ ~

n n O B O

Figure A2 Axial Flux Difference as a Function of Rated Thermal Power 120 Turkey Point Unit 3- Cycle 1Y M Ch

(-1,100) (+7,1 )

CC oo 80 UN A EPTABLE U ACCEPTA LE CC OP TlON OPERATIO 60 I

O W

I- (-30,50)

ACCEPT BLE

(+2,50) lC OPERATI N o 40 0

0

-40 -30 -20 -10 0 10 20 Axial Flux Difference (%)

f~

~ ~ ~