AECM-85-0350, Discusses Util Commitments Resulting from Proposed Tech Spec Changes Re Acceptable High/Low Pressure Boundary Design for RHR Headspray Line.Handswitches Will Be Removed from Remote Shutdown Panel for Valves E12-F023 & E12-F394
Letter Sequence Other | |
---|---|
Administration Questions
Results
Other: AECM-85-0303, Proposed Tech Specs,Changing Table 3.3.7.4-1, Remote Shutdown Sys Controls by Deleting Item 20, RHR to RCIC Head Spray Line, AECM-85-0350, Discusses Util Commitments Resulting from Proposed Tech Spec Changes Re Acceptable High/Low Pressure Boundary Design for RHR Headspray Line.Handswitches Will Be Removed from Remote Shutdown Panel for Valves E12-F023 & E12-F394, ML20133P171, ML20135E723, ML20135G134, ML20138H894, ML20138J716 | |
MONTHYEARML20133P1711985-08-12012 August 1985
[Table View]Proposed Tech Specs,Reflecting Design Changes & Editorial Clarification Re Leak Rate Testing of RHR to Head Spray Isolation Valve & ECCS Actuation Instrumentation Project stage: Other AECM-85-0228, Application for Amend to License NPF-29,changing Tech Specs to Reflect Design Changes & Editorial Clarifications.Fee Paid1985-08-12012 August 1985 Application for Amend to License NPF-29,changing Tech Specs to Reflect Design Changes & Editorial Clarifications.Fee Paid Project stage: Request ML20135E7231985-08-30030 August 1985 Notice of Violation from Insp on 850708-12 Project stage: Other ML20135G1341985-09-13013 September 1985 Proposed Tech Specs Reflecting one-time Exception for Qualifications of Replacement Individual for Chemistry/ Radiation Control Superintendent Position Project stage: Other ML20135G1291985-09-13013 September 1985 Application for Amend to License NPF-29,requesting one-time Tech Spec Exception for Qualifications of Replacement Individual for Chemistry/Radiation Control Superintendent Position Project stage: Request ML20135F1051985-09-13013 September 1985 Application for Amend to License NPF-29,changing Tech Spec Table 3.3.7.4-1, Remote Shutdown Sys Controls, by Deleting Item 20, RHR to RCIC Head Spray Line. Fee Paid Project stage: Request AECM-85-0263, Forwards Application for Amend to License NPF-29,requesting one-time Tech Spec Exception for Qualifications of Replacement Individual for Chemistry/Radiation Control Superintendent Position.Fee Paid1985-09-13013 September 1985 Forwards Application for Amend to License NPF-29,requesting one-time Tech Spec Exception for Qualifications of Replacement Individual for Chemistry/Radiation Control Superintendent Position.Fee Paid Project stage: Request AECM-85-0303, Proposed Tech Specs,Changing Table 3.3.7.4-1, Remote Shutdown Sys Controls by Deleting Item 20, RHR to RCIC Head Spray Line1985-09-13013 September 1985 Proposed Tech Specs,Changing Table 3.3.7.4-1, Remote Shutdown Sys Controls by Deleting Item 20, RHR to RCIC Head Spray Line Project stage: Other AECM-85-0305, Forwards Resumes of Two Individuals Appointed as Supervisors to Organization Radiation Control Function,Per Request for Addl Info Re 850712 Proposed Change to Tech Spec Figure 6.2.2.-11985-10-0202 October 1985 Forwards Resumes of Two Individuals Appointed as Supervisors to Organization Radiation Control Function,Per Request for Addl Info Re 850712 Proposed Change to Tech Spec Figure 6.2.2.-1 Project stage: Request ML20138J7161985-10-23023 October 1985 Proposed Tech Spec 6.3.1 for one-time Exception of Reg Guide 1.8 Re Qualifications of Chemistry/Radiation Control Superintendent Project stage: Other AECM-85-0346, Application for Amend to License NPF-29,revising Tech Spec 6.3.1 for one-time Exception of Reg Guide 1.8 Re Qualifications of Chemistry/Radiation Control Superintendent1985-10-23023 October 1985 Application for Amend to License NPF-29,revising Tech Spec 6.3.1 for one-time Exception of Reg Guide 1.8 Re Qualifications of Chemistry/Radiation Control Superintendent Project stage: Request ML20138J7011985-10-24024 October 1985 Forwards Application for Amend to License NPF-29,revising Tech Spec 6.3.1 for one-time Exception of Reg Guide 1.8 Re Qualifications of Chemistry/Radiation Control Superintendent.Fee Paid Project stage: Request AECM-85-0350, Discusses Util Commitments Resulting from Proposed Tech Spec Changes Re Acceptable High/Low Pressure Boundary Design for RHR Headspray Line.Handswitches Will Be Removed from Remote Shutdown Panel for Valves E12-F023 & E12-F3941985-10-30030 October 1985 Discusses Util Commitments Resulting from Proposed Tech Spec Changes Re Acceptable High/Low Pressure Boundary Design for RHR Headspray Line.Handswitches Will Be Removed from Remote Shutdown Panel for Valves E12-F023 & E12-F394 Project stage: Other ML20138H8941985-12-11011 December 1985 Proposed Tech Spec,Allowing one-time Exception Re Qualifications of Chemistry/Radiation Control Superintendent Project stage: Other AECM-85-0404, Application for Amend to License NPF-29,revising Tech Spec 6.3.1 to Allow one-time Exception Re Qualifications of Chemistry/Radiation Control Superintendent1985-12-11011 December 1985 Application for Amend to License NPF-29,revising Tech Spec 6.3.1 to Allow one-time Exception Re Qualifications of Chemistry/Radiation Control Superintendent Project stage: Request 1985-10-30 |
ML20198A510 | |
Person / Time | |
---|---|
Site: | Grand Gulf |
Issue date: | 10/30/1985 |
From: | Dale L MISSISSIPPI POWER & LIGHT CO. |
To: | Harold Denton Office of Nuclear Reactor Regulation |
References | |
AECM-85-0350, AECM-85-350, TAC-59439, TAC-59680, TAC-59692, NUDOCS 8511060023 | |
Download: ML20198A510 (2) | |
Similar Documents at Grand Gulf | |
---|---|
Category:CORRESPONDENCE-LETTERS
MONTHYEARML20217F8911999-10-13013 October 1999
[Table view]Forwards Copy of FEMA Region IV Final Rept for 990623-24, Grand Gulf Nuclear Station Exercise.Rept Indicates No Deficiencies or Areas Requiring Corrective Action Identified During Exercise ML20216J8891999-10-0404 October 1999 Forwards Details of Existing Procedural Guidance & Planned Administrative Controls.Util Respectfully Requests NRC Review & Approval of Changes by 991020.Date Will Permit to Implement Changes & Realize Full Benefit During Refueling ML20217B0361999-10-0404 October 1999 Refers to Investigation Conducted by NRC OI Re Activities at Grand Gulf Nuclear Station.Investigation Conducted to deter- Mine Whether Security Supervisor Deliberately Falsified Unescorted Access Authorizations.Allegation Unsubstantiated ML20212J8151999-09-29029 September 1999 Forwards Insp Rept 50-416/99-12 on 990725-0904.One Violation Noted & Being Treated as Noncited Violation.Licensee Conduct of Activities at Grand Gulf Facility Characterized by Safety Conscious Operations,Sound Engineering & Maint Practices ML20216J6811999-09-28028 September 1999 Ack Receipt of ,Transmitting Rev 31 to Physical Security Plan for GGNS Under Provisions of 10CFR50.54(p). NRC Approval Not Required,Based on Determination That Changes Do Not Decrease Effectiveness & Limited Review ML20212J7361999-09-28028 September 1999 Forwards Insp Rept 50-416/99-11 on 990830-0903.No Violations Noted.Purpose of Insp to Review Solid Radioactive Waste Management & Radioactive Matl Transportation Programs ML20212J5321999-09-27027 September 1999 Forwards Insp Rept 50-416/99-14 on 990830-0903.No Violations Noted.Inspectors Determined That Radioactive Waste Effluent Releases Properly Controlled,Monitored & Quantified ML20216J7101999-09-26026 September 1999 Forwards NRC Form 536,in Response to NRC Administrative Ltr 99-03, Preparation & Scheduling of Operator License Examinations ML20216J8141999-09-26026 September 1999 Forwards Proprietary Renewal Applications for Licensed Operators for Wk Gordon & SA Elliott at Grand Gulf Nuclear Station.Proprietary Info Withheld ML20212F5521999-09-23023 September 1999 Forwards SER Accepting Util Analytical Approach for Ampacity Derating Determinations at Grand Gulf Nuclear Station,Unit 1 & That No Outstanding Ampacity Derating Issues as Identified in GL 92-08 Noted ML20212D9211999-09-16016 September 1999 Informs That NRC Staff Completed Midcycle PPR of GGNS on 990818 & Identified No Areas in Which Licensee Performance Warranted Insp Beyond Core Insp Program.Details of Insp Plan Through March 2000 Encl ML20212A9331999-09-13013 September 1999 Forwards Partially Withheld Insp Rept 50-416/99-15 on 990816-20 (Ref 10CFR73.21).One Violation of NRC Requirements Occurred & Being Treated as Ncv,Consistent with App C of Enforcement Policy ML20211P7631999-09-10010 September 1999 Discusses Staff Issuance of SECY-99-204, Kaowool & FP-60 Fire Barriers at Plant.Proposed Meeting to Discuss Subj Issues Will Take Place in Oct or Nov 1999 ML20212A6951999-09-0909 September 1999 Requests That Licensees Affected by Kaowool Fire Barriers Take Issue on Voluntary Initiative & Propose Approach for Resolving Subj Issues.Staff Plans to Meet with Licensees to Discuss Listed Topics ML20212A8341999-09-0909 September 1999 Requests That Licensees Affected by Kaowool Fire Barriers Take Issue on Voluntary Initiative & Propose Approach for Resolving Subj Issues.Staff Plans to Meet with Licensees to Discuss Listed Topics ML20211Q3471999-09-0909 September 1999 Forwards Federal Emergency Mgt Agency Final Rept for 990623 Plant Emergency Preparedness Exercise.No Deficiencies Noted & One Area Requiring Corrective Action Identified ML20211Q3091999-09-0909 September 1999 Forwards Safety Evaluation Accepting BWROG Rept, Prediction of Onset of Fission Gas Release from Fuel in Generic BWR, Dtd July 1996 ML20211Q4861999-09-0808 September 1999 Informs That Util Has Discovered Dose Calculation Utilized non-conservative Geometry Factor for Parameter.Calculation Error Being Evaluated in Accordance with Corrective Action Program ML20211Q0091999-09-0808 September 1999 Forwards Request for Addl Info Re Individual Plant Exam of External Events for Grand Gulf Nuclear Station,Unit 1. Response Requested by 000615 ML20211N4301999-09-0808 September 1999 Discusses Proposed Meeting to Discuss Kaowool Fire Barriers. Staff Requesting That Affected Licensees Take Issue on Voluntary Initative & Propose Approach for Resolving Issues ML20211P4171999-09-0707 September 1999 Ack Receipt of ,Which Transmitted Addendum to Rev 30 to Physical Security Plan for Ggns,Per 10CFR50.54(p).NRC Approval Is Not Required,Since Util Determined That Changes Do Not Decrease Effectiveness of Plan ML20211P4121999-09-0707 September 1999 Requests NRC Staff Review & Approval of Integrated Nuclear Security Plan (Insp) & Integrated Security Training & Qualification Plan (Ist&Q), for Use by All Entergy Operations,Inc.Encl Withheld,Per 10CFR2.790(d) ML20211K6061999-08-31031 August 1999 Informs That Plant Has No Candidates to Take 991006 Generic Fundamentals Exam ML20211K5641999-08-31031 August 1999 Forwards Rev 39 to Grand Gulf Nuclear Station Emergency Plan Non-Safety Related, IAW 10CFR50,App E,Section V. Changes Do Not Decrease Effectiveness of Plan & Continues to Meets Stds of 10CFR50.47(b) & Requirements of App E ML20211J2321999-08-26026 August 1999 Advises That Info Contained in to Support NRC Review of GE Rept, Prediction of Onset of Fission Gas Release from Fuel in Generic BWR, Will Be Withheld from Public Disclosure ML20211J3761999-08-25025 August 1999 Corrected Ltr Informing That Info Provided (on Computer Disk & in Ltr to Ineel ) Marked as Proprietary Will Be Withheld from Public Disclosure Per 10CFR2.790(b)(5) & Section 103(b) of AEA of 1954,as Amended.Corrected 990827 ML20211F4881999-08-25025 August 1999 Advises That Info Submitted by 990716 Application & Affidavit Containing Diskette & to Ineel Mareked Proprietary Will Be Withheld from Public Disclosure,Per 10CFR2.790(b)(5) & Section 103(b) of AEA of 1954 ML20211F7751999-08-24024 August 1999 Forwards Insp Rept 50-416/99-10 on 990809-13.No Violations Noted.Insp Covered Licensed Operator Requalification Program & Observations of Requalification Activities ML20211C4381999-08-20020 August 1999 Forwards Rev 31 to Physical Security Plan for Protection of Grand Gulf Nuclear Station,Iaw 10CFR50.54(p).Util Has Determined That Rev Does Not Decrease Effectiveness of Plan. Encl Withheld,Per 10CFR73.21 ML20211C5101999-08-19019 August 1999 Forwards Certified Copies of Liability Insurance Policy Endorsements Issued in First Half of 1999 for Each Entergy Operations,Inc Nuclear Unit,Per 10CFR140.15 ML20211B3761999-08-16016 August 1999 Submits Voluntary Response to NRC AL 99-02, Operating Reactor Licensing Actions Estimates, for Fys 2000 & 2001, ML20211A9501999-08-12012 August 1999 Discusses 990720-21 Workshop Conducted in Region IV Ofc,Re Exchange of Info in Area of Use of Risk Insights in Regulatory Activities.List of Attendees,Summary of Topic & Issues,Agenda & Copies of Handouts Encl ML20211A9481999-08-12012 August 1999 Informs of Completion of Analysis of Heat Transfer in Cooler During Fan Coast Down & Concludes That Potential Exists for Steam Foundation,Under Conditions Where Dcw Sys Flow Is Lost Prior to Full Isolation Valve Closure ML20210P8411999-08-0909 August 1999 Forwards Insp Rept 50-416/99-09 on 990613-0724.No Violations Noted.Activities at Facility Generally Characterized by safety-conscious Operations,Sound Engineering & Maint Practices & Careful Radiological Work Controls ML20210N6401999-08-0303 August 1999 Informs That Eighteeen Identified Penetrations Will Be Restored to Conformance with Licensing Requirements Prior to Restart from RFO10,scheduled for Fall 1999,per GL 96-06. Example of Piping Analysis Being Performed,Encl ML20210L1461999-08-0303 August 1999 Informs That NRC Plans to Administer Gfes of Written Operator Licensing Exam on 991006.Requests Submittal of Ltr Identifying Individuals Taking Exam,Personnel Allowed Access to Exams & Mailing Address for Exams ML20210K1951999-07-30030 July 1999 Forwards Insp Rept 50-416/99-03 on 990405-08 & 0510-11.No Violations Identified ML20211K7491999-07-30030 July 1999 Forwards Ltr Rept Documenting Work Completed Under JCN-W6095,analyses Performed at Ineel to Calculate Minimum Time to Fuel Pin Failure in Boiling Water Reactors (BWR) ML20210K6661999-07-29029 July 1999 Forwards Fitness for Duty Program Performance six-month Rept for Period Covering Jan-June 1999,per 10CFR26.71 ML20210F3591999-07-26026 July 1999 Forwards Proprietary Version & Redacted Version of Wyle Test Rept M-J5.08-Q1-45161-0-8.0-1-0,re Pressure Locking & Thermal Binding Test Program.Proprietary Version Withheld ML20210E3251999-07-23023 July 1999 Forwards Insp Rept 50-416/99-07 on 990622-25.No Violations Noted.Emergency Plan & Procedures During Biennial Emergency Preparedness Exercise Was Conducted ML20210D2401999-07-21021 July 1999 Informs of Resignation of Operator WE Griffith,License OP-20806-1,from Entergy Operations,Inc ML20209J0311999-07-16016 July 1999 Forwards Proprietary Info Supporting Review of Generic Alternate Source Term Request.Proprietary Info Withheld Per 10CFR2.790 ML20209G4791999-07-15015 July 1999 Forwards Proposed Emergency Plan Change as Addendum to Changes Previously Submitted Via GNRO-98/00028 & GNRO-99/00007,for NRC Review & Approval ML20210B1031999-07-15015 July 1999 Forwards Insp Rept 50-416/99-08 on 990502-0612.Determined That Three Severity Level IV Violations Occurred & Being Treated as Noncited Violations ML20210H3211999-07-14014 July 1999 Forwards Proprietary Info Supporting Review of 970506 Submittal of BWROG Rept, Prediction of Onset of Fission Gas Release from Fuel in Generic Bwr. Proprietary Info Withheld Per 10CFR2.790 ML20209D7511999-07-0909 July 1999 Responds to RAI on GL 92-01,rev 1,suppl 1, Rv Structural Integrity. as Result of NRC Review of Util Responses,Info Revised in Rvid & Rvid Version 2 Will Be Released ML20209D7671999-07-0101 July 1999 Submits Response to Violations Noted in Insp Rept 50-416/99-02 on 990222-26 & 0308-12.Corrective Actions: Contractor Performance Has Been re-evaluated in Regards to UFSAR Reviews ML20196K4901999-07-0101 July 1999 Discusses Relief Requests PRR-E12-01,PRR-E21-01,PRR-E22-01, PRR-P75-01,PRR-P81-01,VRR-B21-01,VRR-B21-02,VRR-E38-01 & VRR-E51-01 Submitted by EOI on 971126 & 990218.SE Accepting Alternatives Proposed by Util Encl ML20196J5711999-06-30030 June 1999 Advises That Versions of Submitted Info in 990506 Application & Affidavit, Re Proposed Amend to Revise Ts,Marked Proprietary Will Be Withheld from Public Disclosure,Per 10CFR2.790(b)(5) & Section 103(b) of AEA 1999-09-09 Category:INCOMING CORRESPONDENCE MONTHYEARML20216J8891999-10-0404 October 1999
[Table view]Forwards Details of Existing Procedural Guidance & Planned Administrative Controls.Util Respectfully Requests NRC Review & Approval of Changes by 991020.Date Will Permit to Implement Changes & Realize Full Benefit During Refueling ML20216J7101999-09-26026 September 1999 Forwards NRC Form 536,in Response to NRC Administrative Ltr 99-03, Preparation & Scheduling of Operator License Examinations ML20216J8141999-09-26026 September 1999 Forwards Proprietary Renewal Applications for Licensed Operators for Wk Gordon & SA Elliott at Grand Gulf Nuclear Station.Proprietary Info Withheld ML20211Q4861999-09-0808 September 1999 Informs That Util Has Discovered Dose Calculation Utilized non-conservative Geometry Factor for Parameter.Calculation Error Being Evaluated in Accordance with Corrective Action Program ML20211P4121999-09-0707 September 1999 Requests NRC Staff Review & Approval of Integrated Nuclear Security Plan (Insp) & Integrated Security Training & Qualification Plan (Ist&Q), for Use by All Entergy Operations,Inc.Encl Withheld,Per 10CFR2.790(d) ML20211K6061999-08-31031 August 1999 Informs That Plant Has No Candidates to Take 991006 Generic Fundamentals Exam ML20211K5641999-08-31031 August 1999 Forwards Rev 39 to Grand Gulf Nuclear Station Emergency Plan Non-Safety Related, IAW 10CFR50,App E,Section V. Changes Do Not Decrease Effectiveness of Plan & Continues to Meets Stds of 10CFR50.47(b) & Requirements of App E ML20211C4381999-08-20020 August 1999 Forwards Rev 31 to Physical Security Plan for Protection of Grand Gulf Nuclear Station,Iaw 10CFR50.54(p).Util Has Determined That Rev Does Not Decrease Effectiveness of Plan. Encl Withheld,Per 10CFR73.21 ML20211C5101999-08-19019 August 1999 Forwards Certified Copies of Liability Insurance Policy Endorsements Issued in First Half of 1999 for Each Entergy Operations,Inc Nuclear Unit,Per 10CFR140.15 ML20211B3761999-08-16016 August 1999 Submits Voluntary Response to NRC AL 99-02, Operating Reactor Licensing Actions Estimates, for Fys 2000 & 2001, ML20211A9481999-08-12012 August 1999 Informs of Completion of Analysis of Heat Transfer in Cooler During Fan Coast Down & Concludes That Potential Exists for Steam Foundation,Under Conditions Where Dcw Sys Flow Is Lost Prior to Full Isolation Valve Closure ML20210N6401999-08-0303 August 1999 Informs That Eighteeen Identified Penetrations Will Be Restored to Conformance with Licensing Requirements Prior to Restart from RFO10,scheduled for Fall 1999,per GL 96-06. Example of Piping Analysis Being Performed,Encl ML20211K7491999-07-30030 July 1999 Forwards Ltr Rept Documenting Work Completed Under JCN-W6095,analyses Performed at Ineel to Calculate Minimum Time to Fuel Pin Failure in Boiling Water Reactors (BWR) ML20210K6661999-07-29029 July 1999 Forwards Fitness for Duty Program Performance six-month Rept for Period Covering Jan-June 1999,per 10CFR26.71 ML20210F3591999-07-26026 July 1999 Forwards Proprietary Version & Redacted Version of Wyle Test Rept M-J5.08-Q1-45161-0-8.0-1-0,re Pressure Locking & Thermal Binding Test Program.Proprietary Version Withheld ML20210D2401999-07-21021 July 1999 Informs of Resignation of Operator WE Griffith,License OP-20806-1,from Entergy Operations,Inc ML20209J0311999-07-16016 July 1999 Forwards Proprietary Info Supporting Review of Generic Alternate Source Term Request.Proprietary Info Withheld Per 10CFR2.790 ML20209G4791999-07-15015 July 1999 Forwards Proposed Emergency Plan Change as Addendum to Changes Previously Submitted Via GNRO-98/00028 & GNRO-99/00007,for NRC Review & Approval ML20210H3211999-07-14014 July 1999 Forwards Proprietary Info Supporting Review of 970506 Submittal of BWROG Rept, Prediction of Onset of Fission Gas Release from Fuel in Generic Bwr. Proprietary Info Withheld Per 10CFR2.790 ML20209D7671999-07-0101 July 1999 Submits Response to Violations Noted in Insp Rept 50-416/99-02 on 990222-26 & 0308-12.Corrective Actions: Contractor Performance Has Been re-evaluated in Regards to UFSAR Reviews ML20209B6081999-06-30030 June 1999 Submits Response to NRC GL 98-01,Suppl 1, Y2K Readiness of Computer Sys at Nuclear Power Plants. Disclosure Encl ML20195J6351999-06-16016 June 1999 Forwards Addendum to Rev 30 of GGNS Physical Security Plan IAW 10CFR50.54(p).Addendum Is Submitted to Announce Relocation/Reconfiguration of Plant Central & Secondary Alarm Station Facilities.Rev Withheld,Per 10CFR73.21 ML20195G0281999-06-0909 June 1999 Submits Summary on Resolution of GL 96-06 Re Eighteen Penetrations Previously Identified as Being Potentially Susceptible to Overpressurization ML20207F5041999-06-0202 June 1999 Forwards Updated Medical Rept IAW License Condition 3 for DA Killingsworth License OP-20942-1.Without Encls ML20206P2981999-05-13013 May 1999 Forwards Responses to RAI Re GL 96-05, Periodic Verification of Design-Basis Capability of Safety-Related Movs, Cancelling 990402 Submittal ML20206N1921999-05-10010 May 1999 Provides Revised Attachment 2 for Alternative Request IWE-02,originally Submitted 990429 Re Bolt Torque or Tension Testing of Class Mc pressure-retaining Bolting as Specified in Item 8.20 of Article IWE-2500,Table IWE-2500-1 ML20206J0941999-05-0404 May 1999 Forwards Proprietary & Redacted ME-98-001-00,both Entitled, Pressure Locking & Thermal Binding Test Program on Two Gate Valves with Limitorque Actuators. Rept ME-98-002-00 Re Flexible Wedge Gate Valves,Encl.Proprietary Rept Withheld ML20206E7811999-04-29029 April 1999 Proposes Alternatives to Requirements of ASME B&PV Code Section XI,1992 Edition,1992 Addenda,As Listed.Approval of Alternative Request on or Before 990915,requested ML20206D8171999-04-29029 April 1999 Informs NRC of Results of Plant Improvement Considerations Identified in GGNS Ipe,As Requested in NRC . Licensee Found Efforts Have Minimized Extent of Radiological Release in Unlikely Event That Severe Accident Occurred ML20206D7281999-04-28028 April 1999 Forwards South Mississippi Electric Power Association 1998 Annual Rept, Per 10CFR50.71(b).Licensee Will Submit 1998 Annual Repts for System Energy Resources,Inc,Entergy Mississippi,Inc & EOI as Part of Entergy Corp Annual Rept ML20206C9551999-04-22022 April 1999 Forwards 1999 Biennial Emergency Preparedness Exercise Scenario. Without Encl ML20205M1311999-04-0202 April 1999 Forwards Response to RAI Re GL 96-05, Periodic Verification of Design-Basis Capability of Safety-Related Motor-Operated Valves. Info Was Discussed During Conference Call with NRC on 990126.Wyle Position Paper Encl.Subj Paper Withheld ML20205H5861999-04-0101 April 1999 Requests Relief from ASME B&PV Code,Section XI for Period of Time That Temporary non-code Repair Was in Effect,Per 10CFR50.55a(g)(5)(iii) ML20205F1781999-03-31031 March 1999 Forwards Consolidated Entergy Submittal to Document Primary & Excess Property Damage Insurance Coverage for Nuclear Sites of Entergy Operations,Inc,Per 10CFR50.54(w)(3) ML20196K7101999-03-26026 March 1999 Submits Reporting & Recordkeeping for Decommissioning Planning,Per 10CFR50.75(f)(1) ML20205A6511999-03-25025 March 1999 Responds to NRC Re Violations Noted in Insp Rept 50-416/99-01 on 990201-05.Corrective Actions:Program Will Be Implemented to Ensure Accessible Areas with Radiation Levels Greater than 1000 Mrem/H ML20204E7391999-03-15015 March 1999 Forwards Objectives for June 1999 Emergency Preparedness Exercise for Plant.Without Encl ML20207H9291999-03-0404 March 1999 Submits Update to Original Certification of Grand Gulf Nuclear Station Simulation Facility IAW Requirements of 10CFR55.45(b)(5) ML20207E3081999-03-0303 March 1999 Informs That GGNS Severe Accident Mgt Implementation Was Completed on 981223.Effort Was Worthwhile & Station Ability to Respond & Mitigate Events That May Lead to Core Melt Has Been Enhanced ML20207E3221999-03-0303 March 1999 Notifies of Change in Status of Mj Ellis,License SOP-43846. Conditional License Requested to Accommodate Medical Condition.Revised NRC Form 396 with Supporting Medical Evidence Attached.Without Encls ML20207A8161999-02-24024 February 1999 Forwards 1998 Annual Operating Rept for Ggns,Unit 1. Listed Attachments Are Encl ML20207A9901999-02-24024 February 1999 Informs That Util Has No Candidates from GGNS to Nominate for Participation in Planned Gfes,Scheduled for 990407 ML20203A1551999-02-0101 February 1999 Forwards Grand Gulf Nuclear Station Fitness for Duty Program Performance six-month Rept for Reporting Period 980701-981231 ML20202G0791999-01-26026 January 1999 Informs That He Mcknight Has Been Permanently Reassigned from Position Requiring License to Perform Assigned Duties. License Is No Longer Needed,Effective 981231 ML20199K4151999-01-20020 January 1999 Forwards Proposed Addendum to Emergency Plan Changes Previously Submitted Via GNRO-98/00028 for NRC Review & Approval as Required by 10CFR50.54(q) & 50.4 ML20199K6771999-01-14014 January 1999 Provides Notification of Planned ERDS Software Change Scheduled to Take Place on 990215 ML20199D8811999-01-11011 January 1999 Submits Response to SE JOG Program on Periodic Verification of motor-operated Valves,In Response to GL 96-05 ML20199D9521999-01-0808 January 1999 Informs That CE Cresap,License SOP-4220-4,has Been Permanently Reassigned from Position Requiring License & No Longer Has Need for License,Per 10CFR50.74 ML20199A6081999-01-0606 January 1999 Submits List of Plant Info Brochures Disseminated Annually to Public & List of Updated State &/Or Local Emergency Plan Info,Per NRC Administrative Ltr 94-07, Distribution of Site-Specific & State Emergency Planning Info ML20202B7531998-12-21021 December 1998 Submits Ltr Confirming Discussion with J Tapia,Documenting Extension for Response to NOV 50-416/98-13.Util Response Will Be Submitted by 990212 1999-09-08 Category:UTILITY TO NRC MONTHYEARAECM-90-0169, Forwards Operator Licensing Natl Exam Schedule for FY91 Through FY94,per Generic Ltr 90-071990-09-17017 September 1990
[Table view]Forwards Operator Licensing Natl Exam Schedule for FY91 Through FY94,per Generic Ltr 90-07 AECM-90-0172, Forwards Endorsement 67 to Nelia Policy NF-257 & Endorsement 46 to Maelu Policy MF-1061990-09-17017 September 1990 Forwards Endorsement 67 to Nelia Policy NF-257 & Endorsement 46 to Maelu Policy MF-106 AECM-90-0174, Forwards List of Submittals Pending NRR Review Re Grand Gulf Licensing Activities1990-09-14014 September 1990 Forwards List of Submittals Pending NRR Review Re Grand Gulf Licensing Activities AECM-90-0165, Forwards Addl Info on NRC Bulletin 90-001, Loss of Fill-Oil in Transmitters Mfg by Rosemount1990-09-12012 September 1990 Forwards Addl Info on NRC Bulletin 90-001, Loss of Fill-Oil in Transmitters Mfg by Rosemount AECM-90-0158, Forwards Quarterly Status Rept for Reg Guide 1.97 Re Neutron Monitoring Sys for Period Ending 900630.Rept Includes Major Actions Completed to Date for Unit ex-core Sys.Estimated Milestone Schedule for Activities Also Encl1990-09-0808 September 1990 Forwards Quarterly Status Rept for Reg Guide 1.97 Re Neutron Monitoring Sys for Period Ending 900630.Rept Includes Major Actions Completed to Date for Unit ex-core Sys.Estimated Milestone Schedule for Activities Also Encl AECM-90-0163, Forwards Endorsement 61 to Nelia Policy NF-257,Endorsement 40 to Maelu Policy MF-106,Endorsement 62 to Nelia Policy NF-257,Endorsement 41 to Maelu Policy MF-106 & Endorsement 63 to Nelia Policy NF-2571990-09-0606 September 1990 Forwards Endorsement 61 to Nelia Policy NF-257,Endorsement 40 to Maelu Policy MF-106,Endorsement 62 to Nelia Policy NF-257,Endorsement 41 to Maelu Policy MF-106 & Endorsement 63 to Nelia Policy NF-257 AECM-90-0161, Forwards Quarterly Status Rept Re Degraded Core Accident Hydrogen Control Program, for Apr-June 19901990-08-30030 August 1990 Forwards Quarterly Status Rept Re Degraded Core Accident Hydrogen Control Program, for Apr-June 1990 AECM-90-0149, Forwards Semiannual Radioactive Effluent Release Rept for Jan-June 1990 & Rev 3 to Process Control Program1990-08-30030 August 1990 Forwards Semiannual Radioactive Effluent Release Rept for Jan-June 1990 & Rev 3 to Process Control Program AECM-90-0162, Forwards fitness-for-duty 6-month Rept for Period Ending June 1990,per 10CFR26.Success of Program Evident in Statistical Data Indicating Extremely Low Incident Rate1990-08-29029 August 1990 Forwards fitness-for-duty 6-month Rept for Period Ending June 1990,per 10CFR26.Success of Program Evident in Statistical Data Indicating Extremely Low Incident Rate ML20028G8591990-08-27027 August 1990 Forwards Updated Svc List to Be Used for Licensee Correspondence.Requests That Author Be Primary Addressee for All Correspondence Re Plant AECM-90-0144, Forwards Security Boundary Upgrade Bimonthly Status Rept for Period Ending 900731,per 900330 Commitment.Rept Covering Period 900801-0930 Will Be Submitted in Oct 19901990-08-22022 August 1990 Forwards Security Boundary Upgrade Bimonthly Status Rept for Period Ending 900731,per 900330 Commitment.Rept Covering Period 900801-0930 Will Be Submitted in Oct 1990 ML20056B3511990-08-20020 August 1990 Suppls Info Re 900806 Application for Amend to License NPF-29,changing Tech Specs on Alternate DHR Sys,Per NRC Comments.Proposed Tech Spec 3/4.5.2 Encl AECM-90-0147, Informs That Annual Emergency Preparedness Exercise for Facility Scheduled for Wk of 9108261990-08-14014 August 1990 Informs That Annual Emergency Preparedness Exercise for Facility Scheduled for Wk of 910826 AECM-90-0142, Forwards Supplemental Info Re 900705 Application for Amend to License NPF-29,revising Tech Specs Due to Addition of Alternate DHR Sys1990-08-0909 August 1990 Forwards Supplemental Info Re 900705 Application for Amend to License NPF-29,revising Tech Specs Due to Addition of Alternate DHR Sys AECM-90-0143, Notifies That Cd Bland No Longer Employed by Util,Effective 9007191990-08-0202 August 1990 Notifies That Cd Bland No Longer Employed by Util,Effective 900719 AECM-90-0139, Forwards Endorsement 68 to Nelia Policy NF-257,Endorsement 47 to Maelu Policy MF-106 & Revised Endorsement 35 to Maelu Policy MF-1061990-08-0202 August 1990 Forwards Endorsement 68 to Nelia Policy NF-257,Endorsement 47 to Maelu Policy MF-106 & Revised Endorsement 35 to Maelu Policy MF-106 ML20055J0551990-07-27027 July 1990 Forwards Summary of Environ Protection Program Re Const of Unit for 6-months Ending 900630,per Exhibit 2-A in Subsection 3.E.1 of CPPR-119 AECM-90-0136, Forwards Executed Amend 4 to Indemnity Agreement B-72,per NRC 891214 Request1990-07-27027 July 1990 Forwards Executed Amend 4 to Indemnity Agreement B-72,per NRC 891214 Request AECM-90-0130, Forwards Corrected Pages to Rev 17 to Physical Security Plan.Pages Withheld (Ref 10CFR73.21)1990-07-17017 July 1990 Forwards Corrected Pages to Rev 17 to Physical Security Plan.Pages Withheld (Ref 10CFR73.21) ML20044A9251990-07-0909 July 1990 Forwards Rev 1 to Relief Request I-00018 Correcting Valve Number & Description of One Component.Review & Approval Requested Prior to 901001 ML20044A7861990-06-29029 June 1990 Responds to NRC 900601 Ltr Re Violations Noted in Insp Rept 50-416/90-08.Corrective Actions:Operations Superintendent Counseled Individuals Re Inoperable Reactor Water Level Transmitter & Met W/All Shift Senior Reactor Operators AECM-90-0121, Withdraws 880831 & 890324 Proposed Amends,Deleting Certain Test,Vent & Drain Valves from Tech Spec Table 3.6.4-11990-06-27027 June 1990 Withdraws 880831 & 890324 Proposed Amends,Deleting Certain Test,Vent & Drain Valves from Tech Spec Table 3.6.4-1 AECM-90-0115, Forwards List of Followup Actions as Result of NRC Requalification Reexam of Three Licensed Operators on 900531.Lessons Learned Guideline Will Be Prepared Re Ability of Training Personnel to Evaluate Simulator Crew1990-06-26026 June 1990 Forwards List of Followup Actions as Result of NRC Requalification Reexam of Three Licensed Operators on 900531.Lessons Learned Guideline Will Be Prepared Re Ability of Training Personnel to Evaluate Simulator Crew ML20044A2931990-06-22022 June 1990 Responds to NRC Request for Addl Info Re Boraflex Gap Analysis.If Vibratory Ground Motion Exceeding OBE Occurs,Per 10CFR100,App a & as Previously Committed,Plant Will Be Shut Down.Listed Addl Surveillance Will Be Performed ML20043G6231990-06-14014 June 1990 Forwards Evidence That Cash Flow Would Be Available for Payment of Deferred Premium Obligation for Facility.Sys Energy Resources,Inc Responsible for Generating 90% of Required Cash Flow ML20043G3341990-06-11011 June 1990 Forwards Rev 9 to GGNS-TOP-1A, Operational QA Manual, for Evaluation ML20043G5861990-06-0808 June 1990 Forwards Bimonthly Status Repts Re Security Boundary Upgrade Project for Period Ending 900531 ML20043F5121990-06-0808 June 1990 Forwards List of Directors & Officers of Entergy Operations, Inc.Operation of All Plants Transferred to Entergy on 900606 ML20043E8011990-06-0707 June 1990 Forwards Nonproprietary ANF-90-060(NP), Criticality Safety Analysis for Grand Gulf Fuel Storage Racks W/ANF-1.4 Fuel Assemblies. ML20043E7831990-06-0707 June 1990 Forwards Updated Svc List to Be Used Re Plant Correspondence.Requests WT Cottle Be Primary Addressee for All Correspondence Concerning Plant ML20043E8161990-06-0606 June 1990 Informs That Sys Energy Resources,Inc Received Necessary Regulatory Approvals to Transfer Performance Activities for Facility to Entergy Operations & All Conditions in Amend 9 to CP CPPR-119 Implemented,Effective on 900606 ML20043F2061990-06-0606 June 1990 Forwards 1989 Annual Financial Repts for Sys Energy Resources,Inc & South Mississippi Electric Power Assoc ML20043E8111990-06-0606 June 1990 Informs That Sys Energy Resources,Inc Received Necessary Regulatory Approvals to Transfer Operating Responsibility for Facility to Entergy Operations & All Conditions in Amend 65 to License NPF-29 Implemented,Effective on 900606 ML20043C8611990-05-31031 May 1990 Forwards Preliminary Drafts of Plant Specific Tech Specs in Order to Facilitate NRC Validation of BWR Owners Group Improved Tech Specs,Per NRC Request.Understands That Util & NRC Will Meet During Wk of 900716 to Discuss NRC Review ML20043B6811990-05-24024 May 1990 Forwards Degraded Core Accident Hydrogen Control Program, Quarterly Status Rept for Jan-Mar 1990 ML20043B6021990-05-23023 May 1990 Confirms NRC Understanding That Safety Evaluation Will Be Written for Use of New Tech Spec 3.0.4 Flexibility Regardless of Plant Condition at Time Flexibility Required ML20043B2471990-05-18018 May 1990 Forwards Final Response to Generic Ltr 89-04, Guidance on Developing Acceptable Inservice Testing Programs & Rev 4 to Pump & Valve Inservice Testing Program. ML20043A9651990-05-17017 May 1990 Forwards Draft Tech Specs for Power Distribution Limits,Rcs, ECCS & Plant Sys as Part of Util Involvement W/Bwr Owners Group as BWR-6 Lead Plant ML20042G6931990-05-0909 May 1990 Forwards Rev 4 to Fire Hazards Analysis. Design Changes Include Installation of Alternate DHR Sys & Access Hatch in Pipe Chase ML20042G8681990-05-0909 May 1990 Forwards Response to Recommendations Re Areas of Concern Noted in NRC SER Dtd 900316 & 900316 Request for Addl Info Re Design Criteria for Cable Tray Supports in Turbine Bldg ML20042G6731990-05-0909 May 1990 Notifies of Cancellation of Emergency Plan Procedure 10-S-01-13, Onsite Radiological Monitoring. Info Incorporated Into Procedure 10-S-01-14,Rev 13, Radiological Monitoring. ML20042F4891990-05-0404 May 1990 Requests Extension of 90 Days to Provide Addl Time for Securities & Exchange Commission Review Re Implementation of Amend 65 to License NPF-29 ML20042F4441990-05-0404 May 1990 Forwards Response to Generic Ltr 89-19 Re USI A-47, Safety Implications of Control Sys in LWR Nuclear Power Plants. Plant Has Adequate Automatic Reactor Vessel Overfill Protection,Procedures & Tech Specs ML20042F1791990-04-30030 April 1990 Responds to NRC 900402 Ltr Re Violations Noted in Insp Rept 50-416/90-03.Corrective Actions:Valves Closed,Effectively Isolating Flow of Contaminated Water Into Makeup Water Sys & Demineralized Water Sys Flushed & Cleaned of Contamination ML20042F1811990-04-30030 April 1990 Responds to Generic Ltr 89-15, Emergency Response Data Sys. Util Volunteers to Participate in Emergency Response Data Sys ML20042F3711990-04-30030 April 1990 Forwards Certificate of Insurance for Nuclear Property Insurance Submitted by Nuclear Mutual Ltd for Policy Period 900401-910401 & Certificate of Insurance Evidencing Increased Excess Property Insurance,Per 900330 Ltr ML20042F1751990-04-30030 April 1990 Advises That Util Will Not Be Able to Provide Complete Supplemental Summary Rept on Dcrdr by 900430,as Indicated in Util 891221 Ltr.Supplemental Rept Will Be Submitted by 900930 ML20012F3311990-04-0202 April 1990 Forwards GE Affidavit Requesting That All Drawings Presently Denoted as Proprietary in Rev 4 to Updated FSAR Re Offgas Sys Should Remain Proprietary (Ref 10CFR2.790) ML20012E2961990-03-26026 March 1990 Forwards Updated Svc List for NRC Correspondence to Util. Facility Fee Bills Sent to Wrong Primary Addressee ML20011F2171990-02-23023 February 1990 Responds to NRC 900131 Ltr Re Violations Noted in Insp Rept 50-416/89-30.Corrective Actions:Quality Deficiency Rept Initiated to Document & Resolve Incident & Incident Rept & Reportable Events Procedure Enhanced 1990-09-08 |
Text
_
.r ,
MISSISSIPPI POWER & LIGHT COMPANY Helping Build Mississippi EdHil6llddE P. O. BOX 1640 J ACKSON, MISSISSIPPl 39215-1640 October 30, 1985 NUCLEM UCENSING & SAFETY DEPMTMENT U. S. Nuclear Regulatory Commission Office of Nuclear Reactor Regulation Washington, D. C. 20555 Attention: Mr. Harold R. Denton, Director
Dear Mr. Denton:
SUBJECT:
Grand Gulf Nuclear Station Unit 1 Docket o. 50-416 LicenseiNo. NPF-29 File: 0260/0840/L-860.0 Additional Information on PCOL-85/11 and 85/16 AECM-85/0350
References:
- 1) Letter from Mr. O. D. Kingsley, Jr. to Mr. Harold R. Denton dated August 12, 1985, MP&L correspondence AECM-85/0228
- 2) Letter from Mr. O. D. Kingsley, Jr. to Mr. Harold R. Denton dated September 13, 1985, MP&L correspondence AECM-85/0303 Recent discussions between Mississippi Power and Light (MP&L) and NRC staff concerning the proposed technical specification' changes in References 1 and 2 have resulted in additional commitments to the NRC staff to assure an acceptable high/ low pressure boundary design for the Residual Heat Removal (RHR) head spray line. In addition to the information provided in References 1 and 2, MP&L will remove handswitches from the remote shutdown panel for valves E12-F023 and E12-F394 which are located on the RHR head spray line. The removal of these handswitches ensures that the E12-F023 and E12-F394 valves cannot be inadvertently opened from the remote shutdown panel. The control circuits for both these valves in the main control room are designed with pressure interlocks that prohibit their opening unless reactor pressure is below the setpoint specified as item 6.d in Technical Specification Table 3.3.2-2. Section 7.6.1.3 of the GGNS FSAR describes this pressure interlock for the E12-F023 valve and this description is also applicable to the control circuit for the E12-F394 valve added as a result of the design change described in Reference 1.
MP&L will delete the handswitch from the remote shutdown panel for the E12-F'!94 valve prior to startup from the present plant outage. The handswitch for the E12-F023 valve will be deleted from the remote shutdoun panel when the technical specification change associated with Reference 2 is approved by the NRC and when an appropriate " window" is available to enter the LCO required to perform this work.
jO0023851030 P DOCK 05000426 '7 0
PDR J16AECM85102901 - 1 Member Middle South Utilities System 0 a
4
= - . s AECM-85/0350
' # # ~ Pcga 2 If additional information is-desired feel free to contact my office.
Yours truly, L. F. Dale Director WJH/SHH: bas I cc: Mr..J. B. Richard
" Mr. O. D. Kingsley, Jr.
Mr. R. B. McGehee Mr. N. S. Reynolds
' Mr. H. L. Thomas Mr. R. C. Butcher Mr. James M. Taylor, Director Office of Inspection & Enforcement U.'S. Nuclear Regulatory Commission Washington, D. C. 20555 i
Dr. J. Nelson Grace, Regional Administrator U. S. Nuclear Regulatory Coumission Region II
. 101 Marietta St...N. W., Suite'2900
. Atlanta, Georgia 30323 Dr. Alton B. Cobb
> State Health Officer State Board of Health Box 1700 Jackson, Mississippi 39205 t
~J16AECM85102901 - 2 bl- J