7..- .

7 .

A l t. ;R A H SERVICE. CENTER /b 1 -

HIDDLETOLN, VA. 22645 g g],{,(rg ', g {y O g i g

! @.im.9@yl4[EfEjl$ssg@@p Attachment to 1 0131821Ad84002 10/11/78 TFX ESB DATA B PGHA Hovc-235-78 01 r10RSHAM, PA OCTOBER 11 s1TSSARD - REGION III HAYNES - REGION V 7- p g j gg -

XOOS - IE:HQ USNRC OFFICE OF'INSPFCTION AND E.NFORCEMENT C 631, PARK AVENUE O,.

KING OF PRUSSIA, PA 16406, f0 E-11.

s m g -

' ~

EAIDE INDUSTRIAL dATiE.RY DIVISION OF ESB INCORPORATED BELIEVES ,

THERE IS A POTENTIAL PROBLEM wITH PRODUCT IT HAS SUPPLIED RECENTLY }

TU SOUTHERN CALIFORNIA EDIS0N FOR TetEIR S A.N. O N O F R E UNITS 2 AND 3 ,!

AND CONSUHERS POWER ro. FOR THEIR HIDLAND UNITS 1 AND C, bbICH H A Yf BE ,iEPORT ABLE UNDEd* 10CFR 21. IT HAS BEEN OETERPINED BY EX1DE W SEISMIC ANALYSIS C GSULTANT THAT AN ADDITIONAL ISOLATION BAR IS RE00!dE0 10 6E ADDED TO THE CLASS 1E BATTkRY RACKS TO ISOLATE, IN Tw0-CELL INCREMENTS, THE :$UILD UP OF tt0RIZONT AL HOME.NTUM IN A STRING OF CELLS ON A BATTEPY.RACKLSTEP DURING A S E I S t'I C EVENT.

THIS ADDITiuNAL PIEC'E IS NOT REQUIRED FOR THE STRUCTURAL IfJTEGRITY B U V F O,R T rt E ISOLATIdh DF MOMENTUM AND WILL HDT AFFECT THE S1HUCTURAL INTEG#ITY OF T HE C L[A,S S IL 6ATTERY RACKS.

EXIDE IS CURRENTLY WORFING ON THE DESIGN OF SUCH AN ACCESSORY FOR THE ADDITION 10 inE PRODUCT SUPPLIED FOR THE AFOREMENTIONED CON-STRUCTION PbASE NUCLEAR GENERATING STATIONS. EXIDE SHOULD HAVE THIS ITEM AVAILABLE FOR RETRO-FIT wITHIN 60 DAYS.

THE NEED FOR SUCH ITEH wAS DETERMINED 10/10/78.

THIS N01IFICATION IS APPLICABLE TO THE FOLLOWING CLASS 1E DATTERY RACNS FUR THE SOUTHERN CALIF 0dNIA EDISON SAN ONUFRE NUCLEAR GENERA-TING STATIDNt UNIT d UNIT 3 26009, 26010, 20007, 2B006 3B009, 3B010, 39007, 30008 CONSUPERS POWER HIOLAND NUCLEAR GENERATING STATIONS 1 82 UNIT 1 UNIT 2 1001, 1002 2001, 2002 THIS POTENTI AL PROBLEM H AS uEEN RE ALIZED BY EXIDE kHO IS ACTING TO RECTIFY THE PRonLEM AT THIS TIME. THE PERSON TO Cot. TACT FOR ADDITION-AL INFGHMATION HELATIVE To THIS WIRE IS MR, C. K. MC MANUS AT EXIDE, AvAllA6LE AT T E L E P riuNE (215) 674-9500.

THIS NOTIFICATION IS oEING MADE IN ACCORDiNCE WITt, THE HEDUIREHENTS OF TITLE 10 0F THE CODE OF FEDERAL REGULATIONS, PART 21.

FOR EXIDE INDUSTRIAL BATTERY DIVISION Cri A 4LES K. MC MANUS f) g, /d-/