Special Rept Re Fire Barriers Breached for Longer than 7 Days.Caused by Ongoing App R Alternate Shutdown Work. Impairments Being Reported in One Rept Due to Large Vol of Work.Compensatory Measures Continue to Be Implemented
ML17347A461
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 05/06/1987
From: Woody C
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
L-87-197, NUDOCS 8705080263
Download: ML17347A461 (10)


Text

i REQULATORY I RMATIQN DISTRIBUTION SYS > (R IDB)

ACCESSION NBR: 8705080263 DOC. DATE: 87/05/06 NOTARIZED: NO DOCKET FACIL: 50-250 Turkey Point Plant> Unit 3> Florida Power and Light C 05000250 50-251 Turkeu Point Plant> Unit 4> Florida Power and Light C 05000251 AUTH. NAME AUTHOR AFFILIATION WOODY, C. O. Florida Power h Light Co.

REC IP. NAME, RECIPIENT AFFILIATION Document Control Branch (Document Control Desk)

SUBJECT:

Special rept re compensatorg measures continuing to be in place until safe shutdown mods complete. Breaches incur ed governed during mods governed by Tech Specs as app I i cab IP.

Caused bg on going App R alternate shutdown work.

DISTRIBUTION CODE: *COED DOPIER RECEIVED: LTR I ENCL J SIZE:

TITLE: OR/Licensing Submittal: Fire Protection NOTES:

RECIPIENT COPIES RECIPIENT COP IES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR El'<CL PD2-2 LA 1 0 PD2-2 PD 5 5 Mc DONALD, D INTERNAL: ARM/DAF/LFMB 1 0 NRR NERMEIL> J 1 0 NRR/DEBT/ADB 1 NR, PSB 1 1 OQC/HDB2 1 0 G 0}; } 1 EXTERNAL: LPDR 1 NRC PDR NBIC 1 1 TOTAL NUMBER OF CQP IES REQUIRED: LT I R 16 ENCL 12

f 4 hr<<,"

j h 4 Il >> I I d ~ I It I 4 "/(

6'14'

)f,t ),

C 4$ V 1 4 1'/, I/f I.thva) h p g h I r

"I

,vfjt/ ')Ch>>>> II'

~

)

I 4>>

=4

< 'I P' >>'

~, I/

)/ .

I ( Q) (>>J'" 44>>f I I

~n '. ,"jjhh, >>)C')<

)

~ lt W I 4

~

<jest'<<",

,1

P. O. I4000, JUNO BEACH, FL 33408 gal%

lb'LORIDA POWER & LIGHT COMPANY MAY 6 1987 L-87-I 97 U. S. Nuclear Regulatory Commission Attn: Document Control Desk Washington', D. C. 20555 Gentlemen:

Re: Turkey Point Units 3 and 4 Docket Nos. 50-2SO and SO-25 I Special Report - Breached Fire Barriers and Other Fire Protecton S stem Im airments In accordance with Technical Specification 6.9.3 the attached Special Report is provided for your information.

Should there be any questions on this information, please contact us.

Very truly yours, r

C. O. dy Group Vice President Nuclear Energy COW/SDF/gp Attachment cc: Dr. J. Nelson Grace, Regional Administrator, Region II, USNRC Senior Resident Inspector, USNRC, Turkey Point Plant 8705080263 870506 PDR 'ADQCK 05000250,

-8 '.

- -. PDR SDF I /004/I PEOPLE... SERVING PEOPLE

0 M

lh jl I

4

SPECIAL REPORT MAY 6, 1987 FIRE BARRIERS BREACHED FOR LONGER THAN SEVEN DAYS 6

OTHER FIRE PROTECTION SYSTEM IMPAIRMENTS REQUIRING NRC NOTIFICATION

~Pur ose:

Technical Specification (TS) 3.14.5.b requires the submission of a report to the NRC if a non-.functional fire barrier penetration is not returned to functional status within 7 days. TS 3.14 states that certain other conditions also require NRC notification. In accordance with the above requirements, this special report is being generated in order to notify the NRC. This report will be updated on a 30 day basis until the Appendix R associated work is complete.

Event:

The plant has been and is continuing to implement numerous modifications, mainly in accordance with Appendix R Alternate Shutdown requirements.

The schedular exemptions for the Safe Shutdown modifications, which outlined the alternative compensatory measures to be taken when a barrier is breached, expired on September 30, 1986, and on October 1, 1986. Upon the expiration of the exemptions, the compensatory measures as described in Attachment 1 of our letter L-85-386 (dated October 11, 1985), are continuing to be in place until the Safe Shutdown modifications are complete. Breaches incurred during Alternate Shutdown modifications are governed by the Technical Specifications or the exemptions, as applicable. Impairments are also incurred as part of plant maintenance and during the implementation of plant modifications.

Cause and Corrective Actions:

The ma)or cause of the impairments is the Appendix R Alternate Shutdown work which remains to be completed. Due to the large volume of work being performed, the plant is reporting the impairments in this one report, rather than on a case-by-case basis. The impairments reported this month are either open or closed at the present time, but were open in excess of the time period permitted without requiring NRC notification (see attached lists of impairments).

The plant continues to implement the compensatory measures as applicable.

ATTACHMENT FIRE PROTECTION SYSTEM IMPAIRMENTS CLOSED IN APRIL BUT WERE OPEN FOR LONGER THAN TECH SPEC LIMIT Breach or Impairment Open Closing Number Descri tion Date Date I076 Fire Doors 073-I 04/I5/87 04/25/87 87-OI7I Penetration Seals No. I 06F-E I 08 03/22/87 04/0 I /87 87-OI72 Penetration Seals No. I 06F-E I IO 03/22/87 04/0 I /87 87-OI73 Penetration Seals No. I 06F-E320 03/22/87 04/06/87 87-0I77 Penetration Seals No. I06F-E2 ls 03/24/87 O4/O6/S7 87-OI78 Penetration Seals No. I06F-E l92 03/22/87 04/0 I /87 87-OI79 Penetration Seals No. I 06F-E22 I 03/24/87 04/06/87 87-Olso Penetration Seals No. I 06F-E I 20 03/22/87 04/OI/87 87-OISI Penetration Seals No. I 06F-E I 25 03/22/87 04/OI/87 87-0182 Penetration Seals No. I06F-E223 03/22/87 04/06/87 87-OI83 Penetration Seals No. I 06F-E225 03/22/87 04/06/87 87-0I85 Penetration Seals No. I 06F-E072 03/22/87 04/06/87 87-OI86 Penetration Seals No. I 06F-E078 03/22/87 O4/O6/S7 87-0187 Penetration Seals No. I 06F-E I 32 03/22/87 04/06/87 87-Olss Penetration Seals No. I 06F-E204 03/22/87 04/I0/87 FIRE PROTECTION SYSTEM IMPAIRMENTS OPENED IN APRIL WHICH HAVE BEEN OPEN FOR LONGER THAN TECH SPEC LIMITS Breach or Impairment Open Number Descri tion Date I07I Fire Barrier Thermal Lagging 04/02/87 I072 Fire Door 058-3 O4/OS/S7 l075 Fire Door 46-2 04/20/87 5DF I /004/3

hf

' ~

The following barriers were breached prior to April, 1987, however they are being included in this report as they were not reported previously.

Imp/f Description Open Closed 87-0070 Fire barrier 070N-E034 1/19/87 1/29/87 87-0072 Fire barrier 0635-E008 1/16/87 2/19/87 87-0150 Fire barrier 0725-E009 3/10/87 3/28/87