Ro:On 830325,several Fire Barrier Penetrations at New Computer,Cable Spreading & Control Rooms Breached for Longer than Tech Spec Limit.Caused by Implementation of Approved Design Changes
ML17345B059
Person / Time
Site: Turkey Point  NextEra Energy icon.png
Issue date: 04/25/1983
From: Robert E. Uhrig
FLORIDA POWER & LIGHT CO.
To: Harold Denton
Office of Nuclear Reactor Regulation
References
L-83-256, NUDOCS 8304280081
Download: ML17345B059 (2)


Text

REGULATOR Nf.ORi4ATION DISTRIBUTION S M (RIDS)

ACCESSION NBR:8300280081 DOC DATE: 83/OQ/25 NOTARIZED: NO DOCKET ¹ FACIL:50-250 Turkey Point t'lant'nit

~

3i Florida Power and Light C 050 0 50-251 Turkey Point Planti Unit 4i Florida Power and Light C 0025 AUTH INANE AUTHOR AFF ILIATION UHRIGi R ~ E ~ F)or iaa Power 8 Light Co ~

RECIP ~ NAME RECIPIENT AFFILIATION DENTONIH ~ > ~ Office of Nuclear Reactor Regulationi Director

SUBJECT:

RO:on 830325rseveral fire barrier penetrations at new computericable spreading 8, control rooms breached for longer than Tech Spec limit.Caused by implementation of approved design changes.

DISTRIUUTION CODE A006S COPIES RECEIYED LTR ENCL SIZE ~ /

TITLE: OR Submittal: Fir e Protection NOTES:

RFCIPIENT COPIES RECIPIENT COPIES ID CODE/NAME LTTR ENCL ID CODE/NAME LTTR ENCL NRR ORB 1 BC 01 3 3 INTERNAL: ELD/HOSE 1 0 IE FILE 06 1 1 IE/WHITNEYi L 1 1 NRR FIORAYANT07 2 2 NRR ivAHBACH 1 0 D CEB 09 2 2 5 NRR/DL DIR 1 1 PQ 1 1 RGN2 1 1 EXTERNAL; ACRS ii 02 3 3 LPDR NSIC 03 05 1 1 1

NRC PDR 1 1 1 NTIS 1 1 TOTAL NUMbER OF COPIES REQUIRED; LTTR 21 ENCL 19

BOX l4000, JUNO BEACH, FL 3340S FLORIDA POWER 8c LIGHT COMPANY

"-5 /

April 25, 1983 L.-.83-256 Mr. Harold R. Denton, Director Office of Nuclear Reactor Regulation U. S. Nuclear Regulatory'ommission Washington, D. C. 20555

Dear Mr. Denton:

SPECIAL REPORT Turkey Point Units 3 4 0 Date of Occurrence - March 25, 1983 Technical Specification - 3.10.5.b FIRE BARRIER PENETRATIONS This special report is being submitted in accordance with Technical Specification 6.9.3 to provide 30 days notification on the subject occurrence.

Due to the implementation of approved design changes (PC/M 82-60 and 82-110), several fire barrier penetrations were breached for longer than seven (7) days. These penetrations are located at the new computer room, cable spreading room and control room.

Our ability to return the breached penetrations to functional status depends on the time frame required to complete the implementation of the design changes. The projected duration is three (3) months from the date of this report.

In compliance with Technical Specifications, an hourly fire watch has been established.

Very truly yours, Robert E. Uhrig Vice President Advanced Systems <k Technology REU/3A/m j/T3 cc: 3. P. O'Reilly, Region II Harold F. Reis, Esquire 830428008i 830425 PDR ADOCN 05000250 8 PDR PEOP'... SERVING PEOPLE