ML20133E036

From kanterella
Revision as of 13:31, 4 July 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Insp Repts 50-369/84-28 & 50-370/84-25 on 840924-28. Violations/Deviations Noted:Failure to Provide Fixed Suppression Sys in Accordance w/10CFR50,App R,Section III.G.3 for Rooms,Area & Zones Under Const
ML20133E036
Person / Time
Site: McGuire, Mcguire  Duke Energy icon.png
Issue date: 11/28/1984
From: Conlon T, Hunt M, Madden P, Miller W, Taylor P, Wiseman G
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20133D904 List:
References
50-369-84-28, 50-370-84-25, NUDOCS 8507220357
Download: ML20133E036 (33)


See also: IR 05000369/1984028

Text

_ _ _ _ _

s

UNITED STATES

p p MEuq*o NUCLEAR REGULATORY COMMISSION

y* *

, REGION 11

g j 101 MARIETTA STREET.N.W.

    • g ATLANTA. GEORGI A 30323

.

%...../

Report Nos.: 50-369/84-28 and 50-370/84-25

Licensee: Duke Power Company

422 South Church Street

Charlotte, NC 28242

Docket Nos.: 50-369 and 50-370 License Nos.: NPF-9 and NPF-I7

Facility Name: McGuire

t

Inspection Conducted: September 24 - 28, 1984

Inspectors:

M. D. unt

  1. gru >x-

I

L //- J!P' P/[

Date Signed

P. M. Madden V

/ N' 2$~*Y

Date Signed

W k fNaN $y p-20-a+

W. H. Miller Jr.

Q Date Signed

k & //~ at ? ~ N

!

-P.A.Taylorf Date Signed

Elenum A~ __ //~ A R ~ f f

l G. R. Wiseman Date Signed

Accompanying Personnel: T. E. Conlon, NRC Region II

A. R. Herdt, NRC, Region II

R. Anand, NRC/NRR - ASB

!

J. F. Stang, NRC/NRR - CHEB

J. Wilson, NRC/NRR - ASB

A. Coppola, Brookhaven National Laboratory

H. J. Thomas, Brookhaven National Laboratory

l

'

Apprqvedb /Pev v // ,2P- FY

T. E. Conlon, Section Chief Date Signed

Engineering Branch

Division of Reactor Safety

.-

,

) SUMMARY

!

l

Scope: This special, announced inspection entailed 350 (70 contractor and 280

NRC) inspector-hours on site in the areas of fire protection, standby shutdown

system (SSS) and related features required to meet 10 CFR 50 Appendix R,

Sections III.G, III.J III.L and III.O.

,

h $ h K7 8503J5

G 05000369

PDR

L_

s

4

2

Results: Of the area inspected, six apparent violations were

identified: inadequate or failure to provide fixed suppression system in

accordance with 10 CFR 50, Appendix R, Section III.G.3 for rooms, area, and zones

under consideration paragraph 5.a; failure to provide adequate br eaker/ fuse

protection for equipment required for hot standby paragraph 5.b; failure to

comply with the requirements of 10 CFR 50, Appendix R, Section III.J. -

paragraph 7.a.; failure to provide automatic fire detection for, and fire

barriers to separate, safety-related pumps paragraph 8.a; structural steel fire

barrier supports not provided with fire resistant rating equivalent to the fire

barrier paragraph 9.a; inadequate Appendix R,Section III.G, fire pr;tection

features and separation provided for redundant trains of normal shutdewn systems

and the standby shutdown system - paragraph 9.b. Two deviations were

found: failure to provide battery powered hand lanterns in the control room -

paragraph 7.a.; Failure to provide adequate radio communications between local

control stations and the standby shutdown facility paragraph 8.d.

J

l

l

l

,

.

/

_ _ _ _ _ . - _ _ _ _ _ _ . . _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ - - _ _ _ _ _ _ _ _ _ _ . - _ _ _ _ _ _ _ _ _ - _ . _ _ _ _ _ _ _ _ _ _ . . . _

- .

- - _- - - - - - - - .. - . _ - - -- . -

'

,

%

,

REPORT DETAILS

!

1. Licensee Employees Contacted

  • J. V. Almond, Safety Supervisor

'

  • T. A. Belk, Engineer Associate
  • H. D. Brandes, Design Engineer
  • J. M. Bugs, Design Engineer
  • K..S. Canady, Manager, Nuclear Engineering Service
  • R. Gill, Licensing Engineer
*A. D. Harrington, Training and Safety Coordinator
  • J. R. Hendricks, Principle Design Engineer

'

  • D. B. Hyde, Associate Engineer
  • J. A. Keane, Associate Engineer

, *D. P. Kimball, Associate Engineer.

1

'

  • T. A. Ledford, Superintendent, Design Engineering
  • T. V. Lyerly, IAE Staff Coordinator

! *W. N. Matthews, Design Engineer

.( *S. H. McInnis, Compliance

M. D. McIntosh, Station Manager

  • D. Mendezoff, Licensing Engineer

t

  • J. A. Oldham, Design Engineer

i *D. J. Rains, Superintendent of Mair.tenance

  • W. O. Reeside, Associate Engineer

i *R. W. Revels, Design Engineer

*N. Rutherford, Licensing Engineer
  • B. Travis, Operations Engineer
  • G. Vaughn, General Manager, Nuclear Stations

i *L. E. Weaker, Superintendent Station Services

j *C. H. Whitmore, Senior Designer

NRC Resident Inspectors

I *W. T. Orders

! *R. C. Pierson

i

  • Attended exit interview

1

2. Exit Interview

! The inspection scope and findings were summarized on September 28, 1984,

q with those persons indicated in paragraph 1 above. The following inspection

findings were identified to the licensee:

a. Violation Item '(369/84-28-01 and 370/84-25-01), Inadequate or Failure

! to Provide Fixed Suppression Systems in Accordance With 10 CFR 50,

1 Appendix R,Section III.G.3 for Rooms, Areas, or Zones Under

! Consideration paragraph 5.a.

.,

,

.

%

2

b. Unresolved Item (369/84-28-02 and 370/84-25-02), Inadequate Fixed Fire

Suppression System Provided for the Cable Spreading Room and Battery

Room paragraph 5.a.(2)(b).

c. Violation Item (369/84-28-03 and 370/84-25-03), Failure to Provide

Adequate Breaker / Fuse Protection for Equipment Required for Hot

Standby paragraph 5.b.(1).

d. Violation Item (369/84-28-04 and 370/84-25-04), Failure to Comply With

the Requirements of 10 CFR 50, Appendix R, Section III.J -

paragraph 7.a.

e. Deviation Item (369/84-28-05 and 370/84-25-05), Failure to Provide

Battery Powered Hand Lanterns in the Control Room paragraph 7.a.

f. Inspector Followup Item (369/84-28-06 and 370/84-25-06), Inadequate

Surveillance Testing Procedures for Emergency Lighting paragraph 7.b.

g. Violation Item (369/84-28-07 and 370/84-25-07), Failure to Provide

Automatic Fire Detection for, and Fire Barriers to Separate

Safety-Related Pumps paragraph 8.a.

h. Unresolved Item (369/84-28-08 and 370/84-25-08), Adequacy of Power

Supplies for Fire Pumps A, B, and C paragraph 8.c.

1. Deviation Item (369/84-28-09 and 370/84-25-09), Failure to Provide

Adequate Radio Communications Between Local Control Stations and

Standby Shutdown Facility paragraph 8.d.

J. Violation Item (369/84-28-10 and 370/84-25-10), Structural Steel Fire

Barrier Supports Not Provided With Fire Resistant Rating Equivalent to

the Fire Barrier paragraph 9.a.

k. Violation Item (369/84-28-11), Inadequate Appendix R,Section III.G,

Fire Protection Features and Separation Provided for Redundant Trains

of Normal Shutdown Systems and the Standby Shutdown System -

paragraph 9.b.

'

1. Unresolved Item (369/84-28-12 and 370/84-25-12), NRR Evaluation of

Appendix R, Deviation Request paragraph 9.c.

m. Inspector Followup Item (369/84-28-13 and 370/84-25-13), Amplify and

Clarify Certain Steps of OP/0/A/6100/17 - paragraph 5.q.(2)(a),

n. Unresolved Item (369/84-28-14 and 370/84-25-14) Analysis Effects on

SSF/SSS Operation, Potential Excessive Feedwater to Steam Generators -

paragraph 5.c.(2)(a)(7),

o. Unresolved Item (369/84-28-15 and 370/84-25-15), Correct Procedure l

Deficiencies used to Accomplish 10 CFR 50, Appendix R, Section III.L -

paragraph 5.c.(2)(b).

!

, l

_- _ _ _ _ _ _ _ - _ _ _ - _ _ _ _ -

.

e

3

3. Licensee Action on Previous Enforcement Matters

This subject was not addressed in the inspection.

4. Unresolved Items

Unresolved ' items are matters about which more information is required to

determine whether they are acceptable or may involve violations or devia-

tions. New unresolved items identified during this inspection are discussed

-in paragraphs 5.a(2)(b), 5.c.(2)(a)(7), 5.c.(2)(b), 8.c. and 9.c.

5. Compliance With 10 CFR 50, Appendix R Sections III.G. and III.L

- An inspection' was conducted to determine if the fire protection features

provided for structures, systems, and components important to safe shutdown

at McGuire were in compliance with 10 CFR 50, Appendix R, Sections III.G.

and III.L. .Since the McGuire Nuclear Station utilizes the dedicated

shutdown system approach, the scope of this inspection determined if the

fire protection features provided were capable of maintaining either the

safe shutdown system or one train of normal plant hot standby systems free

from fire damage, and were capable of limiting potential fire damage to both

trains of redundant normal plant safe shutdown systems in those plant areas

where alternate or dedicated shutdown capabilities are provided.

a. Safe Shutdown Capabilities

In - order to ensure safe shutdown capabilities, where cables or

equipment of redundant trains of systems necessary to achieve and

maintain hot stand-by conditions are located within the same fire area

outside the primary containment,10 CFR 50, Appendix R, Section III.G.2

requires that one train of hot standby systems be maintained free of

fire damage by one of the following means:

Separation of cables and equipment and associated non-safety

circuits of redundant trains by a fire barrier having a 3-hour

rating;

Separation of cables and equipment and - associated non-safety

circuits of redundant trains by a horizontal distance of more than

20 feet with no . intervening combustibles or fire hazards. In

addition, fire det.ectors and an automatic fire suppression system

-shall be installed in the fire area; or,

Enclosure of cable and. equipment and ' associated non-safety

circuits of one redundant' train in a fire barrier.having a.1-hour

rating. In addition, fire detectors 'and 'an automatic fire ,

suppression 1 system shall be installed in the fire area.

.

i

'

, . , , , - - - - ,- ,,-r,---,i.-, .. , , , , . , , ,,--,nu,e-, , , , , - , , - . , , . ~ - , ,~- ..r.m- ,---w+.

- , , - . . . . . . ._, . = .-.

! -

I O

4

i

Where the protection of systems whose function is required for hot

! standby _ does not satisfy the above requirements or Section III.G.2,

! alternative or dedicated shutdown capabilities independent of cables,

systems or components in the area, room or zone under consideration

shall be provided in accordance with 10 CFR 50, Appendix R,

Section III.G.3 and III.L. In addition,Section III.G.3 requires that

fire detection and fixed suppression be installed in the area, room or

zone under consideration.

On -the basis of .the above Appendix R criteria, the inspectors made an

audit of cabling and components associated with the dedicated standby

shutdown system (SSS) to determine the adequacy of the separation

afforded to the SSS with respect to plant areas containing both

redundant trains of normal essential hot standby systems (i.e,

auxiliary feedwater system, component cooling water system, nuclear

service water system, chemical volume control system and reactor

coolant system). In addition, the inspectors made an audit of the .

standby shutdown system's ability to achieve and maintain hot standby

l and determined the adequacy of the fire protection features afforded

i for those plant areas which contain both redundant trains or normal

! essential; plant systems required to achieve and maintain safe shutdown

l conditions.

l

( (1) Separation of Standby Shutdown System (SSS) from Normal Plant

Shutdown Systems.

A walk down' inspection was.made of the following SSS-cables routes

within the Unit 1 auxiliary building to verify that the SSS cables

were separated from the redundant or compliment device of the

normal essential plant shutdown system in _accordance with the

_

requirements of 10 CFR 50, Appendix R, Section III.G.2.

SSS SSS Compliment Compliment

Function Device Cable (s) Device Cable (S)

Pressurizer INCP5151 1CF726 INCLT5170 INC665

Level Inst. INC992

l 1NC990

i

Steam Generator 1CFP6090 ICF726 1CFP5530 1CF588

B Level Inst. 1CF773

1CF771

Reactor Coolant INCP5121 1CF726 INCPT5170 INC713

Pressure ~ Inst. INC995

l 1N6993

Changing F1ow 1NVP6420- ICF726 Control- INV657

,

Inst.- INV826 -Gauge

INV827

I

.

P , , -

- . , . . . - . . - . . _ - ,.._,, , . - . - ,

. - _ - . . _ _

Q-

5

4 .

Reactor Coolant INC1, Valve INC984 Control Room INC971

System Vent NC272AC Controls (Note *)

'

'

1NC2, Valve Valves NC272AC

NC273AC & NC273AC

Reactor Coolant INC3, Valve INC977 Control Room INC707

System Isolation NC27 Controls (Note *)

Valve NC27

1NC4, Valve INC977 Valve NC29 INC706

NC29

'

1N04, Valve IWZ540 Valve ND2AC 1EPE590

,

ND2AC

NV Valve IWZ540 a ve 1EPE590

NOTE
* Normal shutdown and SSS cables terminate in cabinet SSSFARC.

-

Normal shutdown cables extend from this cabinet to normal

system isolation valves. Cables are routed by separate routes

to assure that the cables will not ground or fault in such a

manner to cause spurious valve operations.

l'

In general, the SSS cables are. routed with Train A cables and are

separated from Train B cables by three hour fire rated barriers.

'

A review was conducted of drawing Nos. MC-1919-01.01, MC1920-

01.01, and MC1921-02.01 and " computer. cable routing program data

sheets" to determine the above cable routes within the auxiliary

and reactor buildings. Portions of the SSS cabling and the normal

shutdown cabling within the annulus of the reactor building are in

close proximity to each other. This situation is not in violation

to Appendix R,Section III.G.2,. since the annulus is considered

'

part of the containment and is provided with fire detection and

automatic sprinkler protection.

For:a fire within the remainder of the containment, the SSS is-not

required to bring the plant to hot standby condition. 'The n_ormal

shutdown systems would be used and these systems have been

L

evaluated by the licensee and NRR and found to be adequate to

bring the plant to 'a . safe shutdown condition following a

'

containment fire.

A review of. components and cable route drawing for the SSS within

,

Unit 2 indicated that the installation 'within Unit 2 was similar

,

to Unit 1 and appears to be provided with sufficient separation

'

from the normal shutdown" components' to meet the requirements of

10 CFR 50 Appendix R, Section III.G.

,

i

, m - , , ~ ,-y ....>.--w s 4 v a n ,x ,-- ,w,pwy

,

c

6

(2) Fire Protection of Safe Shutdown Capabilities

(a) An inspection was made to determine if the fire protection

features provided for various auxiliary building areas meet

the fire protection requirements of 10 CFR 50 Appendix R,

Section III.G.3.

1) Fire Area 4 - Auxiliary Building Common Area 649

On elevation 716'-0" of the Auxiliary Building a partial

fixed automatic sprinkler system is provided to Common

Area 649 to protect the Nuclear Service Water (RN)

pumps. The area of sprinkler application in Common

Area 649 is provided between column line EE-GG-54 and

column line EE-GG 58. Power cables 1*RN571 and 2*RN559

for RN pumps 1A and 2A are partially routed outside the

area protected by sprinklers in Common Area 649 from

column line GG 56 to HH 54, where they enter the

unprotected electrical duct shaft adjacent to Charging

Pump Room 627 and are routed up through elevation

733'-0" to elevation 750'-0." Power cables 1*RN572 and

2*RN560 for RN pumps 18 and 2B are routed in Common

Area 649 from the pumps to the unprotected electrical

duct shaft near column FF57 within the sprinklered area,

where they enter the shaft and are routed up to

elevation 733'-0."

Even though train "B" RN pump power cables are located

within the sprinklered area and the train "A" RN pump

power cables are partially routed through this area, the

water discharge pattern for the sprinkler heads

installed near the ceiling level over both redundant

trains of RN pumps and their associated cabling appears

to be obstructed by cable trays and piping. In

addition, the sprinkler protection does not fully

protect the train "A" RN pump cabling in Common Area

649. Therefore, based on the sprinkler obstructions and

the lack of adequate fixed suppression coverage for both

redundant trains of normal shutdown systems located in

Auxiliary Building Common Area 649, it cannot be assured

that fire damage to both trains of the nuclear service

water system can be minimized if an exposure fire were

to occur within this plant area.

2) Fire Area 14 - Auxiliary Building Common Area 723

Component Cooling Water (KC) pump suction isolation

valves 1*KC-1A, 1*KC-2B, 1*KC-3A and 1*KC-18B are

located in Common Area 723 on Auxiliary Building

elevation 733'-0". Common Area 723 is partially

,

%

7

protected by an automatic sprinkler system. The area of

sprinkler application in Common Area 723 is provided

between column line GG-JJ 55 and column line GG-JJ 57.

Valves v*KC-1A,1*KC-2B and 1*KC-188 are located within

the Compohent Cooling Water (KC) pump area which is

protected by the actomatic sprinkler system. The

sprinkler water discharge patterns for those sprinkler

heads which provide partial protection for valves

1*KC-1A,1*KC-2B and 1*KC-188 and their control cables

1*KC501, 1*KC527, 1*KC515, 1*KC541, and 1*KC516 appear

to be obstructed by cable trays and piping. Component

Cooling Water (KC) suction valve 1*KC-3A and its control

cabling 1*KC502 and 1*KC527 and control cables 1*KC501

are located outside the sprinklered area near column

line HH54 and JJ54. Therefore, based on the sprinkler

obstructions and the lack of adequate fixed suppression

coverage for both redundant trains of normal shutdown

systems located in Common Area 723, it cannot be assured

that fire damage to both trains of the Component Cooling

Water System can be minimized if an exposure fire were

to occur within this plant area.

Unit 1 Centrifugal Charging (NV) pump 1A and 1B power

cables 1*NV501 and 1*NV502 are located in Common Area

723 on auxiliary building elevation 733'-0". Common

Area 723 is partially protected by an automatic

sprinkler system. The area of sprinkler application in

Common Area 723 is provided between column line GG-JJ55

and column line GG-JJ57. Cable 1*NV502 is routed up to

elevation 733'-0" from elevation 716'-0" through the

unprotected cable shaft located outside the sprinklered

area near column line HH-54. Once on elevation 733'-0",

cable 1*NV502 stays in the cable shaft and is routed up

to auxiliary building elevation 750'-0" where it

terminates. Cable 1*NV501 is routed up to elevation

733'-0" from elevation 716'-0" through an electrical

floor penetration near column line JJ-55. Cable

1*NV501, once on elevation 733'-0", is routed across

Common Area 723 outside the sprinklered area to column

line JJ-56. Once cable 1*NV501 has reache'd this plant

location, it makes a 90* turn south and is routed

through the sprinklered area. The water discharge

pattern for . the sprinklers installed near the ceiling

level over both redundant trains of Component Cooling

Water pumps and cable 1*NV501 appears to be obstructed

by piping and cable trays.

Therefore, based on the sprinkler obstructions and the

lack 'of adequate fixed suppression coverage for bo.th

redundant trains of normal shutdown systems located in

Common Area 723, it cannot be assured that fire damage

_----___

-

s

,

8

to both trains of the Unit 1 Chemical Volume Control

System can be minimized if an exposure fire were to

occur within this plant area.

Unit 2 Centrifugal Charging (NV) pump 2A and 2B power

cables 2*NV538 and 2*NV537 are located in auxiliary

building Common Area 723 on elevation 733'-0". Common

Area 723 is partially protected by an automatic

sprinkler system. The area of sprinkler application in

Common Area 723 is provided between column line GG-JJ55

and column line GG-JJ57. Cable 2*NV537 is routed up to

elevation 733'-0" from elevation 716'0" through the

l unprotected cable shaft located outside the sprinklered

'

'

area near column line JJ-58. Once on elevation 733'-0",

cable 2*NV537 stays in the cable shaft and is routed up

l

'

to auxiliary building elevation 750'-0" where it

terminates. Cable 2*NV538 is routed up to elevation

733'-0", from elevation 716'-0" through an electrical

floor penetration near column line HH57. Cable 2*NV538

once on elevation 733'-0", is routed through the

sprinklered portion of common area 723. However, the

water discharge pattern for the sprinkler heads

installed near the ceiling level over cable 2*NV538

appears to be obstructed by piping and cable trays.

Therefore, based on the sprinkler obstructions and the

l lack of adequate fixed suppression coverage for both

t redundant trains of normal shutdown systems located in

Common Area 723, it cannot be assured that fire damage

to both redund nt trains of the Unit 2 Chemical Volume

Control System can be minimized if an exposure fire were

i

to occur within this plant area.

Cabling for both trains of redundant Charging Flow

Isolation Valves is located in Auxiliary Building Common

Area 723 on elevation 733'-0". Common Area 723 is

partially protected by an automatic sprinkler system.

The area of sprinkler application within this area is

~i

provided between column line GG-JJ57 and GG-JJ55. Cable

1*NV555, which is associated with Charging Flow

Isolation Valve 1*NV244A, is routed up to elevation

733'-0" from elevation 716'-0' through the unprotected

cable shaft located outside the sprinklered area near

i

column line HH56. Cables 1*NV575 and 1*NV576 are routed

through the portion of Common Area 723 which is

protected by sprinklers. However, the water discharge

pattern of the sprinkler heads installed near the

ceiling over cables 1*NV575 and 1*NV576 appears to be

obstructed by cable trays and piping. Therefore, based

on the sprinkler obstructions and the lack of fixed

suppression coverage for both redundant trains of normal

shutdown systems located in Common Area 723, it cannot

a

V

.

4

9

! be assured that fire damage to both redundant trains of

!

Unit 1 Chemical Volume Control System can be minimized

if an exposure fire were to occur within this plant

area.

3) Fire Area 4 - Mechanical Penetration Room 603

Normal Charging Flow Isolation Valves 1*NV244A and

1*NV245B to the Reactor Coolant System are located in

Mechanical Penetration Room 603 on elevation 716'-0" of

the auxiliary building. This room is not provided with

a fixed suppression system. The cabling associated with

these valves is also located within this room. Cables

1*NV55B and 1*NV579 are routed out of Mechanical

! Penetration Room 603 in two separate directions. These

cables and cable 1*NV576 associated with valve 1*NV245B

and cable 1*NV555 associated with valve 1*NV244A

reconverge in auxiliary building Common Area 649.

Common Area 649 is partially protected by an automatic

sprinkler system. The area of sprinkler application

within this area is provided between column lines

EE-GG 54 and EE-GG58. Cable 1*NV579 and 1*NV576 for

l

Charging Flow Isolation Valve 1*NV245B terminate within

cabinet 1ATC3. Termination cabinet 1ATC3 and cable

1*NV576 are located within the sprinklered area.

l

'

However, cable 1*NV579 is only partially located in the

sprinklered area. Cables 1*NV558 and 1*NV555 for

Charging Flow Isolation Valve 1*NV244A terminate within

cabinet 1ATC6. Termination cabinet 1ATC6 and cables

1*NV558 and 1*NV555 are located outside the sprinklered

area. The water discharge pattern for the sprinkler

heads installed near the ceiling over termination

cabinet 1ATC3 and in the area of the cable routes for

cables 1*NV579 and 1*NV576 appears to be obstructed by

,

cable trays and piping. Therefore, based on the

sprinkler obstructions and the lack of fixed suppression

'

coverage for both redundant trains of normal shutdown

systems located in Common Area 649 and mechanical

penetration room 603, it cannot assured that fire damage

to both redundant trains of the Unit 1 Chemical Volume

Control System can be minimized if an exposure fire were

to occur within either of these plant areas.

'

4) Fire Area 14 - Corridor 731

Volume Control Tank Isolation Valves 1*NV141A and

1*NV142B are located in corridor 731 on auxiliary

building elevation 733'-0". Cable 1*NV560 associated

with valve 1*NV141A and cable 1*NV582 associated with

valve 1*NV1428 are routed from the valves down to the

end of Corridor 731, then they take a 90* turn and run

- -

,

'

e .

. 10

down the corridor adjacent to the Boric Acid Tank Rooms

and into Common Area 753 where they separate. If an

exposure fire were to affect these valves or their

associated cables, causing these valves to spuriously

operate and go closed, the normal suction flow path to

the charging pumps could be precluded. There are no

fixed suppression capabilities provided in either

Corridor 731 or the corridor adjacent to the Boric Acid

Addition Tank Rooms to protect the Volume Control Tank

Isolation Valves and their associated cabling.

Therefore, based on the lack of fixed suppression in

these plant areas, it cannot be assured that fire damage

to both redundant trains of Unit 1 Chemical Volume

Control System can be minimized.

5) Fire Area 21 - Auxiliary Building Common Area 806

Nuclear _ Service Water Supply Isolation Valve 1*RN86A to

Component Cooling Water Heat Exchanger 1A and Nuclear

Service Water Supply Isolation Valve 1*RN1878 to l

Component Cooling Water Heat Exchanger 18 and their

associated cabling are located in Common Area 806 (fire

area 21) on auxiliary building elevation 750'-0." If an

exposure fire . were to affect these valves or their

associated cables, causing these valves to spuriously

operate and go closed, the normal nuclear service water

supply to the component cooling water heat exchangers

could be precluded. There are no fixed suppression

capabilities provided in Common Area 806 near the area

the' heat exchangers to protect the nuclear service water

supply isolation valves and associated cabling.

Therefore, based on the lack of fixed suppression in the

area of the nuclear service water supply isolation

valves to the component cooling water heat exchangers

and their associated cabling, it cannot be assured that

fire damage to both redundant trains of Unit 1 Component

Cooling Water System can be minimized.

The plant areas identified in items 5.a. 2 a 1)

,. through 5.a.(2)(a)(5), are areas, rooms, or z(on)e(s)u(nder

-

l

' consideration and.if affected by a fire condition would

require the utilization of the dedicated standby

shutdown system to achieve and maintain hot standby

conditions. 10 CFR 50, Appendix R, Section III.G.3,

requires a -fixed suppression to be installed in the

'

room, zone or area under consideration. The plant

-areas, zones, or rooms previously identified, are either

.

not provided with fixed suppressinn capabilities or the

l fixed suppression system provided does not provide

adequate coverage to protect both redundant trains of

I

'

a .

_ . _ _ _ _ _ _ _ _ -

,

.. . .

.

.

~

1

11

normal safe shutdown systems. Therefore, if an exposure

fire were to occur within any of these identified areas,

it could not be assured that the fire damage sustained

by both redundant trains of normal shutdown systems

would be -minimal. The failure to meet the fire

protection requirements of 10 CFR 50 Appendix R,

Section III.G.3, as required by the operating license,

is identified as Violation Item (369/84-28-01 and

370/84-25-01) Inadequate or the Failure to Provide Fixed

Suppression Systems in Accordance with 10 CFR 50

Appendix R,Section III.G.3, for Rooms, Areas or Zones

Under Consideration.

(b) An inspection was made to determine if the fixed manual water

. spray systems in the cable spreading rooms and the automatic

sprinkler system provided to protect the cable tray stacks at <

the east and west ends of the battery room were designed and

installed in accordance with Unit I license Condition 2.C.(4)

and Unit 2 License Condition 2.C.(7). These license

conditions require the licensee to maintain in effect and I

fully implement all the provisions of the approved fire

protection plan and the NRC staff's Safety Evaluation Report,

Supplement No. 2.

Safety Evaluation Report, Supplement No. 2, indicates that

the water suppression systems are designed in accordance with

NFPA 13 and 15. In addition, this safety evaluation report

required the cable spreading rooms to be protected by a

manual fixed water spray system with a level of open spray

heads at the ceiling and an additional level of heads below

the lowest cable. trays throughout the- room. However, the

present systems do not appear to be designed in accordance

with NFPA 13 and 15 as the spray nozzles are not distributed

uniformly throughout the cable spreading rooms at the ceiling

level and at the level below the lowest cable trays.

Therefore, it cannot be assured, that if an exposure fire

were to occur in the cable spreading room, that the present

manual fixed water spray system would assist in controlling a

potential exposure fire and minimize fire damage to redundant

trains of cabling.

The Safety Evaluation Report also indicated that the

sprinklers installed in the b;tttery room provide protection

for the cable tray stacks at the east and west ends of the

room from an' exposure fire. The present battery room

sprinkler system design does not comply with the guidance

provided by NFPA-13. The present placement of the ~ sprinkler

-

heads under the cable trays is approximately 5 ft. above the.

' floor. Without sprinklers placed at or near the ceiling, it

-

_ _ __ _ _ _ _ _ . _ _ ._ . _ _ . . _ _ _. -. .-

.

%

r

12

r

,

cannot be assured that the present sprinkler design would

react in a timely manner to protect the cable tray stacks

against the potential effects of an exposure fire.

These fixed suppression systems inadequacies have been

identified as Unresolved Item (369/84-28-02 and 370/84-

75-02), Inadequate Fixed Fire Suppression System Provided for

the Cable Spreading Room and Battery Room, pending

disposition by NRR. ,

b. Protection of Associated Circuits

The inspection was conducted to verify compliance with the associated

circuit provisions of 10 CFR 50 Appendix R, Sections III.G and III.L.

The emphasis was on the following areas of concern:

Common Bus Concern

Spurious Signal Concern

Common Enclosure Concern

(1) Common Bus Concern

The common bus concern is found in circuits, either non-safety or

safety related, where there is a common power source with shutdown

equipment and the power source is not electrically protected from

the circuit of concern.

,

A number of circuits were identified which did not have adequate

circuit breaker or fuse coordination. The licensee indicated that

an ongoing breaker coordination program is in effect. The

inspectors identified the following circuits which did not meet ,

the requirements of Appendix R,Section III.G.2:

1251/. D.C. control power for charging pumps CCPA

or CCPB from panels EVDA or EVDD respectively.

600 VAC power supply for auxiliary feedwater supply

MOVs CA468, CA508, CA54AC and CA58A.

600 VAC Power supply for PORV block valves MOVINC318

and MOVINC358 -

l

600 VAC nower supply for RHR isolation valve MOVIN01B I

600 VAC power supply for turbine driven auxiliary

feedwater pump suction valve CA7A

600 VAC power for nuclear service valve RN16B

600 VAC-power for VCT outlet valves NV141A and NV1428

, .- - , ., . - - .

._ -. . _ - - - - _ -- . - _ _ _ _ _ ____.- __

.

'

,

13

600.VAC power for component cooling pump suction

valves form RWST NV221A and NV222B

The licensee should perform an analysis to ensure that power to

hot standby equipment is protected from faults in commonly powered

equipment. Presently, these conditions do net meet the require-

ments of Appendix R,Section III.G.2 and are identified as

Violation Item (369/84-28-03 370/84-25-03), Failure to Provide

Adequate Breaker / Fuse Protection for Equipment Required for Hot

Standby.

(2) Spurious Signal Concern

A review of the licensee's spurious signal analysis was conducted

to determine if the following conditions had been considered:

.

The false motor, control and instrument readings

such as what occurred at the 1975 Browns Ferry

Fire. These could be caused by fire initiated

,

grounds, shorts or open circuits.

Spurious operation of safety-related or non-safetyrelated

components that would adversely affect shutdown capability

(e.g., RHR/RCS Isolation Valves).

The licensee intends to remove power and control voltages from

valves that could affect safe shutdown of the unit should they

operate due to a fire induced spurious signal. These are:

Pressurizer Power Op'erated Relief Valves

J

Power will be removed from the pressurizer pswer

operated relief valves by removable disconnect

cables in the 125 VDC control circuit for valves

INC32B and INC368 and by an interlock relay for

INC36A when the shutdown facility is to be

activated.

Reactor Head Vent Valves

^

The head vent valves NC2'478 and NC275B will be

inhibited from operation by the removal of cable

disconnects in the 125 VDC control circuitry.

The head vent valves NC272,C and NC273A,C will have

control capability trarsferred to the standby shut-

down facility which is electrically isolated from

the control room.

The RCS/RHR boundary valves were the only high I'ow pressure

interface which were identified and analyzed for spurious opera- '

tion. There are , installed, a number of interlocks in series in

the control circuit for the RHR suction valve and none of them are-

_. , - - - .

. . . -. - .. -.

.

%

14

l- located in the same fire area. The valve opening circuit contains

in series a control switch contact, a pressure interlock and valve

limit switch interlock contacts. The limit switch ISW27 is locked

opened and consequently inhibits the ability to apply control

power to the control circuits for the INDIE and 1ND2A RCS isola-

tion valvec.

~

l

These additional circuit analyses were reviewed by the inspectors:

l RCS Boundary Valves and Centrifugal Pump Charging

The licensee conducted an analysis to determine the

availability of a charging path to maintain reactor

-

inventory. It was determined, at the time of the inspection,

,

that the necessary modifications, such as one-hour fire

'

retardant blanket wraps on circuits for the RHR/RCS valves

ND2AC, were installed in the turbine driven auxiliary feed-

water pump room.

i

Main Steam Isolation Valves (MSIV) and the Main Steam Power

Operated Relief Valve (PORV)

I

The control circuits for main steam isolation valves ISM 1AB

I

ISM 3AB, ISM 3AB, ISM 7AE were analysed. Two solenoid valves

i

are installed in series in the pneumatic control line, the

closure of any one will cause the MSIV to close. The control

i

ircuits for main steam power operated relief valves 15VIAB,

i 1SV7ABC, ISV13AB, ISV19AB were analyzed. Three solenoid

valves are connected-in series in the pneumatic control lines

for the main steam power operated relief valves, the closure

of any one will cause the respective main steam PORV to

close. The McGuire Nuclear Station does not depend on the

main steam PORVs for safe shutdown.

Dedicated instrumentation, electrically independent of control

room, has been provided at the standby shutdown panel to monitor

the following parameters:

Pressurizer Pressure

Pressurizer Level

Standby Makeup Pump Discharge Pressure

. Steam Generator Level

Incore Temperature (T Hot)

The licensee has committed to install RTDs to monitor T Cold i

during the next refueling.

Source range instrumentation was not installed and an exemption

request had been granted.

.

. - . - ._

.

t

15

The spurious signal concern was not satisfactorily addressed since

some buses feeding safe shutdown equipment did not have adequate -

coordination of circuit breakers and fuses. Some of the safe

shutdown components which were affected by the lack of

coordination were as follows:

i

Centrifugal Charging Pump CCPA

Centrifugal Charging Pump CCPB

Turbine Driven Auxiliary Feedwater Pump Suction Valve CA7A

PORV Block Valves - MOV INC318 and MOVING 358

RHR Isolation Valve MOV INDIE

'

This is another example of Violation Item (369/84-28-03 and

370/84-25-03), Failure to Provide Adequate Breaker / Fuse Protection

for Equipment Required for Hot Shutdown.

'

(3) The Common Enclosure Concern

The common enclosure concern is found when redundant trains are

routed together with a non-safety circuit which crosses from one 1

'

!

raceway or enclosure to another, and the non-safety circuit is not

electrically protected or fire can destroy both redundant trains

due to inadequate fire protection means.

!

The common enclosure concern at McGuire was not a concern since

the standby shutdown system cables were not run in the same trays

with either the redundant trains or their associated non-safety-

related cables.

i

For fires where redundant Trains A and B are to be used instead of

the standby shutdown system, the licensee wrapped one redundant

train. This was done in the Unit 1 Train B switchgear room where

some Train A cabling was wrapped with 3-hour rated fire retardant

blanket.

c. Dedicated Shutdown and Fire Damage Control Capabilities

(1) System Description and Operation

SSER No. 6, dated January 25, 1983, documents NRR review of the

, licensee dedicated shutdown system and its conformance to

10 CFR 50, Appendix P. ,Section III.L. The McGuire dedicated

shutdown system is identified as the Standby Shutdown System ,

L(SSS). This system provides an alternate and independent means to l

achieve and maintain the reactor coolant system in hot standby

condition for one or both units. The (SSS) is placed into

operation only 'if a' postulated fire results in the installed

normal and emergency plant systems becoming inoperable. A masonry

structure located adjacent to and outside the plant, houses the

- - _ _ _ _ _ _ _ - _ _ _ _ - _ _ _ _ - _ _ _ _

1

o

.

16

major equipment and controls for the (SSS). This facility is

designated the Standby Shutdown Facility (SSF) and consist of a

diesel generator, starting batteries and supporting auxiliary

systems. Normal electrical power is supplied via 6.9 kv site

transformer, dedicated emergency power via the diesel generator,

battery bank for 125 VDC, 600 VAC and 125 VAC power distribution

systems, and a control panel for monitoring and controlling

primary and secondary volumes. Reactor coolant system pressure

control is provided by manual control of a bank of pressurizer

heaters and pressurizer level via manual operation of reactor

vessel head vent valves. Makeup water to the reactor coolant

system and sealing water to the reactor coolant pumps (RCP) are

provided by a 26 gpm makeup pump connected to the RCP sealwater

injection line. Each standby makeup pump is located in the unit's

containment building annulus and takes suction from the spent fuel

pool transfer area. Steam generator volume control and decay heat

removal are accomplished by utilizing the normal auxiliary

feedwater system to maintain steam generator water level

requirements. The main steam safety valves are used to control

secondary side pressure and to dump steam to provide decay heat

removal from the reactor coolant system.

The licensee gave a presentation on the general operator actions

and the procedures to be used when the SSF/SSS is placed into

operation for those' cases where the fire renders the control room

and the auxiliary . shutdown panels inoperable. The procedures and

sequence were described as follows:

- AP 1/A/5500/01, Reactor Trip

This procedure provides the instructions to stabilize and

control the plant following the trip of the reactor which

would take place upon detection of a disabling fire.

- OP/0/A/6100/17, Operation of the Standby Shutdown Facility

This procedure describes the use of the SSF/SSS systems,

operational controls, and stations to be manned in order to

maintain the unit or units in a hot standby mode.

- OP/0/A/6100/20, Operational Guidelines Following Fire in

Auxiliary Building er Vital Area

This procedure describes the steps to be taken and plant

systems required to bring the plant to hot shutdown followed

by cold shutdown within 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br />. It is intended by the

licensee to use normal operating and plant shutdown

procedures to accomplish these evolutions.

.

I

I

  • ,  !

,-

e

17

l

- IP/0/A/3090/23, Fire Damage Control Procedure

This procedure establishes methods for the restoration of '

instrumentation, electric motors, system valves, electric

breakers, etc., following a fire so that plant equipment and i

. systems necessary to bring the plant to cold shutdown

conditions are made operable. This procedure is performed in

conjunction with the aforementioned procedures in order to <

expedite efforts to take the plant to cold shutdown.

(2) Review of Operating and Surveillance Procedure

The inspectors reviewed the completed data in PT/A/4209/01C,

Standby Makeup Pump Flow Periodic Test for Units 1 and 2 to verify

that the output capacity for each pump met the 26 gpm minimum

specified in the SSER No. 6. The test results for Unit 1

(completed 9/5/84), indicated a flowrate of 29.0 gpm and for

Unit 2 (completed 8/31/84) a flowrate of 30 gpm which satisfies

those values specified in SSER No. 6.

The inspectors reviewed those plant procedures identified for use

in the case where a fire causes the control room to be abandoned

and the auxiliary shutdown panels are also rendered inoperable.

This review was conducted to verify that information in design and

engineering documents and the information provided in SSER No. 6

have been factored i.nto the appropriate plant operating procedures

for . the SSF/SSS systems and procedure for subsequent cold

shutdown.

In addition to the procedure reviews, walkdown of selected

procedures were conducted to ensure that the instruction provided

-

was complete and usable; that steps identified components _and

equipment correctly and equipment is accessible to plant operators

for operation.

The following plant procedures were reviewed:

-

AP/1/A/5500/01 (Change 1), Reactor Trip

-

~0P/1/A/6100/07 (Change 8),. Operation of the Standby Shutdown

Facility

-

OP/0/A/6100/20 (Change 0), Operational Guidelines Following

Fire in Auxiliary Building or Vital Area-

- '

OP/0/A/6100/13 (Change 0), Operational -Guidelines Following

Fire in Containment or Doghouse

.AP/1/A/5500/17 (Change 0), Loss of Control Room

~

I

L-

t

. _ _ _ _ _ _ __

i

4

18

The review and walkdown of the procedures resulted in the

following findings and concerns, which apply equally to both

units:

(a) OP/0/A/6100/17, Operation of the Standby Shutdown Facility

1) Provide appropriate steps in the procedure to ensure

that pressurizer spray isolation valves are shut and the

reactor coolant pumps are shutdown. SSER No. 6,

Section C.3.5, describes these components as the means

of terminating pressure decreases in the event, the

spray valves become open due to electrical shorts caused

by a fire.

2) Enclosure 4.1, Section 1,' Step 2.2, requires the normal

power source for SSS system equipment to be switched to

its alternate power source, MCC-SMXG. Appropriate steps

need to be added to the procedure that ensure that

either the diesel generator is supplying power to the

alternate bus or the offsite power supply is available.

3) Enclosure 4.1, Section 1, Step 2.4, Note: Requires

obtaining a master key to gain access through fire

doors. This step needs to be moved to the front of the

procedure as preoperations and made readily available so

as not to delay the detailed procedure steps.

4) Enclosure 4.1, Section 2, Step 2.0, second Note:

Specifies maintaining the spent fuel water level per

OP/1/A/6200/05.

Appropriate precautionary measures need to be added to

the procedure to ensure that the makeup water added to

the spent fuel pool is from the refueling water storage

tank or other suitable source. In addition, the baron

concentration is required to be equal to or greater than

2000 ppm. The standby makeup pump suction is from the

spent fuel pool.

5) Enclosure 4.1, Section 4, Step 2.2. Provide

instructions for converting the incore thermocouple-

digital readout to core temperature.

6) -Enclosure 4.1, Section 2, Step 2.2 Note: This note

needs to be expanded and clarified so.that the operator

knows what to look for when monitoring the standby

makeup pump D/P filter gauge.

The above items collectively are identified as Inspector

Followup Item (369/84-28-13 and 370/84-25-13), Amplify

and Clarify Certain Steps of OP/0/A/6100/17.

.

.-.

19

7) Enclosure 4.1, Section 3, Step 2.1, states to verify

that the auxiliary feedwater pumps start when Lo-Lo

level is reached on 2/4 steam generators. Steam

generator levels are maintained by dispatching an

operator to the auxiliary feedwater pump area and

position manual valves to control levels. The inspector

-

expressed a concern as to whether having three auxiliary

feedwater pumps feeding the steam generators, with the

unit in hot standby and natural circulation in progress

would be excessive. The inspector requested that an

analysis be performed to determine if SSF/SSS operations

would be jeopardized regarding maintaining hot standby

conditions, primary, and secondary volume control. The

parameters of specific interest that need to be

addressed are: effects on cooldown rate, amount of

reactor coolant system temperature decrease, the effects

on pressurizer level (amount of shrinkage), overfill of

steam generators, and effects on reactivity shutdown

margin. The time for an operator to be dispatched to

the auxiliary feedwater pump area, and conduct

operations to gain level control need to be considered

in the analysis. These concerns are identified as an

Unresolved Item (369/84-28-14 and 370/84-25-14),

Analysis Effects on SSF/SSS Operation, Potential

Excessive Feeding Steam Generators.

(b) AP/1/A/5500/01, Reactor Trip;

AP/1/A/5500/17, Loss of Control Room; and.

OP/0/A/6100/20, Operational Guidelines Following Fire in

Auxiliary Building or Vital Area

As a result of reviewing and conducting walkdowns of the

above procedures, and holding discussions with licensee

personnel, it. appears that the overall coordinated effort for

a smooth departur_e from the control room to the SSF/SSS to

maintain plant hot standby conditions is fragmented, not well

defined, and may lead to confusion, delays, and possible

errors.

The procedures as presently written has AP/1/A/5500/17, Loss

of Control Room, as the controlling document for establishing

systems and plant conditions for leaving-the controi. room and

then going to the auxiliary shutdown panels for - continued

plant control to eventually cold shutdown. The licensee has

stated, however, that when a fire disables the control room,

it will also make the auxiliary shutdown stations not

available for use. Based on these conditions, the inspectors

have the following findings and concerns:

, _ _ ._ _ . _ _

_

)

,

<

,

20

1) Review and correct the Initial Conditions specified in

OP/0/A/6100/17. Some of these conditions need to be

made procedure steps in order to establish the initial

conditions since AP/1/A/5500/17 will not be used.

2) Establish the necessary procedure steps to place the

plant and equipment in a stable hot standby which will

permit an orderly departure from the Control Room and

the use of the Standby Shutdown Sy3 ten.

3) Establish che necessary procedure steps to take the

plant from hot standby to cold shutdown. These

procedures will address shutdown from the control room

and shutdown from outside the control room.

4) Conduct final walkdowns of procedures giving particular

attention to procedural adequacy, access to system

components, and verify communications are satisfactory.

These concerns and findings were discussed with the licensee

on October 1, 2, and 3, 1984. Subsequent to these

discussions, a Confirmation of Action Letter dated October 9,

1984, was issued which identified October 5, and October 19,

1984, as dates for completing corrective actions on

procedures. The inspector identified this area as Unresolved

Item (369/84-28-15 and 370/84-25-15), Correct Procedure

Deficiencies Used to Accomplish 10 CFR 50, Appendix R,

Section III.L.

(c) Personnel Training

The inspectors- held discussions with training department

instructors to determine that training is being given concerning

the operation and use of the SSF/SSS. It was determined that

-personnel who are receiving training included senior reactor

operator (SRO), ' reactor operator (RO), and nuclear equipment

operators (NE0). The -licensee has scheduled training for the

required personnel. The inspectors reviewed the licensee's lesson

plans, _ training schedules, examination questions, and found these

documents _to be well organized, detailed, and comprehensive.

(d) Fire Damage Control-Procedures

The inspectors reviewed McGuire~ Nuclear Station Fire Damage-

Control Procedure No. IP/0/A/3090/23. The purpose of this

procedure _is to establish a method of making the diesel generators

operable, coritrolling 4.16kv breakers, -installing power and l

control cables to. certain 4.16ky motors, installing instrumenta- '

tion and restoring- valve operability after a' fire in order to

place the plant in cold shutdown status. The procedure identified

the motors, valves'and instrumentation required to bring the plant .

l

1

l

l

. . .l

__

,

.

21

to cold shutdown that would require restoration if damaged by

fire.

The procedure identifies the types of power cables required for

the identified motors. Included in the procedures are instruc-

tions for preparation of stress cones, instructions and routing

, for the. installation of temporary power and control cables and

clearing any control cables that may be faulted due to fire

damage. .This procedure provides for the manual operation of

4.16kv breakers after disconnecting certain remote control

conductors. Instructions are included for replacing certain

electronic sensing instrumentation (level transmitters, flow

transmitters, pr' essure transmitter, etc.) with direct heading

gauges. While drawings are provided as part of the procedure,

instructions require that the latest revision of the drawings be

used to perform the work.

The inspector examined a large box containing the required number

of stress cone kits needed to restore all the 4.16ky motor power

cables that were identified in the procedure. Included in this

box were the necessary gauges required for instrumentation

restoration along with various lengths of sensing line and

fittings. The licensee had designated nine reels of cables to be

used for the power cable replacement. The box of materials was

tagged to indicate the intended use and stored in the warehouse.

The cable reels.had not yet been located in a designated area.

The inspector examined the designated routes for the replacement

power cables for the centrifugal charging pump motors, the

residual heat removal pump motors and the component cooling pump

motors. The routes were found to be practicable and all areas

were accessible for cable pulling. It appears that the cables

could be installed with off-site power not available to power

electric pulling equipment but would require additional personnel.

,

6. Compliance With 10 CFR 50 Appendix R, Section III.0

The inspector (s) reviewed the as-built documentation / drawing file of the oil

collection system for the reactor coolant pumps.

Potential oil leakage points for each pump have been provided with _ a

Westinghouse designed ar.d.fu'rnished RCP oil containment system consisting of

a upper bracket oil overflow enclosure, lower bearing oil catcher, oil lift

enclosure, and oil ' tooler enclosure. These enclosures are connected to

drain piping which discharges into a separate collectionLtank provided for

each reactor coolant pump. The reactor coolant pump oil collection system

was' originally designed and installed at this facility prior to the issuance

-

of Appendix R. In -a letter dated January 9,1981, to the NRC, the licensee

acknowledged their previous commitments to provide the oil . collection

system, but.noted that the RCP oil containment system and its associated

drainage; system would require additional analysis to verify compliance with

_

.

4

22

the requirements of Appendix R,Section III.O. The analysis was completed

and the oil containment system and related drain piping were seismically

upgraded and modified to function following a design base seismic event.

This upgrade was performed under the licensee's seismic quality assurance

(QA) program as verified by a review of the following records:

a. Seismic Analysis:

-

Westinghouse Electric Corporation, Engineering Report Memorandum

5802, dated September 10, 1982

-

Duke Power Memorandum, File MC-1435.03, MC-1223.03, MC-1415.00,

MC-1421.00, dated February 17, 1982

-

Flow diagrams MC-1553-4.0 and MC-2553-4.0

b. Upgraded Seismic Hanger Inspection:

Design Isometric Date of Final

Hanger Number Drawing QC Inspection

1-MCR-NC-2342 (MCSRD-SPM118/1440 11/16/82

1-MCR-NC-2269 MCSRD-SPM118/144A 02/21/83

1-MCR-NC-2303 MCSRD-SPM118/144C 11/13/82

Since both units were operating at full power during the inspection

period, the inspector (s) were unable to review the reactor coolant pump

oil collection system's installation for conformance to the design

requirements. This review will be made during a ' subsequent NRC

inspection when the units are in a refueling outage. Within the areas

reviewed, no items of noncompliance or deviations were identified.

7. Compi*ance With 10 CFR 50, Appendix R, Section III.J

Section III.J, requires that: " Emergency lighting units with at least an

8-hour battery power supply shall be provided in all areas needed for

operation of safe shutdown equipment and in access and egress routes

thereto."

a. Emergency Lighting System Walkdown

The inspector (s). performed a-walkdown examination of the design and

installation of the 8-hour emergency lighting. units for the facility

based upon the licensee desig, drawings, and the post-fire alternate

shutdown procedures utilizing .the standby shutdcwn system,

OP/0/A/6100/17,.0peration of the Standby Shutdown Facility, and

AP/1/A/5500/17, Loss of Control Room. Also, the battery powered

' lighting units for several plant areas were observed while energized to

determine the lighting beam direction and relative illumination levels.

, _~ _ _-

.

s'

23

4

As a result of the emergency lighting walkdown, it appears that

inadequate emergency Itghting conditions existed in the following plant

areas:

(1) Several lights in the Unit 1 doghouse were mounted behind concrete

! columns, piping, etc., which eliminate their effectiveness to

illuminate access ladders to safe shutdown related SM and SV

valves.

. (2) No 8-hour battery powered lighting units were provided for Units 1

!

and 2, Common Corridor 908 which provide a portion of the

access / egress routes between the main control room and the standby

shutdown facility.

The failure to meet the emergency lighting requirements of 30 CFR 50,

Appendix R,'Section III.J is identified as Violation Item (369/84-28-04

and 370/84-25-04), Failure to Comply with the Requirements of

10 CFR 50, Appendix R, Section III.J.

In addition, the licensee requested exemptions from the emergency

lighting requirements for several plant areas in letters dated

November 18, 1983, and February 20, 1984. These letters requested

i exemption from the requirement to provide 8-hour t:attery powered

emergency -lighting units in the standby shutdown facility and along a

portion of the yard area access route between the standby shutdown

facility and the turbine building. NRR granted the above enmption

based upon the licensee's commitment to place battery powered hand

.

'

lanterns in the control room to be used in emergency situations by the

plant operators. During the plant walkdown, an inspection was made to

determine if the battery powered hand lights were provided. Contrary

to the licensee's commitment the hand lights had not been installed in

the control room. However, after this item was identified, the

licensee took immediate corrective action and provided, for emergency

use, two battery powered hand lanterns within the control room. This

is identified as Deviation Item (369/84-28-05 and 370/84-25-05),

,

Failure.to Provide Battery Powered Hand Lanterns in the Control Room.

b. Evaluation of Emergency Lighting Testing Procedures

4

The inspector (s) reviewed the licensee's periodic opeational testing

procedures (PT/1/B/4350/09, Unit 1 Emergency . Lighting Annual' Test;

.

pT/2/B/4350/09, Unit 2 Emergency - Lighting Annual Test.), and ampleted

tests records for 1983 and 1984 on the emergency lighting system. And

as a result of this review, the following discrepancies were

identified:

(1) The = emergency lighting annual . test procedures- did not address

. verifying whether the light beam is pointed in the correct

direction to illuminate all . proper pieces of equipment, electrical

,

cabinets, enclosures, or access / egress path ways required for

emergency operation.

. _-

. . - . . .

.

.

24

(2) The procedures did not provide for immediate corrective actions or

compensatory measures to be taken for deficiencies found during

performance testing of the periodic operational test.

(3) The procedures did not provide the testing frequency and scope of

performance testing in accordance with the manufacturer's

recommendations which:

-

Require the test button be depressed for at least one to two

minutes to assure verification of AC to battery DC transfer

capability and adequate electrical power drain from the

battery to verify operation of the battery charging circuit

of .the battery charging circuit, and

-

Require a specific testing frequency for a particular

manufacturer's lighting unit. The emergency lighting testing

frequency at McGuire is greater than that recommended by the

manufacturer. From the review of the test records, it

appears that the test period for all emergency battery

powered lighting units ranged from two months to almost seven

months duration for both units. Specific dates that

individual battery powered lighting units were tested are not

recorded making testing frequency of the individual lighting

units indeterminate.

(4) The procedures did not include or reference capacity of the 8-hour

self-contained battery packs nor scheduled battery pack

replacement.

Based upon the deficiencies listed above, the 8-hour emergency lighting

system design, performance testing, and surveillance and maintenance

programs appear to be inadequate for ensuring that such a system is

always operational to enable operators to transfer control to, and

operate the SSF and SSS functions. These findings are identified as

Inspector Followup Item (369/84-28-06 and 370/84-25-06), Inadequate

Surveillance Testing Procedures for Emergency Lighting, and will be

reviewed during a subsequent NRC inspection.

8. Fire Protection and Prevention Program

a. Fire Protection for Safety-Related Pumps

The Unit I license condition 2.C.(4) and Unit 2 license condition

2.C(7) requires the licensee to fully implement and maintain in effect

all provisions of the approved fire protection plan. The McGuire

Nuclear Station Fire Protection Review, September 1982 Revisien,

Section F.11 - " Safety-Related Pumps", indicates that redundant

safety-related pumps are separated by required fire barriers and

automatic detection with alarm and annunciation in the control room.

An inspection was made to determine if this license condition was fully

.- .. . .

.

e  !

25

'

.

g .

' implemented with regard to section F.11 of the approved fire protection

plan.

The following safety-related pumps have been identified as not being

4 separated by a fire barrier:

~

-

Recycle Evaporator Feed Pumps, Room 620

-

Waste Drain Tank Pumps, Room 639

-

Boron Injection Recir. Pumps - Unit 2, Room 788

,

-

Boron Injection Recir. Pumps - Unit 1, Room 730

-

Fuel Pool Cooling Pumps - Unit 1, Room 816

-

Fuel Pool Cooling Pumps - Unit 2, Room 829

The following safety-related pumps have been identified as not being

provided with automatic fire detection capabilities:

-

Recycle Evaporator Feed Pumps, Room 620

-

Waste Drain Tank Pumps, Room 639

-

Fuel Pool Cooling Pumps - Unit 1, Room 816

-

_ Fuel Pool Cooling Pumps - Unit 2, Room 829

The failure to fully implement the provisions of the approved fire

protection plan as required by the operating license is identified as

Violation Item (369/84-28-07 and 370/84-25-07), Failure to Provide

Automatic Fire Detection for- and Fire Barriers to Separate

Safety-Related Pumps,

b. Hydrogen Piping Systems

A review was made of the hydrogen gas piping systems to the volume

control tanks and reactor coolant drain -tanks. The hydrogen for the

volume control tanks is supplied from the bulk gas storage located in

the plant yard. The hydrogen to the reactor coolant drain tanks is

supplied from two H2 cylinders also lo'cated in the bulk gas storage

structure outside in the plant yard. The following documentation was

reviewed to verify that the systems were seismically supported. .

Flow Diagram No.

'

- MC-1603-1.0

- MC-1565-1.1

-MC-2565-1.1, and .

i

'

- Duke Power Memorandum W. H. Taylor, Jr. to P. R. Herran, dated

September 27, 1984, McGuire Nuclear Station, W. L. System

Upgrade of Piping to Class F, File MC-1206.02.88 j

The hydrogen gas piping to the volume control tanks inside the i

!

auxiliary building .is designed and installed as Duke Class F (ANSI l

B31.1-Seismic loadin'g). Hydrogen: piping to ; the reactor- drain tanks j

, extends from the yard through -the - turbine building, service building, l

"

,

)

l

!

._2._____ - - _ - _ - - _ _ _ _ , _ _ _ _ _ _ _ _ - _ _ - _ . . --____-_____-_-_:_____. . _ _ _ _ _ _ _ - _ - _ - _ _ - - _ _ _ . _ - _ _ - - _ _ _ - . - - - - _ . _ _ _ _ . _ _ _ _ - _ _ _ _ - _ . _ _ - -

o

. -

...

%

26

auxiliary building and reactor building through the drain tank. The

piping at the entrance to the auxiliary building to the reactor

building containment isolation boundary is Duke Class F, Class C and

Class B respectively, designed for seismic loading.

As noted in' the above Duke memorandum, the piping (approximately 43

inches in length) from containment isolation valves 1WL39A (Unit 1) and

2WL39A (Unit 2) to the reactor coolant drain tanks has been modified to

seismically qualified Duke Class F. The supports are designed with

seismic loads per calculation MCC-1206.12-05-2014 (Unit 1). and

MCC1206.16-27-3104 (Unit 2). Based upon the above review, the hydrogen

piping within safety-related plant areas appears to meet the general

design requirements.

c. Fire Pumps

During the inspection, a question arose regarding the availability of

the three fire pumps for fire suppression activities in certain

instances. Fire pumps A and B are powered from 6900 VAC non-safety

load centers 2TB and ITD respectively, and fire pump C is powered from

a 44ky substation separate from the plant switchyard.

Appendix R requires the plant to recover from the effects of a fire and

be in cold shutdown in 72 hours8.333333e-4 days <br />0.02 hours <br />1.190476e-4 weeks <br />2.7396e-5 months <br /> with the loss of offsite power (LOP).

An LOP at McGuire could render all three fire pumps inoperative, in

that ~ none of the fire pumps are fed from the emergency diesel

generators, which would greatly hamper fire suppression efforts.

Assuming that LOP is caused by grid instability, pump C could also be

lost even though it is fed from a dedicated off-site 44kv line which is

separate from the station switchyard.

A review of the Technical Specifications for McGuire Nuclear Station

revealed another, area of concern. Section 3/4.7.10, Fire Suppression

System, requires that at least.two fire suppression pumps be operable

at all times. There is no requirement as to which pumps must be

operable. Therefore, pump C could be inoperative for -an unlimited

amount of time as long as pumps A and B are inservice /available.

Pumps A and B would be lost on the LOP and with pump.C out of service

the plant would have very limited fire suppression capability. Since '

Appendix R requires that the LOP to be considered concurrent with the.

fire event, it is conceivable that no fire pumps would be available to

support fire fighting activities.

This item is being reviewed by the NRC' staff and is identified as

Unresolved Item (369/84-28-08 and 370/84-25-08), Adequacy of Power

Supplies for Fire Pumps A, B and C.

!

.

'

.

.

27

d. Emergency Communications

Post Fire Alternate Shutdown Procedure OP/0/A/6100/17, Operation of the

Standby Shutdown Facilities, requires that communications must be

established between the various areas of the plant where local control

actions must be taken. This procedure identifies that portable radios

can be utilized _as one method of establishing communications. By

letter dated December 14, 1982, the licensee responded to NRR's

questions concerning the standby shutdown system. The licensee's

response to questions 0 and P states that portable radios will be

available for communications between the standby shutdown facility and

the auxiliary feedwater local control stations.

An inspection was made which evaluated the adequacy of the radio

communications by actually establishing radio communications between

the various local control stations (i .e. , Units 1 and 2 Train "A"

switchgear rooms, Unit 1 doghouse, and Units 1 and 2 Steam Driven

Auxiliary Feedwater Pump Rooms) and the Standby Shutdown Facility.

However, direct radio communications were not feasible between the

standby shutdown facility and the auxiliary feedwater local control

stations and other essential control stations required for the

operation of the standby shutdown system. This item is identified as

Deviation Item (369/84-28-09 and 370/84-25-09), Failure to Provide

Adequate Radio Communications Between Local Control Stations and the

Standby Shutdown Facility.

9. Licensee Identified Items

a. June 1, 1984 Nonconformance Report, Potential Fire Damage to Unit 2

Turbine Driven Auxiliary Feedwater Pump Suction Valves: On May 18,

1984, the licensee discovered that the location and protection of

auxiliary feedwater pump suction valves 2CA-161C and 2CA-1626 were not

in accordance with previous commitments made to the NRC and were in

nonconformance to 10 CFR 50, Appendix R, Section III A. These valves

are required to open automatically to align a long term source of water

supply to the suction of the turbine driven auxiliary feedsater pump

(TDAFP) in case of fire in the adjacent motor driven auxiliary

feedwater pump (MDAFP) room. A fire within the MDAFP room could have

damaged the two MDAFPs and caused damage to the TDAFP suction valve

operators and/or associated cables thus eliminating the capacity for

automatic alignment to the long term water source. However, a

postulated fire in the MDAFP roora of sufficient intensity to- damage

j both MDAFPs and the automatic _ switchover capacity of valves 2CA-161C

' and 2CA-162C was'unlikely due to the light combustible fire loading and

the availability of the early warning automatic fire detection system '

/ and the automatic wet pipe sprinkler system within the room.

Furthermore, the normal suction source to the TDAFP would be available

to provide a water source for a minimum of 41s hours. .This would

probably have allowed adequate time for the fire brigade to extinguish

the fire and' operators to manually realign the valves if necessary.

__ . _ _ _

.

' s

..'

28

This nonconformance was identified by the licensee and promptly

reported to' the NRC on May 18, 1984. Also, as noted above the

deficiency did not present a significant threat to the health and

safety of the public. Therefore, since this discrepancy meets the

guidelines of. 10 CFR 2, Appendix C, Section IV.A, for licensee

identified problems, no violation is being issued. ,

The licensee's ~ corrective action consisted of the installation of a

one-hour fire. barrier enclosure for valves 2CA-161C and 2CA-162C and

associated cables. This arrangement brought this area up to meet the

'

provisions of Appendix R,Section III.G.2, except the structural steel

supports for TDAFP piping and cables to operators for valves 2CA-161C

and 2CA-162C are not protected to provide a fire resistance equivalent

to that of the one-hour fire barriers. This does not meet the

, requirements of'10 CFR 50, Appendix R, Section III.G.2, as required by

License -Section 2, Item C.7.a, and is identified as an example of

'

Violation Item (369/84-28-10 and 370/84-25-10), Structural Steel Fire

Barrier Supports Not Provided with Fire Resistant Rating Equivalent to

the Fire Barrier.

b. August 2, 1984 Nonconformance Report, Potential Fire Damage to

Redundant Safe Shutdown Equipment and Cabling in Various Fire Areas of

Units 1 and 2. On July 18, 1984, the licensee discovered a number of

' areas in Units 1 and 2 which were in nonconformance to commitments made

to the NRC and to the requirements of 10 CFR 50, Appendix R,

Section III.G. These discrepancies were promptly reported to the NRC

on July 18, 1984, and with a-followup written report sent to Region II-

on August 2, 1984. The following items were identified:

(1) Two suction valves which are arranged to open automatically to

align a long term source of water supply to the suction of the

Unit 1 TDAFP and associated cabling to the valve operators are

located within a Unit 1_ pipe chase and mechanical penetration

room. Redundant components and the cabling for the normal plant

shutdown systems of centrifugal charging pumps IA and 18 are also

,

located within this same fire area. A postulated fire in this

area could have incapacitated portions of all safe shutdown trains

and plant' shutdown would have been. difficult.to obtain. The room

was provided with automatic fire detectors but a fire suppression

system was not provided, the area is not readily accessible for

manual fire fighting operations, and is in a potentially high

radiation area.

The failure to meet the separation requirements of 10 CFR 50,

Appendix R,Section III.G, for this area as required by the

operating -license is identified as Violation Item (369/84-28-11),

Inadequate Appendix R,Section III.G, Fire Protection Features and

Separation Provided for Redundant Trains of Normal Shutdown

Systems and the Standby Shutdown System.

.

_ _ ____ - _____

.

,.

29

The licensee maintained an hourly fire watch patrol for this room

until the TDAFP cabling and valve operators were enclosed in a

three-hour fire rated barrier. This barrier was reviewed by the

inspectors and appeared satisfactory, except the structural steel

supports for valves, piping and cabling to the valve operators

were not provided with a' three-hour fire resistant rating as

required by Appendix R,Section III.G.

(2) Unit 1 Train A associated control circuits and the standby

shutdown system (SSS) cables are both located in Train 8 switch-

gear room. None of these cables were enclosed in a three-hour

fire barrier. A fire detection system is provided for this area

but a fire suppression system is not provided. A postulated fire

within the Unit 1 Train B switchgear room could have damaged

control cables for Train A centrifugal changing and auxiliary

feedwater pumps, control and power cables for the standby makeup

pump, and control and power cables for Train B centrifugal

changing and auxiliary feedwater pumps. This could have prevented

safe plant shutdown.

The failure to meet the separation requirements of 10 CFR 50,

Appendix R,Section III.G, for this area as required by the

operating license is identified as Violation Item (369/84-28-11),

Inadequate Appendix R,Section III.G, Fire Protection Features and

-

Separation Provided for Redundant Trains of Normal Shutdown

Systems and the Standby Shutdown System.

The licensee maintained an hourly fire watch for this area until

the normal Train A shutdown component cabling within Train B

switchgear room was enclosed within - a three-hour fire barrier.

This barrier was reviewed by the inspectors and appeared

satisfactory.

(3) Control and cabling for the MDFPs components and the other Train A

and B safe shutdown components including the cer trifugal changing

pumps are. routed through the Units 1 and 2 TDAFP rooms. The TDAFP

rooms are provided with fire detection systems and automatic halon

fire suppression systems. However, the cabling in this area was

not~ enclosed within a one-hour fire barrier as required by '

Appendix R,.Section III.G. A postualted fire within one . of the

TDAFP rooms of sufficient ' intensity to damage the shutdown

components 'to prevent plant shutdown was not probable due to the

low fire loading within the rooms, early . warning fire detection

system, and automatic halon fire suppression system.

This discrepancy was promptly reported to the NRC after being

~ identified by the licensee on July 18,1984, : and with a written

report sent to Region II on August 2, 1984. An hourly fire watch

was initiated and is to be maintained until the. controls and

~

cabling associated with the MDAFP suction valves are removed from

the Units 1 and 2 TDAFP rooms and/or the Train B -shutdown cabling

I

,

j

e.

_ - _ - .

.. _ . _ -

.

s

.*

30

within - the TDAFP rooms are enclosed within a one-hour fire

barrier. Based on the above, this discrepancy did not present a

significant threat to the health and safety of the public, was

identified by the licensee, and appropriate corrective action was

initiated. Therefore, this discrepancy meets the guidelines of

10 CFR 2, Appendix C,Section IV.A, for licensee identified

problems and no violation is being issued.

c. August 3, 1984 Appendix R Deviation Notice:

During the licensee's ongoing fire protection program review, several

deviations from Appendix R . were identified. These deviations and

technical justifications were forwarded by the licensee to NRC/NRR on

August'3, 1984. These deviations as listed below will remain

outstanding pending NRR evaluation:

(1) Steel Penetrating Fire Barriers

(a) The lh hour fire barriers between redundant nuclear service

water pumps and component cooling water pumps are penetrated

by cable tray hangers.

(b) The 3-hour fire walls separating the TDAFP and MDAFP room are

penetrated by steel pipe supports and restraints.

(2) Reactor Building Wall Penetrations

'

(a) Process piping penetrations in reactor building are designed

for pressure boundary integrity .in lieu of fire boundary

penetrations.

(b) Spare sleeves and instrument tubing penetrations are sealed

by steel plate or pipe cap on the auxiliary building side of

sleeve.

4

(c) HVAC duct penetrations do not have fire dampers.

(d) Access into the reactor building from the auxiliary building

is provided by two portals which have not been fire tested.

(3) Fire Boundary Doors With . Security Hardware

Fire doors have been modified to meet security requirements and

-some fire walls have security and other special type doors in lieu

of standard fire dcors.

(4) . Cork Expansion Joints

Cork has .been provided in the structural joints between : cme

structures for seismic considerations. However, this configura-

tion has not been tested for three-hour fire resistance rating.

.. ., , - - -

- _ _ _ . . . - - . _ _. . - ._ __ _ _ __- _ _ _ . . _ _ . . --. _ _ . . _ _ .

,

,,>

...

' 31

,

.The above items. do not technically meet Appendix R requirements and

'

other NRC guidelines. -Therefore, pending NRR evaluation, these items

are identified as Unresolved Item (369/84-28-12 and 370/84-25-12), NRR

Evaluation of Appendix R Deviation Request of August 3,1984, and will

~

be-reviewed during a subsequent NRC inspection.

1

r

a

?

.

.I

e

d-

.

i

L

!

<

!

l

t

.

I

'

i

.i

i

'

i

.

1-

i

s'

'

(

i

,. i

. I

,

1

-m..

  • - , mv ,- , ,_e ., wy s --,~w r er - -

-v-. - .t-y- w-*e v -

yve