ML20114E61920 June 1996Forwards Event Notification Worksheet Re 960413 Event Concerning Defective Cam Follower Springs for Edgs. Replacement Springs Obtained from Mfg W/O Defect
ML20205R89830 March 1987Followup Ro:On 870317,portion of Fire Suppression Water Sys Made Inoperable Due to Leak in Piping.Small Hole Discovered in Cement Asbestos Pipe Used for Fire Protection Piping. Parts Ordered & Sys Expected to Be Back in Svc by 870430
ML20204B54018 March 1987Ro:On 870318,portion of Tech Spec 3.7.9.1b Re Fire Suppression Sys Made Inoperable in Order to Perform Corrective Maint.Leak Developed on East Leg of Outside Fire Protection Ring Header.Broken Pipe Suspected
ML20211G56219 February 1987Special Rept:On 870212,fire Protection Sys Inoperable for More than 14 Days Due to Incomplete Calibr Procedure.Caused by Scheduling Methodology & Personnel Error.Fire Detection Sys Returned to Operation on 870212
ML20207P78716 January 1987Ro:On 870114,fire Suppression Water Sys Inoperable,Per Tech Spec 3.7.9.1,due to Isolation of West Leg of Unit 2 Turbine Bldg Fire Header to Allow for Replacement of Pipe on Fire Hose Standpipe 48.Item Not Reportable
ML20214K43520 November 1986Followup Ro:On 861106,north Leg of Fire Suppression Water Sys Outside Ring Header Between Valves FP-109 & FP-112 Inoperable.Section Isolated to Replace Piping.Pipe Replacement Underway & Will Be Returned to Svc by 861215
ML20215E0442 October 1986Ro:Fire Door 227 Inoperable Since 860826 Due to Operator Failure & Fire Door 350 Inoperable Between 860912 & 22 Due to Supervisor Failure.Design Change for Door 227 Initiated & Door 350 Repaired
ML20197D6631 May 1986Special Rept:Min Lower Limits of Detectability in Lake Water Sampling & Drinking Water Stations Exceeded Limits of Tech Specs.Caused by Inefficient Radiochemistry Counting Equipment.Water Samples Sent to Contractor
ML20151R80024 January 1986Special Rept:On 841202,fire Protection Deluge Sys for ESF Ventilation Sys 1-HV-AES-1 Charcoal Filters Inoperable in Excess of 14 Days.Fire Suppression Sys Manually Isolated. Tech Spec Change Request Being Processed
ML20137L8519 January 1986Ro:On 851121 & 1212,high-range Area Radiation Monitor Failed.Caused by Inadequate analog-to-digital Inherent Drift Considerations During Calibr.Monitor Recalibr & Restored to Svc on 860102.Info Submitted Per Util
ML20141F20427 December 1985Ro:On 851227,fire Suppression Water Sys Inoperable.Caused by Leak in Sys Which Resulted in Sectionalizing Outside Ring Header.Backup Fire Suppression Available from Nearby Hose Station & Dedicated Plant Fire Truck
ML20137M0939 December 1985Ro:On 851029,while in Mode 3,steam Generator PORV Radiation Monitor MRA-1701 Failed to High Alarm Status.Caused by Defective Detector.Detector Replaced & Sys Restored to Operable Status on 851113
ML20107K13120 February 1985Ro:On 850107,low Pressure CO2 Sys Declared Inoperable When Common Halon/CO2 Piping Header Modified by Design Change DC-12-2624 & Remained Inoperable in Excess of 14 Days.Design Change Implemented to Maintain Halon Concentrations
ML20101L74528 December 1984Special Rept Re 11 Inoperable Fire Doors in Excess of 7 Days.Caused by New Door Assemblies Not Fitting Designated Location & Scheduling Problems Due to Unforeseen Installation & Hardware Problems
ML20099B8638 November 1984RO-84-021-0.Due to Complexity of Event,Updated Submission Delayed Until 841207
ML20083J83320 December 1983Ro:On 831220,discovered That Action Statement in Tech Spec Table 3.3-13 Not Met.Samples Required for Weekly Analysis Not Continuously Collected W/Auxiliary Sampling Equipment. Followup Rept Will Be Submitted within 14 Days
ML20082T1255 December 1983RO SI-07/08:on 831104,steam Line Pressure Safety Injection Signal Switch Placed in Reset Instead of in-block Position. Train B Safety Injection Occurred.Caused by Personnel Error. Operator Counseled
ML20082F69721 November 1983Ro:On 831119,while Performing Investigation Into Why High Oxygen Level Existed in One Gas Decay Tank,Action Statement (B) of Tech Spec 3.11.2.5 Not Complied With.On 831103,waste Gas Holdup Tank Concentration Exceeded 4%
ML20082J58821 November 1983Ro:On 831119,while Performing Investigation Why High Oxygen Level Existed in Gas Decay Tank,Discovered That Concentration in Waste Gas Holdup Tank Exceeded 4% for Both Oxygen & Hydrogen on 831103
ML20082J70018 November 1983Ro:On 831117,Loop 1 Overpower Delta Temp Rod Stop & Reactor Trip Bistable Failed & Loop 2 Overtemp Delta Temp Bistable Failed High.Module Replaced,Recalibr & Returned to Svc
ML20082C61014 November 1983Ro:On 831028,during Containment Purge,Two Radioactive Gaseous Monitoring Instruments Inoperable for 6 Hrs & 2 Minutes,Contrary to Tech Specs.Tech Spec Change Will Be Initiated to Remove Requirement for Monitors
ML20081H86728 October 1983Ro:On 831028,during Contamination Purge in Mode 5,two Radioactive Gaseous Monitoring Instruments Inoperable, Violating Tech Specs.Initially Reported 831028.Followup Rept Will Be Submitted within 14 Days
ML20081G03927 October 1983Suppl to RO Reported on 831020 Re Unit Operating in Mode 4 W/Automatic Actuation Logic Inoperable.Subsequent Review Revealed Automatic Actuation Logic Operable.Ro Retracted
ML20081G34325 October 1983Ro:On 831024,while in Operational Mode 4,for Steam Generator Crevice Flushing,Esf Automatic Actuation Logic Sys Inoperable Per Tech Specs.Followup Rept Will Be Submitted within 14 Days
ML20081G98520 October 1983Ro:On 831020,due to Misunderstanding in Communicating Requirements for Fire Protection,Hourly Fire Watch Checks for Drumming Room Not Performed as Required.Min Number of Detectors Required Not Violated.Rept RetractedFire Watch
Hourly Fire Watch
ML20085K76911 October 1983Ro:On 831003,24 H Rept Notification Made Re Incorrect Installation of Containment Hydrogen Monitoring Sys.Sys Modified & Reinstalled Correctly on 831005
ML20080R11410 October 1983Ro:On 831007,wrong Valves Used for Ep(Z) in-core Detector Computer Code During Cycle Viii Operation
ML20080Q3804 October 1983Ro:On 831004,steam Jet Air Ejector Monitor (SRA-2905) Determined Inoperable & 8 H Grab Sample Not Completed within Required Time Frame.Followup Rept Expected within 14 DaysGrab sample
ML20080Q1093 October 1983Ro:On 830930,while Making pre-startup Valve Lineups, Discovered Pump Reversal on Component Cooling Water Supply & Return Piping for Containment H Sampling Sys.Sys Being Reviewed to Determine Effect During Accident Conditions
ML20080P23929 September 1983Ro:On 830929,during Insp of Containment Lower Vol,One Drop Per Second Leak Discovered on Nonessential Svc Water Sys. Leak Originated at Packing on Manual Isolation Valve. Followup Rept Will Be Submitted within 14 Days
ML20078G43027 September 1983Ro:On 830927,during Sampling Process,Sample Valve on Boron Injection Tank Found Partially Open Allowing Boric Acid Solution to Drain Out.Caused by Personnel Error.Boron Injection Tank Brought Back Into SpecBoric Acid
ML20080Q10827 September 1983Ro:On 830926,carbon Dioxide Sys for Diesel Generator Room Left in Isolated Condition W/No Personnel in Attendance.Upon Discovery,Sys Immediately Returned to Operable Status
ML20078A50515 September 1983Ro:Penetration Cable Tunnel in Quadrant 2 Left in Isolated Condition W/O Fire Watch for Approx 2 H.Equipment in Area Not Required to Be OperableFire Watch
ML20077P1126 September 1983Ro:On 830903,carbon Dioxide Protected Area Left in Isolated Condition W/No One Working in Area.Sys Restored to Operable Status.Followup Rept Will Be Submitted in 14 Days
ML20076K7895 July 1983Ro:On 830704,during Routine Tour of Containment,Leak Discovered in Nonessential Svc Water Sys.Written Rept Will Be Forwarded within 14 Days,Per IE Bulletin 80-24
ML20072J24217 June 1983Ro:On 830612,performance of Train B Boron Injection Tank Inlet Piping Heat Trace Circuitry Questioned,But Train Not Declared Inoperable Until 830616.Investigation Underway
ML20072C9583 June 1983Ro:On 830603,maint Personnel Discovered Gauge Had Been Removed from Outside Wall of Outer Airlock Door Providing Vent Path from Containment to Auxiliary Bldg When Inner Airlock Door Open.Pressure Gauge Reinstalled
ML20072C4633 June 1983Ro:On 830603,during Operational Surveillance Test,Both Containment Spray Sys Made Inoperable for Approx 15 Minutes. Error Discovered in Independent Verification of Valve Lineup.Immediate Action Taken to Restore Spray Sys
ML20074A6069 May 1983Ro:On 830506,discovered That Chemical Vol Control Sys Holdup Tanks Not Sampled in 12 H Time Period Required When Automatic Gas Analyzer Inoperable.Sample Performed Approx 4-5 H Late
ML20069L80820 April 1983Ro:On 830420,waste Gas Holdup Sys Exceeded Oxygen & Hydrogen Limits.Cause Not Stated.Proposed Tech Spec Changes Increasing Oxygen Concentration Limit Will Be Reviewed by 830422.Followup Rept Will Be Submitted within 14 Days
ML20073M59915 April 1983Ro:On 830414,following Nonroutine Concentration Test,Control Room Cable Vault Halon Sys Declared Inoperable
ML20073F0086 April 1983Ro:On 830405,halon Sys Declared Inoperable Following Completion of Nonroutine Concentration Test.Followup Rept Will Be Submitted within 14 Days
ML20072H30617 March 1983Ro:On 830219,reservoir Containing Lubricating Oil for Turbine 2 Leaked Into Lake Mi.Caused by Tube Failure.Tube Plugged
ML20069E54814 March 1983Ro:On 830311,fire Door in Boron Injection Tank Room Found Not to Have Label to Substantiate Ul Certification.Cause Not Stated.Continuous Fire Watch PostedContinuous fire watch
ML20072C44724 February 1983Ro:On 830224,during Review of Computerized Printout Which Delineates Calibr Surveillance Test Schedules,Discovered That Containment Fire Detector Instrumentation Surveillance Test Not PerformedFire Watch
ML20070T1751 February 1983Ro:On 830201,outlet Valve of Spray Additive Tank Discovered in Closed Position.Valve Immediately Opened
ML20064G5363 January 1983Ro:On 821223,presence of Obstruction in Valve SI-152-S Prevented Attainment of Min Required Flow Through South Safety Injection Header.Caused by Unattached Disc from Previous Repair of SI-152-S Lodged W/Valve.Disc Removed
ML20067C6252 December 1982Ro:On 821201,west Centrifugal Charging Pump Rendered Inoperable Following Mod on East & West Centrifugal Pump Common Mini Flow Line.Caused by Cut Made on Pressurized Portion of Piping.Investigation in Progress
ML20067B05324 November 1982Ro:On 821123,essential Svc Water Sys Motor Operated Valve WMO-753 Failed to Open.Caused by Reverse Operation of Valve Due to Incorrect Installation of Cable Feeding Motor Control Ctr During 821117 Design Change
ML20066A88927 October 1982Ro:On 821027,informed That in Past Instances,Plant Did Not Correctly Implement Tech Spec 3.3.3.7 Re Defective Pyrotronics Ionization Detection.Annunciator Response Procedures Revised & Spare Detectors ProvidedFire Watch