Special Rept:On 841202,fire Protection Deluge Sys for ESF Ventilation Sys 1-HV-AES-1 Charcoal Filters Inoperable in Excess of 14 Days.Fire Suppression Sys Manually Isolated. Tech Spec Change Request Being Processed
ML20151R800
Person / Time
Site: Cook  
Issue date: 01/24/1986
From: Will Smith
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8602060240
Download: ML20151R800 (2)


Text

O M8 o

1 PRIORITY ROUTING 4

  • p T

NY.hkY

~~",, INDI NA & MICHIGAN ELECTRIC COMPANY f

L f U

" ss' f

DONALD C. COOK NUCLEAR PLANT P.O. Box 458, Bridgman, Michigan 49106 DFSS t

(616) 4654901 DRMA Of PLC FIL b January 24, 1986 Donald C. Cook Nuclear Plant Unit Nos. 1 and 2 Docket Nos. 50-315 and 50-316 License Nos. DPR-58 and DPR-74 Mr. J.G. Keppler, Regional Administrator United States Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137

Dear Mr. Keppler:

In accordance with Technical Specification 3.7.9.2 Action Statement A we are submitting this Special Report to advise you that the Fire Protection Deluge System for the ESF Ventilation System 1-HV-AES-1 charcoal filters, was inoperable in excess of 14 days.

The Unit 1 Reactor Coolant System entered Mode 4 on December 2, 1984, at which time the ventilation unit and the Fire Suppression System were required to be operable.

The Fire Suppression System was manually isolated to prevent exposing the ESF Ventilation System Charcoal Filters to water damage due to leaking automatic isolation valves and sticking check valves'in the associated drainage system.

The system was returned to service following valve repairs.

The check valves are presently being replaced with stainless steel check valves.

During the time the system was declared inoperable it was always available for manual actuation.

A Technical Specification change request is being processed changing the mode of operation of the Fire Suppression System from an automatic system to a manual system.

The public health and safety were not affected by this event.

Sincerely, g44/ -

pn2 nsn 885Np W.G.

Smith Jr.

S Plant Manager