ML20085K769

From kanterella
Jump to navigation Jump to search
Ro:On 831003,24 H Rept Notification Made Re Incorrect Installation of Containment Hydrogen Monitoring Sys.Sys Modified & Reinstalled Correctly on 831005
ML20085K769
Person / Time
Site: Cook American Electric Power icon.png
Issue date: 10/11/1983
From: Will Smith
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8310210137
Download: ML20085K769 (1)


Text

bMS h

W]=,,,,, INDIANA & MICHIGAN ELECTRIC COMPANY C'

y, DONALD C. COOK NUCLEAR PLAh"r P.O. Box 458, Bridgman. Michigan 49106 (616) 465-5901 October 11, 1983 Mr. J.G. Keppler, Regional Administrator United States Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137 Operating License DPR-58 Docket Nos. 50-315

Dear Mr. Keppler:

On October 3, 1983, a 24-hour report notification was made relative to the incorrect installation of our Containment Hydrogen Monitoring System.

At that time we informed you that the component cocling water supply and return piping for the Containment Hydrogen Sampling System sample pumps and sample cooling coil were reversed.

This condition was subsequently reviewed by our Corporate Engineering Department who have deemed that the Nash vacuum pumps and the Beckman hydrogen analyzer would have fulfilled their intended function of monitoring the hydrogen gas concentration in the containment atmosphere following a LOCA.

The results of our calculations have been reviewed with the manufacturer and they have concurred with our findings.

On October 5, 1983, this system was modified and is now installed correctly.

Based on our engineering study and the fact that the system would have performed its intended function, we are rescinding our 24-hour notification.

No further report is deemed necessary at this time.

Sincerely, 8310210137 831011 PDR ADOCK 05000315 S

PDR DN'd.'mfth7-J).

W.

Plant Manager

/bab cc:

John E. Dolan J.M. Hennigan M.P. Alexich R.O.

Bruggee R.F. Kroeger INPO H.

Brugger PNSRC E.

Swanson/N. DuBry, RO:III J.F.

Stietzel R.C. Callen, MPSC E.L. Townley G. Charnoff, Esq.

Dir., IE (40 copies)

Dir., MIPC (4 copies)

DCT 14 m.

\\0 722%

__