ML20101L745

From kanterella
Jump to navigation Jump to search
Special Rept Re 11 Inoperable Fire Doors in Excess of 7 Days.Caused by New Door Assemblies Not Fitting Designated Location & Scheduling Problems Due to Unforeseen Installation & Hardware Problems
ML20101L745
Person / Time
Site: Cook  American Electric Power icon.png
Issue date: 12/28/1984
From: Will Smith
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To:
NRC OFFICE OF ADMINISTRATION (ADM)
References
NUDOCS 8501020357
Download: ML20101L745 (2)


Text

?

s' O C INDIANA & MICHIGAN ELECTRIC COMPANY u,,,,

DONALD C. COOK NUCLEAR PLANT P.O. Box 458, Bridgman, Michigan 49106 (616) 465-5901 December 28, 1984 Document Control Manager United States Nuclear Regulatory Commission Document Control Desk Washington, D.C.

20555 Operating License DPR-58/74 Docket Nos. 50-315/50-316 Document Control Manager:

This special report is being submitted pursuant to the requirements of Technical Specification 3.7.10 Action Statement (a) to inform you of Fire Rated Assemblies (Fire Doors) being inoperable in excess of seven days. The inoperable fire door events are all associated with the installation of a design change which upgrades fire doors as part of our Appendix "R" commitments. A total of 59 fire doors are affected by this design change.

During the modifications,27 of the doors remained inoperable in excess of seven days. The cause for this can be attributed to one or more of the following reasons-o On several doors the hardware from the existing doors had been designated for reinstallation on the new doors but for various reasons could not be used or required extensive modifications.

o New fire door assemblies did not fit the designated location, thus requiring modifications or replacement.

o Deficiencies were identified during a post-installation inspection by the Underwriters' Laboratory Representative.

Some of these deficiencies were corrected; however, for eleven doors the corrective actions require the procurement of replacement hardware and these doors remain inoperable.

l o

Scheduling problems due to unforeseen installation and hardware l

problems, f

i I

B501020357 841228 gDRADOCK 05000315

}p V%

1 61 PDR

' 0 l

b

}

-1 Document Control Manager December 28, 1984 While the eleven fire doors that did not receive'UL approval remain inoperable, T.S. 3.7.10 Action Statement. requirements are being met.

Procurement of the replacement hardware is being expedited and it is anticipated that the modi-fications will be completed and the doors declared operable no later than April 30, 1985.

Sincerely, b

W W. G. Smith, Jr.

Plant Manager BAS /ljl cc: John E. Dolan H. Brugger E. L. Townley.

J. G. Keppler R. C. Callen, MPSC J. F. Stietzel M. P. Alexich G. Charnoff, Esq.

INPO R. F. Kroeger J. M. Hennigan PNSRC D. Shermen W. C. Rigg NRC Resident Inspector i

t