ML20215E044

From kanterella
Jump to navigation Jump to search
Ro:Fire Door 227 Inoperable Since 860826 Due to Operator Failure & Fire Door 350 Inoperable Between 860912 & 22 Due to Supervisor Failure.Design Change for Door 227 Initiated & Door 350 Repaired
ML20215E044
Person / Time
Site: Cook  
Issue date: 10/02/1986
From: Will Smith
INDIANA MICHIGAN POWER CO. (FORMERLY INDIANA & MICHIG
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8610140414
Download: ML20215E044 (2)


Text

__

DD1G

  • C PRIORITY ROUTING if-

/ '*****

LicM -.-

GK IN0 LANA & MICHIGAN ELECTRIC COMPANY by-g Donald C. Cook Nuclear Plant P.O. Box 458. Bridgman, Mchigan 49106 ff

'~

q f October 2, 1986 g'

g_ __

WH9e~1 FILE F# W Donald C. Cook Nuclear Plant Nos. 1 and 2 Docket Nos. 50-315 and 50-316 License Nos. DPR-58 and DPR-74 Mr. J. G. Keppler, Regional Administrator United States Nuclear Regulatory Commission Region III 799 Roosevelt Rd.

Glen Ellyn, IL 60137

Dear Mr. Keppler:

This special report is being subnitted pursuant to the require-ments of Technical Specification 3.7.10 Action Statement (a) to inform you of two Fire Rated Assemblies being inoperable in excess of seven days.

Fire Door #227 (Unit 1, Access Door to the Turbine Driven Auxiliary Feed Pump Room) has been inoperable since August 26, 1986 due to the door closer coordinator's failure to operate as required. A design change request has been initiated to modify the door fre.me in the area of the door closer coordinator. This modification is necessary to strengthen the frame so as to prevent the door closer coordinator from tilting down into the path of the closing doors and obstructing them. Until the time that the design change review process is completed and implementation of repairs is achieved, Technical Specification 3.7.10 Action Statement requirements will continue to be met while the fire door is in an inoperable condition.

Fire Door #350 (Unit 2, Access Door in the 4KV Electrical Switchgear Room) was inoperable between September 12, 1986 and September 22, 1986 due to failure on the part of the responsible supervisor to take appropriate action within the required time. The failure of this door to be repaired in a prompt and timely manner was due to the supervisor responsible for the work not properly identifying the job's requirements when it was issued. After the supervisor recognized the significance of the door in question, repairs were implemented to return the door to operable status. The fire door was subsequently repaired and returned to service on September 22, 1986. Emphasis on jobs requiring immediate attention has been addressed to all concerned parties.

PDR ADOCK 05000315 E $g

)/g).a 8610140414 861002 V

g PDR

, fp I

October 2,'1986 J. G. Kipplar

- Page 2 Technical Specification 3.7.10 Action Statement requirements were met during the time that fire door #350 was in an inoperable condition.

Sincerely, o

W. G. Smith, Jr.

Plant Manager KFJ/kjh cc:

J. E. Dolan INPO M. P. Alexich PNSRC R. F. Kroeger H. R. Denton R. W. Jurgenson A. A. Blind R. C. Callen, EPSC Dottie Sherman, ANI Library G. Charnoff, Esq.

. NRC Resident Inspector D. Hahn File t

4 e

i

..-,-r.

e

,,,,---e-

,-e-r,-n

.,..,.r--.e.--e-w

, _. -. ~, -, -.,,,

--_c,,-#,..-w

-~.,_m._,---

--p e.. y.

y-,.

. -,. - -, - -. - -n.