INDIANA & MICHIGAN ELECTRIC COMPANY P.O. BOX 16631 COLUMBUS, OHIO 43216 PRIO2f Ty gy: TIM

$$3 - ULf January 9, 1986 jiF-4l

/k#

h(-

d AEP:NRC:0678R 07 R

~

d 2[i

Donald C. Cook Nuclear Plant Unit No. 2 d

7 Docket No. 50-316 License No. DPR-74 CONTAINMENT AREA RADIATION MONITOR Mr. James G.

Keppler, Regional Director U.S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, IL 60137

Dear Mr. Keppler:

This information is being transmitted to you in accordance with our letter AEP:NRC:0678N, dated August 8, 1985.

Unit 2 Containment high-range area radiation monitor VRA-2310 failed at 10:50 a.m. on November 21, 1985. The monitor was serviced and restored to operable status on December 11, 1985. On December 12, 1985 the same type of failure occurred on VRA-2310.

The monitor was restored to operable status on January 2, 1986 following recalibration.

It should be noted that throughout these periods of inoperability, the other containment high-range area radiation monitor in Unit 2, VRA-2410, was available for use in the event of an accident.

The cause of these failures was determined to be associated with the calibration of the analog-to-digital (a/d) converter board. The uncertainties allowed for in the calibration did not sufficiently account for the inherent drift in the a/d board. The revised calibration encompasses the values of the drift which caused the failures.

This document has been prepared following Corporate procedures which incorporate a reasonable set of controls to insure its accuracy and completeness prior to. signature by the undersigned.

Very truly yours,

<t 9601290111 860109 PDR ADOCK 05000316 g

PDR M.

. Al ich (

Vice President

[ 'h cm cc: John E. Dolan L

W. G. Smith, Jr. - Bridgman R. C. Callen G. Bruchmann G. Charnoff fg NRC Resident Inspector - Bridgman f