ML20082J700

From kanterella
Jump to navigation Jump to search
Ro:On 831117,Loop 1 Overpower Delta Temp Rod Stop & Reactor Trip Bistable Failed & Loop 2 Overtemp Delta Temp Bistable Failed High.Module Replaced,Recalibr & Returned to Svc
ML20082J700
Person / Time
Site: Cook 
Issue date: 11/18/1983
From: Will Smith
INDIANA MICHIGAN POWER CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8312020284
Download: ML20082J700 (1)


Text

42 e

Gg

.,.souan nicwomowa coman DONALD C. COOK NUCLEAR PLAhT P.O. Box 458, Bridgman. Michigan 49106 (6*3) 465-5901 November 18, 1983 Mr. J. G. Keppler, Regional Administrator United Sta6es Nuclear Regulatory Commission Region III 799 Roosevelc Road Glen Ellyn, Illinois 60137 Operating License DPR-58 Docket No. 50-315

Dear Mr. Keppler:

This is to confirm a telephone report made by our Assistant Plant Manager, Mr. B. A. Svensson, to your Mr. D. C. Boyd at 1535 hours0.0178 days <br />0.426 hours <br />0.00254 weeks <br />5.840675e-4 months <br /> on November 17, 1983, at which time we reported that two unrelated equipment failures on Unit I solid state reactor protection system placed the Unit in a less conservative condition than allowed by the applicable Action Statement

  1. 6 of Table 3.3-1, Technical Specification 3.3.1.1.

The first event, which occurred at 0910 hours0.0105 days <br />0.253 hours <br />0.0015 weeks <br />3.46255e-4 months <br /> on November 17, 1983, involved the Unit One, Loop 1, Overpower Delta Temperature Rod Stop and Reactor Trip Bistable failure. The bistable was declared inoperable, the module replaced, recalibrated, and the loop was returned to service at 1226 hours0.0142 days <br />0.341 hours <br />0.00203 weeks <br />4.66493e-4 months <br />.

The second event, which occurred at 1150 hours0.0133 days <br />0.319 hours <br />0.0019 weeks <br />4.37575e-4 months <br /> on November 17, 1983, involved the Unit One, Loop 2, Over Temperature Delta Temperature Bistable failure.

The bistable failed high. The problem was corrected and the loop was returned to service. The fact that two loops were inoperable at the same time created the prompt reportable situation.

As required by Technical Specification 6.9.1.12, a follow-up report will be submitted within fourteen (14) days.

Sincerely, V{}0hW'Q W. G. Smith D r.

8312O20284 831118 Plant Manager PDR ADOCK 05000315 S

pop WGS:frb cc:

J. E. Dolan J. M. Hennigan M. P. Alexich R. O. Bruggee R. F. Kroeger INP0 H. Brugger PNSRC E. Swanson, R0:III J. F. Stietzel R. C. Callen, MPSC E. L. Townley G. Charnoff, Esq.

Dir., IE (40 copies)

Dir., MIPC (4 copies)

NOV 2 s g Z 4E.2

.