INDIANA &_n9/CHIGAN POWJR COMPAMX y,a.,,.

DONALD C. COOK NUCLEAR PLANT P.O. Box 458, Bridgman, Michigan 49106 (616) 465-5901 November 14, 1983 Mr. J. G. Keppler, Regional Administrator United States Nuclear Regulatory Commission Region III, 799 Roosevelt Road Glen Ellyn, Illinois 60137 Operating License DPR-58 Docket No. 50-315

Dear Mr. Keppler:

The purpose of this letter is to rescind a 24-hour notification that was made to your Mr. Boyd on October 28, 1983. At that time we advised Mr. Boyd that during a Unit 1 Containment Purge, while in Mode 5, two of our Radioactive Gaseous Monitoring Instruments (ERS-1300 and ERS-1400) were inoperable for a time period of 6 hours6.944444e-5 days <br />0.00167 hours <br />9.920635e-6 weeks <br />2.283e-6 months <br /> and 2 minutes, contrary to Technical Specification 3.3.3.10, Table 3.3-13, Item 4.

Subsequent investigation into this event revealed the 'following:

1.

There were no releases via this pathway; thus the monitors (ERS-1300 and ERS-1400) were not required to be operable.

2.

When the Unit is in Mode 5, the requirements for Contain-ment integrity and purge isolation are not applicable.

These monitors (ERS-1300 and ERS-1400) are strictly used to monitor containment conditions for personnel habitability.

3.

The Donald C. Cook Plant does not use ERS-1300 and ERS-1400 to monitor radioactive gaseous effluent releases.

Such releases are monitored through the Unit vent monitor, ERS-1500. A Technical Specification change request will be initiated to remove this requirement for monitors ERS-1300 and ERS-1400.

Sincerely, ask W. G. Smi

, Jr.

Plant Manager WGS:frb cc: See attached distribution p

Q&

,)

8 8311220152 831114 PDR ADOCK 05000315 L

S PDR

c-

~

Mr. J. G. Keppler l

November 14, 1983 Page 2 of 2 cc: John E. Dolan M. P. Alexich R. F. Kroeger -

H. Brugger E. R. Swanson, R0:III R. C. Callen, MPSC G. Charnoff, Esq.

J. M. Hennigan R. O. Bruggee, EPRI INPO PNSRC J. F. Stietzel E. L. Townley Dir., IE (40 copies)

Dir., MIPC (4 copies)

~.

. _. _..