Telecopy Ao:On 750717,two of Four High Drywell Pressure Switches Tripped at Values Exceeding Tech Specs Limit. Two Switches Recalibr.Further Info to Be Provided in AO 50-265/75-20
ML20084S724
Person / Time
Site: Quad Cities Constellation icon.png
Issue date: 07/17/1975
From: Kalivianakis N
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20084S715 List:
References
NJK-75-362, NUDOCS 8306170183
Download: ML20084S724 (1)


Text

_ _ _ _ _ - _ _ _ _ _ __ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ __

/,C C:mm:nw alth Edisen

/ '* Quad Cities NucA Power Station /~'T

  • l (t' /*, . . . Cordosa,Ilknois 61242

/. Qi (p/. Post Off.cc Boxi

,i Tc!cphonc 309/654 2241 i

,E T,'A

/

NJK-75-362 /h gr ,\

Mr. C. Feierabend f Jl b Telecopy: Reglon iII, Attention:

5g-JUL221975 ;--

July 17, 1975 u. N'mt-a s.

r; w ~~

Kh ..s .;t j q, h1 swan ,

J. Keppler, Regional Di rector - gG Directorate of Regulatory Operations Ragion l11 ,

U. S. fluclear Regul'atory Commission 799 Roosevelt Road.

Glen Ellyn, Illinois 60137 Rafe rence : Quad-Ci ties Nuclear Power Statio-Docket No. 50-265, D?R-30 Appendix A, Sections 1.0.A.2, 3 1 Table 3.1.1, 6.6.B.l.a

Dear Mr. Keppler:

The purpose of this letter is to provide you with notification of an Abnormal Occurrence as required by Technical Specification 6.6.B.I.a within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br /> of the occurrence.

On July 17, 1975 while performing quarterly surveillance calibration of the "High Drywell Pressure Scram" pressure switches, two of the four switches tripped at values exceeding the Technical Specification L.C.O. PS-2-1001-88 B & C tripped at 2.05 psig while the L.C.0. is < 2.0 psig. The two switches were recalibrated and functionally tested. ,

1 This occurrence was discussed by telephone with Mr. Feierabend of your office ,

on July 17, 1975 Further information will be provided by Abnormal Occur- '

rence Report A0 50-265/75-20 which wi11 be submitted within 10 days of the d:te of this occurrence. . .

Vary truly yours ,

COMMONWEALTH EDIS0!! COMPANY QUAD-CITIES NUCLEAR POWER STATION .

/ ,

  • A f ' [ i.$ 4h.y/ ?

N. J. Kalivianakis t, Station Superintendent  ;

NJK/itAR/lk cc: Director of Of fice of Nuclear Reactor Regulation J. S. Abel q O