Telecopy Ao:On 750724,pressure Switch 1-1622B Found to Trip at Value Exceeding Tech Specs Limit.Switch Was Immediately Recalibr.Further Info to Be Provided in AO 50-254/75-18
ML20084S336
Person / Time
Site: Quad Cities 
Issue date: 07/28/1975
From: Kalivianakis N
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
Shared Package
ML20084S335 List:
References
NJK-75-380, NUDOCS 8306160692
Download: ML20084S336 (1)


Text

Y 4-Commo

' alth Edison '

i ' < nh Ouad. Cit octear Power Station A

El Post Othe x 216

\\.,/

/,'

Cordova,lihnom 01212

-f Tc!cphone 309/0E4-2241 NJ K-75-380 Telecopy:

Region 111, Attention:

fir. C. Feie rabend a

July 28.-1975 E

JUL3 0 n.(*

4 i

\\'A i

\\

t.

(hY J. Keppler, Regional Di rector g*/

Di rectorate of Regulatory Operations Region ill U. S. ~lluclear Regulatory Commission r

799 Roosevcit Road Glen Ellyn, Illinois 60137 l

Reference:

quad-Ci ties -iluclear Power Station Docket No. 50-254,.DPR-29 l

s Appendix A, Sections 1.0.A.2, 3.7.A.3.a, 6.6.B.I.a i

Dear fir. Keppler:

'l The purpose of this 1ctter is to provide you with notification of an Abr.ormal Occurrence as requi red by Techni cal Speci ficaticn 6.6.B. I.a within 24 hours2.777778e-4 days <br />0.00667 hours <br />3.968254e-5 weeks <br />9.132e-6 months <br />

[j of the occurrence.

At 3:00 p.m. on July 24, 1975 while performing routino quarterly surveillance on reactor building to suppression chamber vacuum breakers, pressure switch l-1622D was found to trip 0.0126 PSI -above the Technical Specification limit

[

a of 0.5 psid.

The switch was immediately recalibrated to trip at 0.451 psid.

I -

This occurrence was discussed by telephone with fir. Feierabend of your of fice j

on July 25,l1975 Further information will be prov'ided by Abnormal Occurrence Report A0 50-254/75-18 ~which will be submitted within 10 days of the date of this occurrence.

.s Very truly yours, COMf40NWEALTil EDISON C0liPANY QUAD-CITIES NUCLEAR POWER STATION Y