Interim Deficiency Rept M-49 Re Radiographic & Weld Defects in Sacrificial Shields,Containment Monorail & Vent Stack Welds.Analysis Reviewed.Corrective Actions Contingent Upon Lifting of NRC 821112 Show Cause Order
ML20071Q502
Person / Time
Site: Zimmer
Issue date: 06/01/1983
From: Williams J
CINCINNATI GAS & ELECTRIC CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
10CFR-050.55E, 10CFR-50.55E, 956C, LO2-83-37, LO7-83-37, LOZ-83-0037, LOZ-83-37, M-49, NUDOCS 8306090127
Download: ML20071Q502 (2)


Text

, -

---=====-a .a THE CINCINNATI GAS & ELECTRIC COMPANY dlF CINCIN N ATI,OHto 4 5201 June 1, 1983 LOZ-83-0037 J. WILLI AMS JR SUN 804 VICE PRESIDENT NUCLEA4 OPERATIONS Docket No. 50-358 U.S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, Illinois 60137 Attention: Mr. J.G. Keppler Regional Administrator Gentlemen:

RE: WM. H. ZIMMER NUCLEAR POWER STATION - UNIT 1 10CFR50. 55 (e) , ITEM M-49, RADIOGRAPHIC AND WELD DEFICIENCIES FOR SACRIFICIAL SHIELDS CONTAINMENT MONORAIL AND VENT STACK WELDS W.O. 57300, JOB E-5590, FILE NO. 956C, M-49 This letter constitutes an interim report concerning the subject conditions initially reported to the Commission on May 10, 1982 under the requirements of 10CFR50.55 (e) .

As stated in our previous report, QA-2272, dated February 23, 1983, certain unacceptable areas in the sacrificial shield welds were identified from the radiographic film review. These areas will be either repaired or accepted based on fracture mechanics analysis. The welds will also be brought up to the visual acceptance criteria of AWS D.l.1-1972, " Structural Welding Code" or the design will be adjusted to take no credit for weld areas not meeting this criteria.

The status of the reradiography of the welds on the Monorail and Vent Stack remains unchanged from our previous report.

Scheduling and completion of the corrective action is contingent upon the NRC release of the November 12, 1982 " Order to Show Cause and Order Immediately Suspending Construction" for work in this area. A schedule for completion of the corrective action will be submitted at that time.

8306090127 830601 DR.ADOCK05000pg8 3QUN 6 gg33 l

1 sia

6 - - --

g

- - -- ~ ~ ~ * - s+-- - *+ -+

s /

,)

+4 g /, ,

I

'i l

/-

i ,

f-

) ,

J Y, ' / ,

t <>

Mr. J.G. Keppler _

Regional Administrator .

June 1, 1983  !'

LOZ-83-0037 i Page 2 /

We trust the above will be found acceptable as an interim report under 10CFR50.55 (e) .

<- Very truly yours,

^

, , ~

_ THE CINCINNATI GAS & ELECTRIC COMPANY l s' d g g , 4 %'#

By 4[ : - .

. WILLIAMS, JR. ,

SENIOR VICE PRESIDENT cc: NRC Office of Inspection & Enforcement Washington, D.C. 20555 NRC SenioriResident Inspector '

ATTN: W.F. Christianson ,

NRC Zimmer-Project Inspector, Region III '

< ATTN: E.'R. Schweibinz i- "