ML20082H904
| ML20082H904 | |
| Person / Time | |
|---|---|
| Site: | Zimmer |
| Issue date: | 11/23/1983 |
| From: | Williams J CINCINNATI GAS & ELECTRIC CO. |
| To: | James Keppler NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III) |
| References | |
| 10CFR-050.55E, 10CFR-50.55E, LOZ-83-0228, LOZ-83-228, M-102, NUDOCS 8312010317 | |
| Download: ML20082H904 (2) | |
Text
a
^.,
_are.
TIIE CINCINNATI GAS & ELECTRIC COMPANY CINCINNATt, OHIO 45201 November 23, 1983 LOZ-83-0228 J. WILLIAMS, JR sanH)= wict Patssoant NUCLEAR OPERATIOces Docket No. 50-358 U.S. Nuclear Regulatory Commission Region III 799 Roosevelt Road Glen Ellyn, Illinois 60137 Attention:
Mr. J.G. Keppler Regional Administrator Gentlemen:
RE:
WM. H. ZIP 94ER NUCLEAR POWER STATION - UNIT 1 10CFR50. 55 (e ), ITEM M-102, FEEDWATER LINE SEISMIC ANALYSIS W.O.~57300, JOB E-5590, FILE NO. 956C, This letter constitutes an interim report concerning the subject condition reported to the Commission on October 28, 1983 as a reportable deficiency under 10CFR50.55(e).
The following constitutes the substance of our October 28, 1983 report:
The Main Steam Isolation Valve (MSIV) - Leakage Control System (LCS) is required to minimize the release of fission products after a LOCA.
As such, the system is designated Category I.
Portions of the Feedwater System are designated nonseismic and are in proximity to the MSIV-LCS system outside of containment.
The failure of these portions of the feedwater piping during a seismic event could adversely impact MSIV-LCS operation resulting in a release of radioactivity in excess of 10CFR100 limits.
Therefore, the Feedwater piping does not conforn to the design requirements of U.S. Nuclear Regulatory Guide 1.29 Position C.2 and is reportable under 10CFR50.55 (e).
Additional time is necessary to complete the evaluation.
A follow-up report will be submitted by February 24, 1984.
]
1 1E39 hfhy$)$
/
8312010317 831123 PDR ADOCK 05000358 S
PDR g g)
o w,
Mr. J.G. Keppler Regional Administrator November 23, 1983 LOZ-83-0228 Page 2 We trust the above will be found acceptable as an interim report under 10CFR50.55(e).
Very truly yours, THE CINCINNATI GAS & ELECTRIC COMPANY By Iff,IAMS,. 21:==,[
JR SENIOR VICE PRE IDENT DJS/sfr cc:
NRC Office of Inspection & Enforcement Washington, D.C.
20555 NRC Resident Site Supervisor ATTN:
W.M. Hill NRC Zimmer Project Inspector, Region III ATTN:
E. R. Schweibinz a
4
,-__,,.y_f
. _ _,. _,.,, _ ~ _.....
._-c.,
.,._,__.__.,,._.,,_n_
e._..-,
-v-
--- ~_,._ _.
,y-,.
_