Interim Deficiency Rept Re HPCS Diesel Generator Qualification Documentation.Initially Reported on 820805. Matter Under Investigation.Next Rept Expected by 821101
ML20065A508
Person / Time
Site: Nine Mile Point Constellation icon.png
Issue date: 08/31/1982
From: Manno S
NIAGARA MOHAWK POWER CORP.
To: Starostecki R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
10CFR-050.55E, 10CFR-50.55E, 82-484, NUDOCS 8209130245
Download: ML20065A508 (2)


Text

.

.. /

Ki? Y NIAGARA Nu MOHAWK Ni AGARA MOHAWK POWER CORPOf TAT 10N/300 ERIE BOULEVARD WEST, SYRACUSE, N.Y.13202/ TELEPHONE (315) 4741511 SAMUEL F. MANNO V8CE PRESIDENT.

NUCLE AR CONSTRUCTICN August 31, 1982 82-484 Office of Inspection and Enfortement Region I Attention Mr. R. W. Starostecki, Director

. Division of Project and Resident Programs U. S. Nuclear Regulatory Comission 631 Park Avenue King of Prussia, PA 19406 Re: Nine Mile Point - C'itn 2 Docket No. 50-410

Dear Mr. Starostecki:

Enclosed is an interim 30-day report in accordance with 10CFR50.55(e) for the potential deficiency regarding HPCS Diesel Generator Qualification documentation. This condition was reported by telephone conversation to Mr. W. Baunack of your staff on August 5,1982 as a potentially reportable deficiency.

Very truly yours, NIAGARA M0 HAWK POWER CORPORATION Samuel F. Manno Vice President

% clear Construction SFM/NLR: sam Enclosure xc: Director of Inspection and Enforcement

U.S. Wclear Regulatory Comission Washington, DC 20555 Mr. R. D. Schulz, Resident Inspector I

l _

B209130245 B20031 ppH ADOCK 05000 e

NIAGARA M0 HAWK POWER CDRPORATION WINE MILE POINT - UNIT 2 000(ET NO. 50-410 Interim Report for a Potentially Reportable Deficiency Under 10CFR50.55(e) Regarding HPCS Diesel Generator Qualification Documentation Description of Deficiency WPC conducted a QA review of the qualification documentation for the HPCS diesel generator system at GE-NEG in San Jose, CA, during the week of June 28, 1982. The following conditions were observed:

1. During the production test of the itigh Pmssure Core Spray (HPCS) diesel generator, the ambient temperature of 122*F (50*C) specified in the purchase specification data sheet, GE Document No. 21 A9236CB, was not attained. The ambient temperature during the testing did not exceed 96*F (35.5'C) at any time. Paragraphs 5.2.3.1 and 5.2.3.6 of IEEE 323-1971 require testing to the extren,es of service conditions.
2. The Vibration Test Data, requimd by GE Document No. 21 A9236, paragraph 5.1.1.b, to show the unit is free of excessive vibration during operation, was not included in the test report.
3. The test report does not include the following items required by IEEE 323-1971:
a. The variables to be measumd including accuracies (paragraph 5.2.3.2)
b. The number, type, and location of test monitors for each variable (paragraph 5.2.3.3)
c. The range, sequence, and combinations of environments to simulate the design basis event (paragraph 5.2.3.6)
d. Equipment mountings relative to performance (paragraph 5.2.3.7)
e. Cable connections and other mquimd appurtenances (paragraph 5.2.3.8)
f. Sumary, conclusions, and recommendations (paragraph 5.2.4.6)
4. Seismic analysis of the skid assembly does not clearly demonstrate

, operability of the assembly during and after a seismic event.

Although the analysis of the components covemd in the mports is comprehensive, there are apparent omissions. As an example, no analysis or justification for omitting the analysis for the starter solenoid valve is provided.

The matter is still under investigation. A final report will be submitted by November 1,1982.