Part 21 Rept 10CFR21-0047 Re Control Wiring Insulation of Inner Jacket Used on General Motors Diesel Generator Sets Identified as 999 or MP Series.Encl List of Owners of Units Notified
ML20247D301
Person / Time
Site: Beaver Valley, Monticello, Dresden, Browns Ferry, Nine Mile Point, Kewaunee, Point Beach, Oyster Creek, Prairie Island, Surry, North Anna, Turkey Point, Maine Yankee, 05000000, Fort Saint Vrain, Trojan
Issue date: 07/12/1989
From: Kulchak R
MORRISON-KNUDSEN CO., INC.
To: Murley T
Office of Nuclear Reactor Regulation
References
REF-PT21-89, REF-PT21-89-121-000 10CFR21-0047, 10CFR21-47, PT21-89-121, PT21-89-121-000, NUDOCS 8907250151
Download: ML20247D301 (7)


Text

_ _ - _ _ - _ - _ - - _ _ _ - _

MORRISON KNUDSEN CORPORATION

{

"fu's 4 om I? July 1989 S/N 10CFR21-89-3 Ref.

10CFR21-0047 Mr. Thomas Murley, Director Office of Nuclear Reactor Regulation 11555 Rockwell Pike Rockwell, Maryland 20852

Subject:

10CFR21 Reportable Defect Power Systems Division Reference No. 10CFR21-0047 Diesel Generator Units / Control Wiring Insulation - Inner Jacket

Dear Sir,

I have been advised by our power Systems Division of a Reportable 10CFR21 Finding regarding the Control Wiring Insulation Inner Jacket used on General Motors Diesel Generator Sets identified as the 999 or MP Series.

The attached report describes the reportable defect. We have notified the owners of these units of the reportable defect.

Additional information will be provided as it is received.

Very truly yours, Y-R. D. Kulchak Director - Quality Assurance 8907250151 890712 P

PDR ADOCK 05000010 S

PDC RK189:ed39/2 Attachment cc:

F. M. Adams H. W. Falter V.

Mitchell M.

Sharpe File l' t i

REPORTING OF 10CFR PART 21 POTENTfAL DEFECTS AND NONCOMPLIANCE l

..A ATTACHMENT 4.2 i

10CFR PART 21 APPLICABILITY EVALUATION FORM'

. MA;/n D u pe M ta e fst al-e 6 +1 DETZ1MINATICN OF PART 11 APF1.!CAJ!LITY PICCURf. MENT DOCUMNT N0 EMGNI $6fA.1(wt.#of tht%4. E4Mdf I EDII R10715IT20N ITDI NO$ -

Et4> Et4MCs.blidtL DI5C12F!!0N Covrht terets H6AAt ArreM GreAs, s.tTS A.

_bstuseton for f tese l

1.

!s the itas "Ceementisi Crade' Yes We

!! "TZ3,* ICCM, 21 l

does gge, apply a se to C.

If " U," go _to A2 2.

Is t.he iteet I

Procured to ASME Section 121 T

~ es No Resetor coolant Pressure Boundary

~

[Ta s [Ne No Irst class 1Z T.lactrical Tem

$nianit Catatory 1 Tes Ne

~

iialdir.g Ma ted al (AS P2)

Yes

~Ne Em Cora er Cere flalated

_Ts a

_N o p

If any " TIS

  • cheshed above,10 CTI 21 appliens se to C.

If all

  • NO," so to A.3.

!a the ita's being procured the asse as a tempista ceaponses, system, 3.

et structura listed in the plant c55C listi f

~ ee.

No 12

  • TIS.* 10 GT1 2.1 a pplie s go to C.

~

If "No,* 30 to A4 i

4 Vauld tha failun of the itse being procurid c.ause a bula cespesant tot to perform its requind sa.f aty functions

.es

. We 3.f "T23.* 10 CFA 11 appliasg go to C.

M "N0,* 10 CTR'Il does ses apply; go to C.

4.

baluation of fervi es-e

1.. If this is a repair servies, venid tha itas be.tes repaind be proested as a "Caesmettial Crade* itaaf Tes No 12 *TZd,"

10 Crt 11 does sat apply. Se te C.

If *Ide* se E 32.

2.

Comid the service belas procured cause a defect la a heela coopeeest et am the earrisse connected with the desism, inapesties, testing, er consalttag services iopertant to the safety that are associated with a basic composess.

,,,fe if "T13,* 10 CTA 21 applies.

If *NO," 10 CT1 21 d.Tes oes not apptyg to to C.

~

C.

10 Crt 11 Does Dess Not, apply.'

p haluated by W

^L-Cascurrence

,,gyga..

- t, - e...s..

Dasa'

~

De:e 2

  • cl

'T 1W A>OM N3SGnN>HJOSI8dOW 6P TT 68, 01 Tlf

8 PAGE 1 0F 5 w) MO.RRIS.O.N.-KNUDSEN COMPANY, INC.

! _E

)

$$N$NE$"i? $$MiWE,*E?"

~

r ut t'1'*H*)o Mk/PSD REQUEST NO. 10CFR21-0047 JULY 10, 1989 10CFR21 REPORTABLE DEFECT MK/PSD REFERENCE NO. 10CFR21-OO47

SUBJECT:

Diesel Generator Units d

Applied as Standby Power Suppliers for Nuclear Power j

Generating Stations DEFECT:

Degradation of control wiring insulation in the Engine (Fig. 2) and Generator Control Panels (Fig. 1) Turnished with models EMD645E4 - General Motors - diesel generator sets identified as the 999 or MP series.

These series utili=e an EMD A20 generator.

DISCUSSION:

Examination of the control wiring as reported by Bob Freeman of Growns Ferry has revealed that wires with a black insulation with a singlo yellow stripe (approx..010" wide) had experienced degre.dation of the insulation between the wire and outer Jacket.

The degraded insulation is cracked and tends to crumble when flexed.

The wire is approaching 25 years of age and the degradation appears to be age related.

The insulation on other Wiring in the panel does not appear to have degradation.

Other than the yellow stripe, there is no other identification.

The wire is #14A.WG. 19 Strand EMD P/N 82782 1.

RECOMMENDED CORRECTIVE ACTION:

The wire is in low voltage circuits and as long as the outer jacket remains intact, the inner insulation is contained.

The outer Jacket does not appear to have degraded.

As long as the outer jacket is intact, this inner insulation does not appear to pose en urgent probinm.

No electrical failures due to this insulation problem have been reported. However, it is recommended that owners of the EMD 999/MF types of diesel generators inspect this control wiring in the engine and generator cabinets.

The recommendation is that all control wire with black insulation containing the yellow strip be replaced at the earliest opportunity.

14AWG Nuclear grade SIS grede cen t rol wire is an acceptable replacemen t.

g.d

'3*H iW A>Od N35GnN>t-NOSI8 BOW 6p:1I 68, 01 W

REPORT NO.: 10CFR21-0047 DATE:

7/10/69 1

PAGE 2 0F S pf 9A T

O I

1 if,j MOR.R.IS.om.N-KNUD9EN COMPANY, INC.

i E nm er au Nuclear Plants Affected and Notified I m a "

  • a Browns Ferry Nuclear Plant has already completed 1

the corrective action.

This report shall be sent to all known Nuclear Plants with EMD 999 or MP I

Series Diesel Generator Sats.

The Nuclear Plants l

notified aret 1

MR. HUGO P. POMREHN i

BROWNS FERRY NUCLEAR PLANT

{

P.O. BOX 2000 DECATUR, ALABAMA 35601 MR. CHARLES E. LARSON NORTHERN STATES POWER 414 NICOLLET MALL MINNEAPOLIS, MN 55401

)

l 2

MR. JOHN KROEHLER JR.

NIAGARA MOHAWK POWER COMPANY 300 ERIE BOULEVARD WEST SYRACUSE, NY 13202' MR. AL ARRENDONDA TURKEY POINT NUCLEAR PLANT P.O. BOX 3088 FLORIDA CITY, FL 33034 MR. TOM COREY OYSTER CREEK NUCLEAR PLANT (GPU)

P.O.

BOX 389 FCRKED RIVER, NJ 08731 MR. DAVID CRUDEN VEPCO t

ONE JAMES RIVER PLAZA P.O.

BOX 26666 RICHMOND, VA 23261 i

MR. MIKE LEHR FORT ST. VRAIN 16805 WELD CITY ROAD PLATTEVILLE, CD S0651 MR. JACK CAREY DUQUESNE LIGHT COMPANY (BEAVER VALLEY)

ONE OXFORD CENTRE 301 GRANT STREET IITTSDURGH, PA 15279 p.d 3 N IW A>od N35GnN>l-NOSI880W OS:TT 68, OT W

REPORT NO.: 10CFR21-0047 DATE:

7/10/89 PAGE 3 0F 5 s.,

k,ff,f.) rowenennusemenon KNUDSEN COMPANY, INC.

MORRISON

%.;g.

E_

1 MR. E. T. BOULETTE MAINE YANKEE 1,.L.....

BAILEY POINT - FERRY ROAD WISCASSET, ME 04578 l

MR.

J. J.

ZACH l

POINT BEACH NUCLEAR PLANT 6610 NUCLEAR ROAD TWO CREEKS, WI 54241 MR. KEN EVERS l

KEWANEE NUCLEAR STATION i

HWAY 42 (RT. 1) BOX 49 KEWANEE, WI 54216 MR. ED NEPZEL DRESDEN NUCLEAR PLANT RURAL ROUTE 1 MORRIS, IL 60450 If furthur assistance is required to assist in the resolution of this notice, contact me at 919-977-2720.

4 sess.se.oroes,!%

k...$

US

,'t Y_

arry Falter, PE 7023

[

g j Principal Engineer

\\l 1033 l '@lo -Ef

'1..til...f i

g.,

m u w ma mwam w n m W

_ _ _ _ _ _ _ _ _ -. - - - - ~ - - ~ - -

REPORT.NO.: CFR21-0047 ELECTRICAL C0hTROL CABINET DATE:

7/10/89 pAGE 4 of 5 e

s0 58 94 39 4

2 28 15 27 g4]

95 i

57 n

i it 1

36 69 ij'%3RNjA#P~skEE 6 33 '

' i 4

s

!!JbtINTW J;

16%

  • -mD I -.-
  1. )

[kN

?%

,,d 38 I

NN~),.

54 29

("-

59

? % ]~Y N "

HM,,N I WE^d0 n,

~

s 7 -

g^

27 2n p//7 8

i g \\x w

./

^

3 I

/ //

[i i!

\\D k

!2!~

\\

^\\l 3

33 7

17 27 31 17 -

27 54 6

25 26

- 33

~ff j

i i

Front View of CsHnet I

Doors Shown Open Ref. No.1 i

GENERATOR CONTROL CABINET Rer"Opty FIG. 1 9.g i

'3*H M AM3d M MM M ddW E W

  • MN

.I

_ _ - - - ~

DATE:

7/10/89 Part No-PAGE 5 0F 5 i

Number Re9-Description l

A B

CABINET EQUIPPED.. Engine contrri

~'

s/

8411519 2

2 SWITCH Pressure. Air. API, AP2 108 8342488 3

3 SWITCH... Pressure High fuel, NFPl. MFP2 - Main bearing MB2 SWITCH.. Pressure Raw water RWS

  • 109 8341873 1
  • 110 8411520 3

2' SWITCH Pressure. Low wster 1.WS Main bearing MB1, MB3 l

  • 111 133784 18 14 SCREW.. Switch mounting 1/4 20 x 11/2 flat head
  • 112 116436 14 13 CONNECTOR.. Flared tube '- 1/4 tube x 1/4 M.P.T, i
  • 113 8040347 6

6 E1. BOW.. Flared tube. 900 1/4 tube x 1/4 F.P.T.

  • 114 116453 8

7 ELBOW.. Flared tube. 900 1/4 tube x 1/4 M.P.T.

  • 115 8098593 A.R. -

TUBING 1/4 in. O.D. x.028 copper brand steel Sold per foot

  • 116 116452 A.R.

NUT.. Tubing.1/4 in.

  • 117

!!6561 1

TEE.1/4 tube x I/4 tube x 1/8 M.P.T.

  • 118 8394665 1

FLANGE.. Tube connector

  • !19 8342568 1

RING.. Rubber. 494 !.D. x.629 0.D.

  • 120 8246073 4

FLASHING. 21/2 x 11/4 x 16 ss.

1

'2 GROMMET.. Rubber 1

  • 123 144226 l

gh]

92 y

=

m 96 3

\\ D D {.

f ss O

-92 dy y-xs 3,

M,

r *7 75

N dd q

' M N h j k [7 r a

  • p f-"

=

j en y

l 67 I4 V,,._ioi gg2 y

%F U

v g

fh"

'e 13 i

+,

4 16_ __ /

i1 e m 95 A

k

\\

65 10 2 N

}

NY es,

/

_/g,

/t 3,

46 4

I ass 77 4

A 94 34

-45 10 3 l[

}-

I 41 l

SECTioN A A g-~ f' ' y.gp y 4,

50 r.

-40 g,

l$

2-3 63 l

,q ENGINE CONTROL PANEL f(sg avt,y FIG. 2 I

4*d

'D*H IN A>OW IGSGnN>t-NOSIMdOW ES:TT 68, OT " int

<