Rev to Part 21 Rept Re Potential Problem W/Master Power Connecting Rods.Vendor Recommends Listed Utils Perform Visual Insp of Master Rods to Determine Applicability of Rept
ML20078G305
Person / Time
Site: Nine Mile Point, Palo Verde, Braidwood, Waterford  
Issue date: 11/09/1994
From: Schneider J
COOPER ENERGY SERVICES
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
REF-PT21-94 QCG-9995, NUDOCS 9411150598
Download: ML20078G305 (3)


Text

.\\

Cooper industries 1

Cooper Bessemer -

Reciproceting Products Divisisn 150 Lincoln Avenue Grove City, PA 16127 1898 412 458-8000 November 9,1994 COOPER Our Ref: OCG-9995 Document Control Desk U.S. Nuclear Regulatory Commission Washington, D.C. 20555

Subject:

10 CFR Part 21 Report Revision Master Power Connecting Rod

Dear Sir:

On January 12,1987 Cooper Bessemer Reciprocating Products Division of Cooper Industries reported a potential problem with the master power connecting rod (KSV 2A#1) utilized in Cooper Bessemer "KSV" Emergency Diesel Generators. The report was identified as OCG-3364, and described master rod failure due to an iron plating repair.

On November 3,1994, Commonwealth Edison Company (CECO) Braidwood -Station experienced a master rod failure in the 2B diesel (Engine S/N 7180, Rod S/N 8H2214).

Examination of the master rod indicated a failure mode similar to that described in the 1987 report.

The purpose of this letter is to report additional affected items. A review of in-house records was conducted and identified 4 affected master rods in addition to those reported in 1987. These 4 rods all bear 8H22XX series serial numbers. Due to the manufacturing practices in use in the 70's when these master rods were produced, the affected rods are identifiable by a production order number. The suspect numbers are 106-2, 106-6,106-10, and 106-11.

Cooper recommends that the utilities listed below perform visual inspection of the master rods to determine applicability of this report. This may be conducted in the installed state.

SUMMARY

P/N:

KSV-4-2A#1

==

Description:==

Master Power Connecting Rod Potential Serial Numbers:

8H2204, 5, 6, 7, 8, 9,10,11,12,13,15,16 Affected Production Numbers:

106-2,106-6,106-10,106-11 Notes:

1]

Only master rods with matching production numbers and serial numbers are affected (4 total).

2]

Master rods will also bear forging numbers identified with a "CA (i.e.

CA150).

I 9411150598 941109 PDR ADOCK 05000440 g

PDR

/ /k b

Cooper Bessemer *

  • Enterprise *
  • Penn*

i 1

~'

P g3 2 QCG-9995 November 9,1994 l

Affected Utilities / Station Location Utility / Station Engine S/N-Master Rod S/N (crankshaft Throw)

Remarks CECO, Braidwood 7179 8H2207

  1. 3

. Original Build 8H2205

  1. 5 Original Build 8H2213
  1. 10 Original Build 7180 8H2210
  1. 2 Original Build APS/Palo Verde Spares 7186 8H2206 Spare Fumished as a Spare 8H2216 Spare Fumished as a Spare l

Ni-Mo/NMP2 7191 8H2212

  1. 1 Original Build 8H2209
  1. 2 Original Build 8H2204
  1. 3 Original Build 8H2211
  1. 8 Original Build Entergy, Waterford 3 Spare Parts 8H2208

. Ref. LP&L P.O.

8H2215 L14200D If you have any questions conceming this matter, please contact John M. Home, Manager, Nuclear and Analytical Engineering at 412-458-3543, or John R. Schneider, Manager, Quality Assurance at 412-458-3434.

Sincere!

t I

c neider Manager, Quality Assurance Copy To:

J. D. Mowery - CES/GC B. R. Sedelmyer - CES/GC A. D. Gillette - CES/GC D. T. Blizzard - CES/GC J. M. Home - CES/GC I

File: K5fa10 Rev.1 i

/kil L

i

P:ge 3

, j.

OCG-9995 November 9,1994 i

  • cc:

Walter Haass - NRC One White Flint North Mailstop 9D4 Washington, DC 20555 1

Mr. Michael Kneble Entergy Operations Waterford 3 SES, Highway 18 Taft, LA 70006 Mr. Dwain Lambert Commonwealth Edison Co.

Braidwood Nuclear Power Station Route 1, Box 81 Braceville, IL 60407 Mr. Teny O'Brien Commonwealth Edison Co.

1400 Opus Place Downers Grove, IL 60515 Mr. Lenny Schiavone Niagara Mohawk Power Corp.

301 Plainfield Road North Syracuse, NY 13212 Ms. Kathleen Russo Niagara Mohawk Power Corp.

Nine Mile Road - Unit 2 P. O. Box 63 Lycoming, NY 13093 Mr. Neil Thibodaux Arizona Public Service Palo Verde Nuclear Generating Station P. O. Box 52034 Mail Station 7566 Phoeniz, AZ 85072-2034 Mr. Thomas Bradish Manager, Nuclear Regulatory Affairs Arizona Public Service P. O. Box 52034 Mail Station 7636 Phoeniz, AZ 85072-2034 Mr. Arthur G. Killinger MPR Associates, Inc.

320 King Street Alexandria, VA 22314-3238 L