ML20215M542

From kanterella
Jump to navigation Jump to search
Final Deficiency Rept (55(e)-86-09) Re Borg Warner electro- Hydraulic Actuator Oil Leak on Dc Motor.Initially Reported on 860516.Valves Returned to Mfg & Rebuilt to Include New Seals & Qualified Pao Hydraulic Fluid
ML20215M542
Person / Time
Site: Nine Mile Point 
Issue date: 06/16/1986
From: Mangan C
NIAGARA MOHAWK POWER CORP.
To: Starostecki R
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION I)
References
(55(E)-86-09), (55(E)-86-9), (NMP2L-0751), (NMP2L-751), NUDOCS 8611030012
Download: ML20215M542 (2)


Text

i-F V

l cD o

o Y NIAGARA NuMOHAWK NIAGARA MOHAWK POWER CORPORATION /300 ERIE BOULEVARD WEST. SYRACUSE, N.Y.13202/ TELEPHONE (315) 474-1511 June 16, 1986 (NMP2L 0751) l Mr. R. W. Starostecki, Director U.S. Nuclear Regulatory Commission Region I Division of Reactor Projects 631 Park Avenue King of Prussia, PA 19406 Re: Nine Mile Point - Unit 2 Docket No. 50-410

Dear Mr. Starostecki:

Enclosed is a final report, in accordance with 10CFR50.55(e), for the problem concerning hydraulic fluid leakage on the DC motor of Borg Warner actuators.

This problem was reported via tele-con to Mr.

J.

Linville of your staf f on May 16,1986.

Very truly yours, C. V. Mangan Senior Vice President CVM/GG/cla i

(1622H) xc:

Director of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, DC 20555 R. A. Gramm, NRC Senior Resident Inspector NMPC Project File 8611030012 860616 PDR ADOCK 05000410 PDR S

1 I

., j r

O s

s G

V NIAGARA M0 HAWK POWER CORPORATION NINE MILE POINT - UNIT 2 DOCKET NO. 50-410 Final Report for a Problem Concerning Borg Warner Electro Hydraulic Actuator 011 Leak On The D. C. Motor (55(e) 09)

Description of the Problem The problem concerns leakage of hydraulic fluid on the D.

C. motor of one actuator described in Specification NMP2 C051M.

This actuator was the only one filled with hydraulic fluid when the leak was detected.

Inspection of this actuator showed significant leakage from the pump seal, allowing oil to saturate the D.C. motor.

The oil on the D.C. motor could cause malfunction of the unit.

The actuator problem affects valves 2HVK*TV21A and B, 22A and B, 2ICS*PCVil5, 2SWP*TV35A and B which were procured undEr Specification NMP2 C051M and which are located in the control building chilled water, reactor core isolation ct,oling and service water systems.

Other valves procured f rom Clow Corporation under Specification NMP2 P304Y which also have Borg Warner actuators are a different design and therefore, are not subject to this problem.

Analysis of Safety Implications 011 saturation of the D.

C. motors on the above mentioned actuators could result in improper operation of their associated system which, if uncorrected, could have adversely affected the safety of operations of the plant.

Corrective Action The seven affected valves mentioned above have been returned to the manufacturer and have been rebuilt to include new seals and qualified PA0 hydraulic fluid.

The subject valves have been re-installed with the motor-pump units in the actuators reoriented.

_ _ -. _