22001 hrthpa:L Drnr Kingwmni,lexas 7733MN01 Tel: 713/348-1000 l'n: 713/348-1283 THIS IS A 10CFR PART 21 NOTIFICATION November 17,1993 Nuclear Regulatory Commission Document Control Desk Washington, D.C. 20555
Subject:
Westronics Recorders - Model 2100C A recent Electromagnetic Interference susceptibility test conducted on a representative sample of Westronics Series 2100C recorders indicated that the recorder was susceptible to interference caused by a radiated field strength of 10 V/m as defined by SAMA Standard PMC 33.1, Class 2.
The recorder was not susceptible to Class 1 radiation level of 3 V/m.
The following failure modes may be exhibited by the recorders in service:
1.
There are momentary changes in the displayed and/or trended values.
Recorder continues to function properly otherwise.
2.
Recorder CPU experiences a reset.
Following the reset, the recorder continues to function properly.
- 3. The recorder fails to respond to changes in the input signals.
Displayed and trended values of the input signals remain at a constant value.
There is no automatic recovery until the recorder is manually reset or recorder power is turned off and back on.
l 4.
The recorder locks up.
There is no automatic recovery until the recorder is manually reset or recorder power is turned off and back on.
i 060021 1
/$ h I
9312090309 931117
~
'/'f(
/
PDR ADOCK 05000155 S
PDR g
g lmAxxxi uess N]Md7 Houston AUas-Westronics-l
i i
PAGE 2 10CFR21 2100C l
11/17/93 i
The interference path was traced to the Signal Input Transition printed circuit board assembly, Westronics part number CB100256C01.
The subject circuit board assembly has been redesigned to improve the recorder's immunity to electromagnetic interference, and preliminary tests have indicated that the recorder i
will be able to meet the requirements of the referenced standard.
l The new printed circuit board assembly may be obtained by contacting Recorder Service f
Department of EmiroTe-ch Controls, Inc. at 1-800-433-2184.
-l Attached is a list of affected recorders and their locations as indicated in our records.
For further information, please contact the undersigned, or Chris Kelly, Quality Assurance Engineer, at 713-348-1000.
i Sincerely, ENVIROTECH CONTROIS INCORPORATED
$ [ Lb ~
\\
Homayoun Hadi Quality Assurance Manager l
~
Attachment 1
l
'i
10CFR PART 21 NOTIFICATION LIST OF AFFECTED RECORDERS AND THEIR LOCATIONS NIAGARA MOHAWK POWER NINE MILE POINT, UNIT 2 LAKE ROAD LYCOMING, NEW YORK 13093 SERIAL #: 2100C1682 2100C1683 2100C1684 2100C1685 2100C1686 2100C1687 NORTHEAST NUCLEAR ENERGY NORTHEAST UTILITIES SERVICE CO.
P. O. BOX 270 HARTFORD, CONNECTICUT 06141-0270 SERIAL #: 2100C1027 2100C1028 2100C1029 PHILADELPHIA ELECTRIC COMPANY P. O. BOX 195 WAYNE, PENNSYLVANIA 19087 SERIAL #: 2100C1688 2100C1689 2100C1590 2100C1691 2100C1692 2100C1693 2100C1694 UNION FENOSA JOSE CABRERA NUCLEAR PLANT CAPITAN HAYA,53 28020 M ADRID, SPAIN SERIAL #: 2100C1711 2100C1712
.~
10CFR PART 21 NOTIFICATION LIST OF AFFECTED RECORDERS AND THEIR LOCATIONS ARKANSAS NUCLEAR ONE CONSUMERS POWER COMPANY ROUTE 3, BOX 137G, S. JUNCTION BIG ROCK NUCLEAR PLANT OF HWYS U.S. 64W & ARK. 333 S 10269 U.S. 31 NORTH RUSSELLVILLE, ARKANSAS 72801 CHARLEVIOX, MICHIGAN 49720 SERIAL #: 2100C1002 SERIAL #: 2100C1005 2100C1003 2100C1006 2100C1004 2100C1007 COMISION FEDERAL DE ELECTRICIDAD DETROIT EDISON MELCHOR OCAMPO NO. 463 90 PISO NUCLEAR ENGINEERING (ETS)
COL ANZURES, MEXICO D.F.
6400 NORTH DIXIE HIGHWAY NEWPORT, MICHIGAN 48166 SERIAL #: 2100C1030 l
2100C1031 SERIAL #: 2100C1001 2100C1032 2100C1025 2100C1033 2100C1026 2100C1034 2100C1713 2100C1035 2100C1036 FLORIDA POWER & LIGHT COMPANY 2100C1037 P. O. BOX 14000 2100C1038 JUNO BEACH, FLORIDA 33408 2100C1039 2100C1040 SERIAL #: 2100C1008 2100C1700 1
2100C1041 2100C1009 2100C1701 2100C1042 2100C1010 2100C1707 2100C1043 2100C1011 2100C1708 2100C1044 2100C1012 2100C1709 2100C1045 2100C1013 2109C1710 2100C1046 2100C1014 2100C1047 2100C1015 2100C1048 2100C1016 2100C1049 2100C1017 2100C1050 2100C1663 2100C1702 2100C1664 2100C1703 2100C1665 2100C1704 2100C1666 2100C1705 2100C1667 2100C1706 2100C1668 i
2100C1715 2100C1669
.