IR 05000324/1987033

From kanterella
Jump to navigation Jump to search
Insp Repts 50-324/87-33 & 50-325/87-34 on 870921-25.No Violations or Deviations Noted.Major Areas Inspected: Emergency Preparedness
ML20236B449
Person / Time
Site: Brunswick  Duke Energy icon.png
Issue date: 10/14/1987
From: Decker T, Sartor W
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION II)
To:
Shared Package
ML20236B446 List:
References
50-324-87-33, 50-325-87-34, NUDOCS 8710260188
Download: ML20236B449 (5)


Text

_ _ - _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ . _-._

r UNITED STATES p ~p Afog% #

. NUCLEAR REGULATORY COMMISSION

{

g

,

j REGION ll 101 MARIETTA STREET,N * r ATLANTA, GEORGI A 30323

%, * * * s / DCI 161987 l Report No.: 50-325/87-34 and 50-324/87-33 Licensee: Carolina Power and Light Company P. O. Box 1551 Raleigh, NC 27602 Docket Nos.: 50-325 and 50-324 License Nos. DPR-71 and DPR-62 Facility Name: Brunswick Inspection Conducted: Sept ber 21-25, 1987 Inspector: /N(

W. M. Sartor J //)-/O8[

Date Signed f-Approved by: [4V/g#//, /O-/Y-87 T. R. Decker, Section Chief Date Signed Division of Radiation Safety and Safeguards SUMMARY Scope: This routine, unannounced inspection was conducted in the area of emergency preparednes Results: No violations or deviations were identifie ADOCK OG hPDR $24-PDR G

_ - _ _ - _ - _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

.. . _ _ .

- . , _ _ _

- . - . .

F REPORT DETAILS'-

' Persons Contacted l

Licensee. Employees

  • G. 'Dorosko, Administrative Supervisor
  • J.- 0'Sullivan, Manager, Maintenance <
. *C. F. Blackmon, Jr. 0perations/ Supervisor

.

.

E *J.-.A. Sm1th, Director, Administration- ]

  • C. R. Dietz, General Manager  !
  • A. G. Cheatham, Manager, Environmental and Radiochemistry 1
  • R. E. Helme,. Director, ONS .

!

  • J. . W. Moyer,- Manager, , Training l
  • W.: J. Dorman, QA Supervisor  :
  • E. R. Eckstein', Manager, Technical Support l
  • J.LM. Brown,; Resident' Engineer 1 Other' licensee employees contacted included engineers, technicians, operators, security office members,l and office personne ..

NRC Resident Inspectors

~ *W..Ruland

'L., Garner

  • Attended' exit interview - Exit Interview A The inspection scope and findings were summarized on September 25, 1987, with those. persons ' indicated in Paragraph 1 abov The inspector described the areas inspected and discussed in detail ~ the inspection i findings' listed below. No . dissenting comments were received from the l licensee. The licensee did not identify as proprietary any of the l material provided to or reviewed by the inspector during this inspectio ! Licensee Action on Previous Enforcement Matters

.This subject was not addressed in the inspectio .. Emergency Detection and Classification (82201)

.i Pursuant to 10 CFR 50.47(b)(4); 10 CFR Part 50, Appendix E, Sections I l and IV.C; and the licensee's Emergency Plan, this program area was j inspected to determine whether the licensee used and understood a standard '

emergency classification and action level schem The inspector reviewed the licensee's classification procedures. The l event classifications in the procedures appeared consistent with those i

-_:_ 2 :__ _

- __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . - - _ - _ .

____,

I,

i required by regulation and the Emergency Pla Selected emergency action f levels (EALs) specified in the classification procedures were reviewe The reviewed EALs appeared to be consistent with the initiating events specified in Appendix 1 of NUREG-0654 and the Emergency Plan, j The inspector verified that the licensee's notification procedures i included criteria for initiation of offsite. notifications and for development of protective action recommendation The notification procedures required that offsite notifications be made promptly after declaration of an emergenc The inspector discussed with licensee representatives the coordination of EALs with State and local official Licensee documentation showed that the. licensee had discussed the EALs during June / July 1987, with State and

"

local officials, and that these officials agreed with the EALs used by the license The _ responsibility and authority for classification of emergency events and initiation of emergency action were prescribed in licensee procedures and in the Emergency Plan. The Shift Operating Supervisor was interviewed and he understood his responsibilities and authorities in rei6 Mon to accident classification, notification, and protective action recommendation No violations or deviations were identifie . Protective Action Decision-making (82202)

Pursuant to 10 CFR 50.47(b)(9) and (10); 10 CFR Part 50, Appendix E, ,

Section IV.D.3; and the licensee's Emergency Plan, this area was inspected to determine whether the licensee had 24-hour-per-day capability to assess '

and analyze emergency conditions and make recommendations to protect the i public and onsite workers, and whether offsite officials had the authority and capability to initiate prompt protective action for the publi The inspector discussed responsibility and authority for protective action decision-making with licensee representatives and reviewed pertinent portions of the licensee's Emergency Plan and procedures. The plan and  ;

procedures clearly assigned responsibility and authority for accident i assessment and protective action decision-makin ]

The capability of offsite officials to make protective action decisions j and to promptly notify the public was discussed with licensee i representative Licensee procedures made provisions for contacting j responsible offsite authorities on a 24-hour basi Backup communication l links with offsite authorities were availabl The inspector j l independently confirmed that offsite decision-makers with authority for j emergency response activities could be contacted by making a telephone l

call to the State Warning Point, Brunswick County Warning Point, New l l Hanover County Warning Point, and the Coast Guard from the Control Room -

'

using the selective signaling telephone syste !

_ - - - - - - 1

__

!. .

!-

No violations or deviations were identifie . Knowledge and Performance of Duties (Training) (82206)

Pursuant to 10CFR50.47(b)(15) and 10 CFR Part 50, Appendix E, Section IV.F, this area was inspected to determine whether emergency response personnel understood their emergency response roles and could perform their assigned function The inspector reviewed the description (in the Emergency Plan) of the training program, training procedures, and selected lesson plans, and interviewed members of the training staff. Based on these reviews and interviews, the inspector determined that the licensee had an emergency training progrcm, but found it difficult to determine the quantitative and qualitative requirements of the program. This was discussed in detail both before and during the exit interview with key licensee personnel. The inconsistencies in the requirements of EP training from that documented in the Emergency Plan and PEP 04.3 versus the training actually being conducted for some members of the emergency organization (specified alternates to the Dose Projection Team Leader were used as examples) was discussed in detail. The licensee provided~ docanentation of how the emergency training was being reviewed for needed improvement and that the formal classroom training being conducted was actually a part of this j improvement progra Based on the licensee's commitment to continue improving and better documenting the emergency training program, the {

inspector identified the training inconsistencies as an inspector followup item (50-325/87-34-01,50-324/87-33-01). 4 No violations or deviations were identifie . LicenseeAudits(82210)

Pursuant to 10 CFR 50.47(b)(14) and (16) and 10 CFR 50.54(t), this area was inspected to determine whether the licensee had performed an independent review or audit of the emergency preparedness progra Records of audits of the program were reviewed. The records showed that independent audits of the program were conducted by the corporate Quality Assurance Department on August 25-29, 1986, and August 24-28, 1987, and documented in Report Nos. QAA/0021-86-07 and QAA/0021-87-07, respectivel These audits fulfilled the 12-month frequency for such audits. The inspector noted that the 1986 audit report did not include an evaluation for adequacy of interfaces with State and local governments. When the inspector requested this information from the licensee, he was provided a preliminary finding of the 1987 audit report (the final 1987 audit report was faxed to the site during the week of the inspection). The finding ;

was: "none of the six audits conducted by CQA prior to 1987 addresses the )

adequacy of the licensee State and local government interface." The !

inspector stated this failure to perform an evaluation for adequacy of '

interfaces with State and local governments as required by 10 CFR 50.54(t)

would not be reported as a violation in accordance with the provisions of i

_ _ _ _ _ _ _ _ _ i

_ -- _ _ - - _ _ _ _ _ _ _ . _ _ - - . - _ _ - . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

.

,

[

L

,

10 CFR 2, Appendix'C, Se'ction V.A, which. encourages and supports licensee initiative for self-identification and correction of problem The .

licensee committed to assuring' that the finding be investigated and to

'

take necessary: corrective: actio .

Inspector Followup. ' Item 50-325/87-34-02,. 50-324/87-33-02, Licensee

- identified failure to ' perform an evaluation of. the adequacy of interface between licenseeL and : State and local government ' in accordance with

'

10 CFR 50.54(t). '

No violations or deviations were identifie . InspectorFollowup(92701)

. (Closed) Inspector Followup Item (IFI) 50-325/81-26-07: Identify OSC areas of rooms in the service buildin The -inspector reviewed Section 3.2.1.1 of Plant . Emergency Procedure 02.6.12, Operations Support Center Leader) which provided - for the lunchroom of the service building as the mustering are (Closed) IFI 50-325/81-26-11: Improve EOF habitability per

.NUREG-069 The E0F constructed since the EP Appraisal has.the same habitab.ility as the Control Roo (Closed) IFI - 50-325/81-26-40: Revise information procedures to identify a program for familiarization of the news medi ~

The licensee conducts an Annual Media Day and/or mails out informatio (Closed) nIFI 50-325, 324/87-23-02: Correction of discrepancy in PEP 2.6.2.1 concerning who has the responsibility for making NRC notifications. The inspector reviewed the revised procedure dated September 20, 1987, which corrects this ite _ _ , _ _ . - - - - _ _ _ - - - - _ - _ - _ - _ - _ - _ _