42
After discussions with the licensee. CR 97-04103 was issued to track the
failure to provide the results of fire door evaluations in the FHA.
This t/SAR discrepancy was identified by the inspector and is discussed
in Sec ion F2.4.
A review of the surveillance ins)ection and testing procedures for fire
doors was perfcrmed to confirm tlat the licensee specified fire door
clearance acce)tance criteria was in accordance with the guidance of
National Fire 3rotection Association (NFPA) 80. Standard for Fire Door <,
and Fire Windows. On December 10. 1997, the inspector observed ongoing
door replacement and repair activities for fire doors in the DG
buildirg.
No discrepancies were identified.
c.
Conclusions
The inspector concluded that fire door surveillance procedures and
acceptance criteria for verification of fire door clearances were in
accordance with NFPA guidance.
However, a UFSAR discrepancy associated
l
documentation of fire door and frame evaluations was identified.
F2.4 UFSAR Review
A recent discovery of.a licensee o>erating tLa facility in a manner
contrary to the UFSAR description -ighlighted the need for a special
focused review that compares plant practices procedures, and/or
parameters to the UFSAR des.' > iptions. While performing the inspections
discussed in this reoort
.e inspector reviewed the applicable portions
of the UFSAR that relatec *. the areas inspected.
The inspector
verified that the UFSAR wording was consistent with the observed plant
practices, procedures, and/or parameters.
The inspector reviewed UFSAR Section 9.5.1.4.3.4.b. Fire Doors as part
of the fire protection program review activities.
An int insistency was
noted in ; hat the licensee failed to document the results of evaluations
of fire doors and frames in the FHA. which is section 9.5.1.5 of the
This issue is discussed in Section F2.3.
This item will be
identified as part of URI 50-325(324)/97-13-05. UFSAR Discrepancy Fire
Doors.
F3
Fire Protection Procedures and Documentation
F3.1 Fire Protection Procedures
a.
InSDeCtion SCoDe (64704)
The inspector evaluated the adequacy and implementation of the
licensee's Fire Protection Program described in the UFSAR and in Plant
Operating Manual Fire Protection Procedure OPLP-01. Revision 6. Fire
Protection Program Document.
In addition. a comparison was made of the
program to selected NRC Safety Evaluation Reports which ap3 roved the
station fire protection program.
The inspector reviewed t1e following
procedures for compliance with the NRC requirements and guidelines: