ML20147C120

From kanterella
Revision as of 11:57, 25 June 2020 by StriderTol (talk | contribs) (StriderTol Bot insert)
(diff) ← Older revision | Latest revision (diff) | Newer revision → (diff)
Jump to navigation Jump to search
Proposes Alternate Mod of Paragraphs 3.1.34(2) & 5.17.6(2) of Fire Protection SER Attached to Amend 19 of License DPR-54.Would Relocate Transformer 250 Ft East of Current Location
ML20147C120
Person / Time
Site: Rancho Seco
Issue date: 12/12/1978
From: Mattimoe J
SACRAMENTO MUNICIPAL UTILITY DISTRICT
To: Reid R
Office of Nuclear Reactor Regulation
References
NUDOCS 7812180159
Download: ML20147C120 (1)


Text

c

$SMUD SACRAMENTO MUNiclPAL UTILITY olSTRICT O 6201 s street, Box 15830, sacramento, California 95813; (916) 452 3211 December 12, 1978 Director of Nuclear Reactor Regulation Attention: Mr. Robert W. Reid, Chief Operating Reactors, Branch 4 U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Docket No. 50-312 Rancho Seco Nuclear Generating Station, Unit No. 1

Dear Mr. Reid:

Paragraphs 3.1.34(2) and 5.17.6(2) of the Fire Protection )

Safety Evaluation Report attached to Amendment No.19 to Facility Operating License No. DPR-54 for the Rancho Seco Nuclear Generating l Station, Unit No.1 require that the small oil filled transformer ,

adjacent to the emergency air lock be replaced with a dry type l transformer. l However, the District has decided a better modification l would be to move the transformer from the fence yard area. The  !

District proposes to move the transformer to a location approximately 250 feet east of its present location and, consequently, approximately the same distance from any equipment required for safe shutdown and cooldown. In this location, it can pose no hazard. Therefore, the  !

District requests that Paragraph 3.1.34(2) be rewritten to state:

l "Relo. ate the small oil filled transformer adjacent .

to the emergency air lock to a location where it is i not a fire hazard to equipment required for safe l shutdown and cooldown." ,

It is also requested that Paragraph 5.17.6(2) be modified to state:  !

. . . (2) relocate the small oil filled transformer exposing the nuclear service cooling water pumps to a location where it cannot present a fire exposure to equipment required for safe s iutdown and cooldown."  ;

Sincerely yours, ll b12bNA J. J. Mattimoe  !

Assistant General Manager and Chief Engineer 6% f  ;

7812180IN r.. l a n u n,c n n o, som ma nm um a nu mo m mmm I- i i

i