Special Rept,Rev 1:updates 871027 Rept Re Violation of Tech Specs.Caused by Inoperability of Smoke Detectors for More than 14 Days Due Undetermined Operability Due to Temps Below 32 F.Replacement Expected to Be Completed by Feb 1988
ML20236R573
Person / Time
Site: Trojan File:Portland General Electric icon.png
Issue date: 11/18/1987
From: Olmstead C
PORTLAND GENERAL ELECTRIC CO.
To:
NRC OFFICE OF ADMINISTRATION & RESOURCES MANAGEMENT (ARM)
References
CAO-418-87, NUDOCS 8711230364
Download: ML20236R573 (1)


Text

-

)

mem see

.l hj November. 18, 19871 Portland General Electric Company 'CAO-418-87 '

Trojan Nuclear Plant 71760 Columbia River Ilwy Rainier, Oregon 97048 (503) $56-3713  :

U.S. Nuclear Regulatory Commission 4 Document Control Desk Washington, D. C. 20555-Gentlemen: 3

l Special Report, Revision 1 '

1 i

I l This Special Report revises the previous report of October 27, 1987 on this subject.

Limiting Condition for Operation (LCO) 3.3.3;7 of'the Trojan Technical Specifications requires:the submittal of a Special' Report if smoke detectors located in'the' electrical penetration area are inoperable for greater than 14 days.

During a review of the smoke detector equipment for the electrical penetration area, it was determined that the smoke detectors for the electrical penetration area cannot.be verified l operable if ambient temperatures fall below 32'F.(.the smoke l

detectors are located outside, under a canopy). The manufacturer's technical material states the detectors'are operable at temperatures equal to or greater than 32*F, thus the detectors are assumed inoperable if the ambient temperature falls below 32*F.

The compensatory measures of LCO 3.7.8.2 (establish a continuous fire patrol) will be established whenever the amb'ient temperature falls below 32'F until the detectors are replaced. It is intended to replace these detectors with equipment which is rated for O'F temperatures. The replacement is expected to be completed by February 1988.

Sincerely, 8711230364 871118 PDR ADOCK 05000344 #.

S PDR ,

( ,, , j C. A. Olmstead CAO/RPS/DWS/ K:sg c: Mr. David Kish, Director Mr. R. C. Barr State of Oregon USNRC Resident. Inspector Department of Energy Trojan Nuclear Plant Mr. John B. Martin Distribution-Regional Administrator US Nuclear Regulatory Commission p gMj