ML20212K862

From kanterella
Jump to navigation Jump to search
Special Rept:On 870129,fire Damper Found to Be Installed Upside Down & Declared Inoperable.Fire Damper Installed Incorrectly During Const.Hourly Fire Watch on at Least One Side of Assembly Established & Work Request Initiated
ML20212K862
Person / Time
Site: LaSalle Constellation icon.png
Issue date: 02/23/1987
From: Diederich G
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8703090438
Download: ML20212K862 (1)


Text

. _ _ _ _ _ . _ _ _ . _ _ _ _ . - _ __ _ . -

i QYMb RICRTTY RCtiltM c

~ . -

) Commonwealth Lt. Sills County Nucitar StItion .

Rurti Routa #1, Box 220 Edloon i c V. Marseilles, Illinois 61341 1 - '

Telephone 815/357-6761 Y b hf"~

/L

, cc -

w. '

RL s (

February 23, 1987 g Mr. James G. Keppler Region Administrator l U. S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Sir,

i

[ This special report is submitted in accordance with LaSalle Unit 1 operating License NPF-11, Appendix A, Technical Specification 3.7.6 and 6.6.c. ,

! On January 29, 1987, ftre damper IVD42Y (Ruskin Model NIBD-23 3-Hour Horizontal Fire Damper) was found to be installed upside down. The damper was

! declared inoperable because the installed configuration deviates from the fire rating test configuration. Fire damper IVD42Y is a component of the three (3)

! hour fire barrier separating fire zones 7Al (HPCS Diesel Ventilation Equipment Room) and 781 (HPCS Diesel Generator Room). Fire damper IVD42Y was installed incorrectly during construction and has exceeded the seven (7) day period allowed by Technical Specification 3.7.6 prior to requiring a special report.

An hourly fire watch on at least one side of the affected assembly has been in effect since the initial startup of Unit 1. Since the time of discovery, t operable fire detection has been verified on at least one side of the affected assembly and an hourly fire watch is being performed (in accordance with the Action Statement of Technical Specification 3.7.6).

Work Request L64933 has been initiated to correct the damper configuration and

! is scheduled to be completed by April 1, 1987.  ;

At this time, all Ruskin Model NIBD-23 3-Hour Horizontal Fire Dampers at LaSalle have been verified for correct installation, only one other damper (Ovc65Y), which had been previously reported on December 31, 1986, was incorrectly installed. Damper OVC65Y is scheduled to be installed properly by March 1, 1987.

j t

' O. J. Diederich

' Station Manager LaSalle County Station GJD/DJR/kg xc: U.S. NRC Document Control Desk l

INp0 - Record Center l NRC Resident Inspector

~

8703090438 DR 870223 ADOCK 05000373 4

~ . - _ _ _ , _ _ _

roa wa, o

._ _ _ . _ . _ _ _ _ _ . _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ . . _ _ . _