ML20249C489

From kanterella
Jump to navigation Jump to search
Special Rept:On 980522,Fire Detection Zone 1-31 Was Noted out-of-service for More than 14 Days.Detection Sys Was Taken out-of-service on 980508 to Prevent False Alarms During Hot Work Activities.Sys Was Returned to Operable Status 980528
ML20249C489
Person / Time
Site: LaSalle 
Issue date: 06/22/1998
From: Dacimo F
COMMONWEALTH EDISON CO.
To:
NRC OFFICE OF INFORMATION RESOURCES MANAGEMENT (IRM)
References
NUDOCS 9806300138
Download: ML20249C489 (2)


Text

_ _ - _

Commonw ealth Irlison Company tealle Generating Station JN)I North 21st Road Marseilles. 11.61.461-97s?

m aisas7 e ni Comed June 22,1998 j

United States Nuclear Regulatory Commission Attention: Document Control Desk Washington, D.C. 20555

Subject:

Special Report on Fire Detection Zone 1-31 LaSalle County Nuclear Power Station, Unit 1 Facility Operating License NPF-11 NRC Docket No. 50-373 This Special Report is submitted in accordance with LaSalle County Station Unit 1 Operating License NPF-11, Appendix A, and Technical Specifications 3.3.7.9 and 6.6.C.

Technical Specification 3.3.7.9 requires, as a minimum, the fire detection instrumentation for each fire detection zcne of Unit 1 shown in Table 3.3.7.91 shall be OPERABLE whenever the equipment protected by the fire detection instrument is required to be OPERABLE, and requires the restoration of the instruments to OPERABLE status within 14 days of being declared inoperable.

On May 22,1998, Fire Detection Zone 1-31 had been out of-service for a period greater than 14 days. Fire Detection Zone 1-31 was taken out-of-service on May 8,1998 to prevent false alarms during hot work

//

activities (i.e., welding, cutting, and grinding) associated with L1F35

/d modification work to support restart. Fire Detection Zone 1-31 is located on

~

elevation 673' of the Unit 1 Reactor Building I

A fire watch was established in accordance with Technical Specification 9,7 Action Statement 3.3.7.9.a. to inspect the affected areas while the fire detection instrumentation was inoperable. The fire watch ensured detection capability was available to minimize potential damage to safety related equipment while the fira detection instrumentation was inoperable. Fire Detection Zone 1-31 was returned to an OPERABLE status on May 28,1998.

,4 9006300138 980622 PDR ADOCK 05000373 -

S PDR A Unicom company

If there are any questions or comments concerning this letter, please refer them to Harold D. Pontious, Jr., Regulatory Assurance Manager, (815) 357 6761, extension 2383.

Respe (fu

/lh' Fred R. Dacimo Site Vice President LaSalle County Station cc:

C. A. Paperiello, Acting NRC Region ill Administrator M. P. Huber, NRC Senior Resident Inspector - LaSalle D. M. Skay, Project Manager - NRR - LaSalle F. Niziotek, Office of Nuclear Facility Safety - IDNS

_