Category:CORRESPONDENCE-LETTERS
MONTHYEARML20210Q6931999-08-0909 August 1999 Forwards Updated Changes to Distribution Lists for Browns Ferry & Bellefonte Nuclear Plants ML1108302361993-05-0303 May 1993 Forwards Rev 1 to NRC Licensing Submittal Review of Licensing Conditions Imposed by NUREG-1216. Submittal Made on Behalf of Eight Utils Having Enterprize EDGs for Emergency Standby Ac Power ML18010A9501992-12-0808 December 1992 Forwards NRC Licensing Submittal Review of Licensing Conditions Imposed by NUREG-1216. Submittal Made on Behalf of Eight Utils Having Enterprise EDGs for Emergency Standby Ac Power ML18036A8701992-09-30030 September 1992 Forwards Updated Distribution Lists for Brown Ferry & Bellefonte Nuclear Plants to Reflect Recent Reorganizational Changes.Lists Should Replace Lists Sent on 920515 ML20086K0871991-12-11011 December 1991 Requests Mod of Periodicity in Which Util Conducts Annual Practice Sessions for Fire Brigade Personnel.Rev to Commitment C.3.D.6(b) of BTP Cmeb 9.5-1 Will Permit Practice Session to Be Held Annually ML20065R6891990-12-12012 December 1990 Advises That Util Intends to Reopen Simulator Training Facility at Plant Site Near Hollywood,Al.Requests That Existing NPDES Permit AL0024635 Be Modified to Include Simulator Training Facility Outfall ML20247C3771989-09-0606 September 1989 Confirms Understanding of Applicability of NRC Requirements Developed During Deferral Period of Plant ML20245D9851989-06-22022 June 1989 Forwards 21 Insp Rept Executive Summaries,Per NRC Contract NRC-03-87-029,Task Order 037.Individual Quality Evaluations of Insp Repts Also Prepared ML20246E3551989-06-21021 June 1989 Submits Plan for Quadrex Corp to Lease Plant,Complete Facility,Operate Facility,Sell Power & Eventually Return Plant to Tva.Topic Will Be Discussed at 890711 Meeting ML20248K5451989-04-0505 April 1989 Responds to 890224 & 0322 Ltrs Re NRC Bulletin 88-011, Pressurizer Surge Line Thermal Stratification. NRC Agrees W/Suggestion for 890407 Meeting to Discuss Util Schedular Proposal ML20247G5411989-03-24024 March 1989 Informs of Recent Changes Made within Mgt Structure of Util Organization.Util Reorganization Efforts Aimed at Implementing Changes Necessary to Reflect Reorientation from Design & Mod ML20247E4941989-03-10010 March 1989 Forwards Insp Repts 50-438/89-01 & 50-439/89-01 on 890111.No Violations or Deviations Noted ML20235A1251987-12-16016 December 1987 Forwards Info Re Resource Technical Svcs,Inc,Including Summary of NRC Contract Work,Nrc Form 26 for Three Existing Contracts,Audit Info,Work History & Lists of Expertise Available for Special Insps & of Current Resource Svcs ML20236V7341987-12-0101 December 1987 Partial Response to FOIA Request for Documents.Forwards Documents Listed in App C ML20236V2801987-11-20020 November 1987 Informs That on 871019,Director of NRR Issued Encl Director'S Decision Which Declined to Institute Proceedings Requested by Ucs Petition,In Response to 870731 Request.W/O Encl NUREG-1231, Forwards NUREG-1231, SER Re B&W Owners Group Plant Reassessment Program. NRC Unable to Reach Final Conclusion on Acceptability of Human Factors Portion of Program. Consideration of NRC Recommendations Requested1987-11-0606 November 1987 Forwards NUREG-1231, SER Re B&W Owners Group Plant Reassessment Program. NRC Unable to Reach Final Conclusion on Acceptability of Human Factors Portion of Program. Consideration of NRC Recommendations Requested ML20235S6281987-10-0101 October 1987 Responds to Supporting Request from Smud That Commission Hold Hearing in Sacramento,Ca Re Safety of B&W Nuclear Plants.Response to Concerns Will Be Addressed When Response to Ucs Petition Issued ML20235L3261987-09-29029 September 1987 Responds to to Zech Informing That Ltrs Recently Received from Two Members of Smud Board of Directors Requesting Adjudicatory Hearing Does Not Reflect Views of Majority of Board.Nrc Responded to Kehoe & Smeloff Re Issue ML20235J5351987-09-28028 September 1987 Responds to Constituent Tf Gross Ltr Supporting Ucs 870210 10CFR2.206 Petition to Suspend OLs & CPs of Any Util Operating or Bldg Nuclear Power Reactors Designed by B&W,Per 870803 Request.Nrc Statements Re Plants Discussed ML20235J1171987-09-28028 September 1987 Responds to Requesting Info Re Ucs 870210 Petition Requesting Mods to B&W Facilities,Per E Gallizzi to Recipient Requesting Support of Petition. Gallizzi Statements Discussed.Petition Under Review ML20235B6261987-09-16016 September 1987 Responds to 870812 Request for Hearing to Address Design Flaws in Each of Five Specific Sys Identified in Ucs Petition & Ability of NRC to Evaluate & Assess Level of Danger Inherent in Continued Operation of B&W Plants ML20235B6581987-09-16016 September 1987 Responds to 870912 Request for Hearing Re Design Flaws in Five Specific Sys Identified in Ucs Petition & NRC Ability to Evaluate & Assess Level of Danger Inherent in Continued Operation of B&W Plants ML20235L3771987-08-27027 August 1987 Advises That Received from Two Smud Board of Directors Re Request for Adjudicatory Hearing Does Not Reflect Views of Majority of Board of Directors ML20237H0091987-08-12012 August 1987 Responds to Ucs Et Al 870210 Petition Requesting Public Hearing Re Sufficiency of Mods for Continued Operation of B&W Designed Nuclear Reactors.Util Requests NRC to Hold Hearing in Sacramento,Ca to Discuss Design Flaws & Dangers ML20236L1811987-08-0404 August 1987 Responds to Addressed to Chairman Zech,Requesting That Commission Keep Recipient Fully Apprised of All Developments Re Both Petition Filed by Ucs & Ongoing Reassessment of B&W Reactors.Review of Petition Continuing ML20235J5701987-08-0303 August 1987 Requests Response to Encl Constituent Tf Gross Urging Support of Ucs Petition to Suspend OLs & CPs for All B&W Nuclear Plants Pending Resolution of Extraordinary Safety Problems ML20236L2431987-07-13013 July 1987 Requests That Author Be Fully Apprised of All Developments Re Both Ucs Petition & Ongoing NRC Reassessment of B&W Reactors ML20215D6371987-06-12012 June 1987 Forwards Reply to Responses from NRC & B&W Owners Group. NRC Response Evidences No Independent Review of B&W Claims. Commission Urged to Take Personal Jurisdiction of Petition to Ensure That Latest Commitment Not Frustrated ML20214E2841987-05-18018 May 1987 Final Response to FOIA Request.No PRAs on File for McGuire 1,Bellefonte 1 & Gassar.Pras for Susquehanna 1 & Oyster Creek Available in PDR IA-87-221, Final Response to FOIA Request.No PRAs on File for McGuire 1,Bellefonte 1 & Gassar.Pras for Susquehanna 1 & Oyster Creek Available in PDR1987-05-18018 May 1987 Final Response to FOIA Request.No PRAs on File for McGuire 1,Bellefonte 1 & Gassar.Pras for Susquehanna 1 & Oyster Creek Available in PDR ML20214E2281987-04-16016 April 1987 FOIA Request for PRAs for Listed Plants Be Placed in PDR ML20206P5191987-04-15015 April 1987 Responds to Severity Level IV Violation Noted in Insp Repts 50-438/86-09 & 50-439/86-09.Corrective Actions:Procurement QA Branch Inspectors Conducted Addl Training in Welding Insp.Future Insp Plans Will Address Welding Requirements ML20207U0731987-03-0606 March 1987 Forwards Insp Repts 50-438/86-09 & 50-439/86-09 on 861201-870131 & Notice of Violation ML20207T4561987-02-26026 February 1987 Forwards Insp Repts 50-438/86-10 & 50-439/86-10 on 861216-18.No Violation or Deviation Noted ML20211C3231987-02-12012 February 1987 Ack Receipt of Informing NRC of Steps Taken to Correct Violations Noted in Insp Repts 50-438/86-07 & 50-439/86-07 ML20211C5251987-02-0606 February 1987 Discusses NRC Analysis of Licensing Schedules for Facility, Per Util 870202 Request for NRC Statement to State of Ca. NRC Sept 1981 - Feb 1982 Monthly Repts to Congress Re Licensing Projections for Pending OL Applications Encl ML20209D7441987-01-28028 January 1987 Responds to NRC Re Violations in Noted Insp Repts 50-438/86-07 & 50-439/86-07.Corrective Actions: Requirements for Timely Documenting of Conditions Adverse to Quality Reviewed by Involved Supervisors ML18031B1361987-01-16016 January 1987 Forwards Updates of TVA Activities for Wks of 870119 & 26 ML20212F4541986-12-29029 December 1986 Forwards Insp Repts 50-438/86-07 & 50-439/86-07 on 861001-1130 & Notice of Violation ML20215A1581986-12-0909 December 1986 Final FOIA Response to Request for Documents Re Welding,Mfg & Const Deficiencies Concerning Tdi.Forwards App E Documents.Documents Also Available in PDR ML18031B0011986-11-14014 November 1986 Forwards Updates of TVA Activities for Wks of 861117 & 24 ML20215K5601986-10-16016 October 1986 Notifies of Util Commitments on Response to IE Bulletin 85-001 Re Steam Binding of Auxiliary Feedwater Pumps. Procedures to Be Developed Will Meet Intent of Bulletin Re Monitoring Fluid Conditions & Recognizing Binding IR 05000438/19860041986-08-0606 August 1986 Ack Receipt of Informing NRC of Steps Taken to Correct Violations Noted in Insp Repts 50-438/86-04 & 50-439/86-04 ML20198E2981986-05-20020 May 1986 Discusses Points of View & Concerns Expressed in Ucs Press Release & Re B&W Reactors,Including Plan Responsiveness,Auxiliary Feedwater Sys & Integrated Control Sys.Achievement of Goals Will Reduce Ucs Concerns ML20203N3901986-05-0101 May 1986 Forwards Rev 2 to Tdi Owners Group App Ii:Generic Maint Matrix & Justifications. Rev Approved by Tdi Owners Group & Tdi ML20141A3541986-03-13013 March 1986 Addl Response to FOIA Request for Documents Re Delays or Progress on Const.App C Documents Available in PDR ML20154M2591986-02-18018 February 1986 Discusses SER of Rev 1 to BAW-1847 & BAW-1889P Re Elimination of Postulated Pipe Breaks in PWR Primary Main Loops.Repts Acceptable.Leakage Detection Sys Info Requested ML20137Y0581986-02-18018 February 1986 Requests facility-specific Info Re Requests for Exemption from GDC 4,concerning Protection Against Dynamic Loads Resulting from Postulated Breaks of Primary Main Loop Piping.Info Re Leakage Detection Sys Should Be Included ML20137Y0431986-02-18018 February 1986 Discusses Safety Evaluation of B&W Owners Group Repts Dealing W/Elimination of Postulated Pipe Breaks in PWR Primary Main Loops.Exemption from GDC 4 & Demonstration That Leakage Sys in Compliance W/Reg Guide 1.45 Needed ML20199F2381986-02-0404 February 1986 FOIA Request for All Documents Re Delays or Progress of Const at Bellefonte Nuclear Plant,Including Const Schedules or Projections & Const Status Repts 1999-08-09
[Table view] Category:INCOMING CORRESPONDENCE
MONTHYEARML20210Q6931999-08-0909 August 1999 Forwards Updated Changes to Distribution Lists for Browns Ferry & Bellefonte Nuclear Plants ML1108302361993-05-0303 May 1993 Forwards Rev 1 to NRC Licensing Submittal Review of Licensing Conditions Imposed by NUREG-1216. Submittal Made on Behalf of Eight Utils Having Enterprize EDGs for Emergency Standby Ac Power ML18010A9501992-12-0808 December 1992 Forwards NRC Licensing Submittal Review of Licensing Conditions Imposed by NUREG-1216. Submittal Made on Behalf of Eight Utils Having Enterprise EDGs for Emergency Standby Ac Power ML18036A8701992-09-30030 September 1992 Forwards Updated Distribution Lists for Brown Ferry & Bellefonte Nuclear Plants to Reflect Recent Reorganizational Changes.Lists Should Replace Lists Sent on 920515 ML20086K0871991-12-11011 December 1991 Requests Mod of Periodicity in Which Util Conducts Annual Practice Sessions for Fire Brigade Personnel.Rev to Commitment C.3.D.6(b) of BTP Cmeb 9.5-1 Will Permit Practice Session to Be Held Annually ML20247C3771989-09-0606 September 1989 Confirms Understanding of Applicability of NRC Requirements Developed During Deferral Period of Plant ML20245D9851989-06-22022 June 1989 Forwards 21 Insp Rept Executive Summaries,Per NRC Contract NRC-03-87-029,Task Order 037.Individual Quality Evaluations of Insp Repts Also Prepared ML20246E3551989-06-21021 June 1989 Submits Plan for Quadrex Corp to Lease Plant,Complete Facility,Operate Facility,Sell Power & Eventually Return Plant to Tva.Topic Will Be Discussed at 890711 Meeting ML20247G5411989-03-24024 March 1989 Informs of Recent Changes Made within Mgt Structure of Util Organization.Util Reorganization Efforts Aimed at Implementing Changes Necessary to Reflect Reorientation from Design & Mod ML20235A1251987-12-16016 December 1987 Forwards Info Re Resource Technical Svcs,Inc,Including Summary of NRC Contract Work,Nrc Form 26 for Three Existing Contracts,Audit Info,Work History & Lists of Expertise Available for Special Insps & of Current Resource Svcs ML20235L3771987-08-27027 August 1987 Advises That Received from Two Smud Board of Directors Re Request for Adjudicatory Hearing Does Not Reflect Views of Majority of Board of Directors ML20237H0091987-08-12012 August 1987 Responds to Ucs Et Al 870210 Petition Requesting Public Hearing Re Sufficiency of Mods for Continued Operation of B&W Designed Nuclear Reactors.Util Requests NRC to Hold Hearing in Sacramento,Ca to Discuss Design Flaws & Dangers ML20235J5701987-08-0303 August 1987 Requests Response to Encl Constituent Tf Gross Urging Support of Ucs Petition to Suspend OLs & CPs for All B&W Nuclear Plants Pending Resolution of Extraordinary Safety Problems ML20236L2431987-07-13013 July 1987 Requests That Author Be Fully Apprised of All Developments Re Both Ucs Petition & Ongoing NRC Reassessment of B&W Reactors ML20215D6371987-06-12012 June 1987 Forwards Reply to Responses from NRC & B&W Owners Group. NRC Response Evidences No Independent Review of B&W Claims. Commission Urged to Take Personal Jurisdiction of Petition to Ensure That Latest Commitment Not Frustrated ML20216E4721987-05-28028 May 1987 Part 21 Rept 140 Re Potential Defect in Air Pressure Regulators Mfg by Bellofram.Dripwell Gasket May Fail Due to Mismachining of Gasket Seating Surface Causing Loss of Control Air & Starting Air Pressure ML20214E2281987-04-16016 April 1987 FOIA Request for PRAs for Listed Plants Be Placed in PDR ML20206P5191987-04-15015 April 1987 Responds to Severity Level IV Violation Noted in Insp Repts 50-438/86-09 & 50-439/86-09.Corrective Actions:Procurement QA Branch Inspectors Conducted Addl Training in Welding Insp.Future Insp Plans Will Address Welding Requirements ML20209D7441987-01-28028 January 1987 Responds to NRC Re Violations in Noted Insp Repts 50-438/86-07 & 50-439/86-07.Corrective Actions: Requirements for Timely Documenting of Conditions Adverse to Quality Reviewed by Involved Supervisors ML20207Q6461987-01-21021 January 1987 Forwards Two Lists Revising Commitment Completion Dates for Final Deficiency Repts.Encl 1 Lists Items to Be Completed at Least 6 Months Prior to Fuel Load.Encl 2 Lists Items Scheduled to Undergo Peer Review ML18031B1361987-01-16016 January 1987 Forwards Updates of TVA Activities for Wks of 870119 & 26 ML18031B0011986-11-14014 November 1986 Forwards Updates of TVA Activities for Wks of 861117 & 24 ML20215K5601986-10-16016 October 1986 Notifies of Util Commitments on Response to IE Bulletin 85-001 Re Steam Binding of Auxiliary Feedwater Pumps. Procedures to Be Developed Will Meet Intent of Bulletin Re Monitoring Fluid Conditions & Recognizing Binding ML20198E2981986-05-20020 May 1986 Discusses Points of View & Concerns Expressed in Ucs Press Release & Re B&W Reactors,Including Plan Responsiveness,Auxiliary Feedwater Sys & Integrated Control Sys.Achievement of Goals Will Reduce Ucs Concerns ML20203N3901986-05-0101 May 1986 Forwards Rev 2 to Tdi Owners Group App Ii:Generic Maint Matrix & Justifications. Rev Approved by Tdi Owners Group & Tdi ML20199F2381986-02-0404 February 1986 FOIA Request for All Documents Re Delays or Progress of Const at Bellefonte Nuclear Plant,Including Const Schedules or Projections & Const Status Repts ML20206J2521986-01-24024 January 1986 Forwards Early Draft of Executive Summary from Analysis of Station Blackout Accidents for Bellefonte PWR, Per Request. Initial Draft of Rept Scheduled to Be Completed by 860315 ML20136F4771985-12-31031 December 1985 Forwards PNL-5718, Review of Tdi Diesel Generator Owners Group Engine Requalification Program,Final Rept, Technical Evaluation Rept ML20138Q8581985-12-17017 December 1985 Forwards Update to Deficiency Rept & Outstanding Commitment Completion Schedules,Per 851107 Commitment.Milestones Revised to Allow Final Repts for Each Item to Be Next Rept Submitted ML20133A3141985-09-27027 September 1985 Forwards Review of Section 4.7 of Technical Evaluation Rept PNL-5600, Review of Resolution of Known Problems in Engine Components for Tdi Emergency Diesel Generators, Reflecting Views Re Crankshafts for 16-cylinder Engines ML20132D1941985-09-16016 September 1985 Resubmits Encl BAW-1875, B&W Owners Group Cavity Dosimetry Program, Inadvertently Addressed to Incorrect Individual at Nrc.Timely Review of Rept Requested ML20133H1511985-08-0202 August 1985 Forwards Drawings to Be Incorporated Into Amend 25 to FSAR Question 480.41.W/25 Oversize Drawings.Aperture Cards Available in PDR ML20136H8721985-07-11011 July 1985 FOIA Request for CA Dobbe & R Chambers, Analysis of Station Blackout Transient for Bellefonte PWR & PD Bayless & R Chambers, Analysis of Station Blackout Transient at Seabrook Nuclear Power Plant ML20128H7371985-06-27027 June 1985 Forwards Rev 1 to Review of Engine Base & Bearing Caps for Tdi DSRV-12,DSRV-16 & DSRV-20 Diesel Engines, Technical Evaluation Rept ML20126E8721985-05-24024 May 1985 Forwards PNL-5200-3, Review of Emergency Diesel Generator Engine & Auxiliary Module Wiring & Terminations, Dtd May 1985 ML20127F8441985-04-10010 April 1985 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-21 & 50-439/84-21.Corrective Actions:Plumb & Levelness Requirements Incorporated Into General Drawing, QC Procedure 6.7 Revised & Ducts Inspected ML20127F9781985-03-29029 March 1985 Responds to NRC Re Violations Noted in Insp Repts 50-438/85-04 & 50-439/84-04.Corrective Actions:Terminal Boards Labeled ML20127J6941985-03-28028 March 1985 Provides Second Supplemental Response to NRC Re Deviations Noted in Insp Repts 50-438/83-10 & 50-439/83-10. Corrective Actions:Deficient Fire Damper/Sleeve Tack Welds Installed Per Ul Approved Instructions ML20099K1391985-02-20020 February 1985 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-26 & 50-439/84-26.Corrective actions:dual-rated Foreman No Longer Supervising Crew & Will Not Supervise Until Proper Training Received ML20112G3451984-12-26026 December 1984 Responds to IE Bulletin 84-03, Refueling Cavity Water Seal. Evaluation of Potential for & Consequences of Refueling Cavity Water Seal Failure Encl,Per 841204 Agreement ML20113A8111984-12-0505 December 1984 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-20 & 50-439/84-20.Corrective Actions: Nonconformance Rept 3522 Written to Document Exceeding of Allowable Temp Limit of Paint Storage Warehouse ML20113A3411984-12-0303 December 1984 Suppls Response to NRC Re Violations Noted in Insp Repts 50-438/84-01 & 50-439/84-01.Corrective Actions: Relevant QC Procedures Will Be Issued by 841212 ML20101T2841984-11-30030 November 1984 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-22 & 50-439/84-22.Corrective Actions:Assemblies Placed on Curbing & Damaged Closures Replaced ML20113A3111984-11-16016 November 1984 Suppls Response to NRC Re Violations Noted in Insp Repts 50-438/81-29 & 50-439/81-29.Corrective Actions: Three Replacement Bolts Returned to B&W Due to Inadequate Markings.Corrective Action Will Be Completed by 850222 ML20107G9331984-09-19019 September 1984 Submits Second Revised Response to NRC 840906 Telcon & Re Violations Noted in Insp Repts 50-438/84-04 & 50-439/84-04.Corrective Actions:Battery Cells Replaced & Reported on 840822 as NRC Bln Eeb 8416 ML20106C4091984-09-19019 September 1984 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-15 & 50-439/84-15.Alleged Violation Re Failure to Follow Procedure for Inspecting for Floor Penetrations Denied ML20106C6501984-09-18018 September 1984 Clarifies Response to NRC Re Violations Noted in Insp Repts 50-438/84-12 & 50-439/84-12 Re Failure to Follow Procedures for Hanger Insps.Rev to Nonconformance Rept 1968 Accomplished on 840712 ML20106C3561984-09-12012 September 1984 Suppls Response to NRC Re Violations Noted in Insp Rept 50-438/84-01.Corrective Actions:Environ Qualified Motor Starters Will Be Installed by 850330 & QC Procedure 3.4 Will Be Revised & Issued by 841014 ML20106C6601984-08-31031 August 1984 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-12 & 50-439/84-12.Corrective Actions:Disposition of Unacceptable Hanger Welds Documented on 840203 Under Nonconformance Rept 1968 ML20113A5441984-08-31031 August 1984 Revises Response to NRC Re Violations Noted in Insp Repts 50-438/83-31 & 50-439/83-31.Corrective Actions: Administrative Controls in Nutac Rept on Generic Ltr 83-28 Will Be Reflected in Interdivisional Procedure 1999-08-09
[Table view] Category:UTILITY TO NRC
MONTHYEARML20247C3771989-09-0606 September 1989 Confirms Understanding of Applicability of NRC Requirements Developed During Deferral Period of Plant ML20247G5411989-03-24024 March 1989 Informs of Recent Changes Made within Mgt Structure of Util Organization.Util Reorganization Efforts Aimed at Implementing Changes Necessary to Reflect Reorientation from Design & Mod ML20235L3771987-08-27027 August 1987 Advises That Received from Two Smud Board of Directors Re Request for Adjudicatory Hearing Does Not Reflect Views of Majority of Board of Directors ML20237H0091987-08-12012 August 1987 Responds to Ucs Et Al 870210 Petition Requesting Public Hearing Re Sufficiency of Mods for Continued Operation of B&W Designed Nuclear Reactors.Util Requests NRC to Hold Hearing in Sacramento,Ca to Discuss Design Flaws & Dangers ML20206P5191987-04-15015 April 1987 Responds to Severity Level IV Violation Noted in Insp Repts 50-438/86-09 & 50-439/86-09.Corrective Actions:Procurement QA Branch Inspectors Conducted Addl Training in Welding Insp.Future Insp Plans Will Address Welding Requirements ML20209D7441987-01-28028 January 1987 Responds to NRC Re Violations in Noted Insp Repts 50-438/86-07 & 50-439/86-07.Corrective Actions: Requirements for Timely Documenting of Conditions Adverse to Quality Reviewed by Involved Supervisors ML18031B1361987-01-16016 January 1987 Forwards Updates of TVA Activities for Wks of 870119 & 26 ML18031B0011986-11-14014 November 1986 Forwards Updates of TVA Activities for Wks of 861117 & 24 ML20215K5601986-10-16016 October 1986 Notifies of Util Commitments on Response to IE Bulletin 85-001 Re Steam Binding of Auxiliary Feedwater Pumps. Procedures to Be Developed Will Meet Intent of Bulletin Re Monitoring Fluid Conditions & Recognizing Binding ML20198E2981986-05-20020 May 1986 Discusses Points of View & Concerns Expressed in Ucs Press Release & Re B&W Reactors,Including Plan Responsiveness,Auxiliary Feedwater Sys & Integrated Control Sys.Achievement of Goals Will Reduce Ucs Concerns ML20203N3901986-05-0101 May 1986 Forwards Rev 2 to Tdi Owners Group App Ii:Generic Maint Matrix & Justifications. Rev Approved by Tdi Owners Group & Tdi ML20138Q8581985-12-17017 December 1985 Forwards Update to Deficiency Rept & Outstanding Commitment Completion Schedules,Per 851107 Commitment.Milestones Revised to Allow Final Repts for Each Item to Be Next Rept Submitted ML20132D1941985-09-16016 September 1985 Resubmits Encl BAW-1875, B&W Owners Group Cavity Dosimetry Program, Inadvertently Addressed to Incorrect Individual at Nrc.Timely Review of Rept Requested ML20133H1511985-08-0202 August 1985 Forwards Drawings to Be Incorporated Into Amend 25 to FSAR Question 480.41.W/25 Oversize Drawings.Aperture Cards Available in PDR ML20127F8441985-04-10010 April 1985 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-21 & 50-439/84-21.Corrective Actions:Plumb & Levelness Requirements Incorporated Into General Drawing, QC Procedure 6.7 Revised & Ducts Inspected ML20127F9781985-03-29029 March 1985 Responds to NRC Re Violations Noted in Insp Repts 50-438/85-04 & 50-439/84-04.Corrective Actions:Terminal Boards Labeled ML20127J6941985-03-28028 March 1985 Provides Second Supplemental Response to NRC Re Deviations Noted in Insp Repts 50-438/83-10 & 50-439/83-10. Corrective Actions:Deficient Fire Damper/Sleeve Tack Welds Installed Per Ul Approved Instructions ML20099K1391985-02-20020 February 1985 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-26 & 50-439/84-26.Corrective actions:dual-rated Foreman No Longer Supervising Crew & Will Not Supervise Until Proper Training Received ML20112G3451984-12-26026 December 1984 Responds to IE Bulletin 84-03, Refueling Cavity Water Seal. Evaluation of Potential for & Consequences of Refueling Cavity Water Seal Failure Encl,Per 841204 Agreement ML20113A8111984-12-0505 December 1984 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-20 & 50-439/84-20.Corrective Actions: Nonconformance Rept 3522 Written to Document Exceeding of Allowable Temp Limit of Paint Storage Warehouse ML20113A3411984-12-0303 December 1984 Suppls Response to NRC Re Violations Noted in Insp Repts 50-438/84-01 & 50-439/84-01.Corrective Actions: Relevant QC Procedures Will Be Issued by 841212 ML20101T2841984-11-30030 November 1984 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-22 & 50-439/84-22.Corrective Actions:Assemblies Placed on Curbing & Damaged Closures Replaced ML20113A3111984-11-16016 November 1984 Suppls Response to NRC Re Violations Noted in Insp Repts 50-438/81-29 & 50-439/81-29.Corrective Actions: Three Replacement Bolts Returned to B&W Due to Inadequate Markings.Corrective Action Will Be Completed by 850222 ML20107G9331984-09-19019 September 1984 Submits Second Revised Response to NRC 840906 Telcon & Re Violations Noted in Insp Repts 50-438/84-04 & 50-439/84-04.Corrective Actions:Battery Cells Replaced & Reported on 840822 as NRC Bln Eeb 8416 ML20106C4091984-09-19019 September 1984 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-15 & 50-439/84-15.Alleged Violation Re Failure to Follow Procedure for Inspecting for Floor Penetrations Denied ML20106C6501984-09-18018 September 1984 Clarifies Response to NRC Re Violations Noted in Insp Repts 50-438/84-12 & 50-439/84-12 Re Failure to Follow Procedures for Hanger Insps.Rev to Nonconformance Rept 1968 Accomplished on 840712 ML20106C3561984-09-12012 September 1984 Suppls Response to NRC Re Violations Noted in Insp Rept 50-438/84-01.Corrective Actions:Environ Qualified Motor Starters Will Be Installed by 850330 & QC Procedure 3.4 Will Be Revised & Issued by 841014 ML20106C6601984-08-31031 August 1984 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-12 & 50-439/84-12.Corrective Actions:Disposition of Unacceptable Hanger Welds Documented on 840203 Under Nonconformance Rept 1968 ML20113A5441984-08-31031 August 1984 Revises Response to NRC Re Violations Noted in Insp Repts 50-438/83-31 & 50-439/83-31.Corrective Actions: Administrative Controls in Nutac Rept on Generic Ltr 83-28 Will Be Reflected in Interdivisional Procedure ML20099L2331984-08-0303 August 1984 Submits Results of Survey to Determine Extent of Missing Washers on Wedge Bolts,Per Initial 840330 Response to Insp Repts 50-438/84-03 & 50-439/84-03.QC Procedure Re Bolt Anchors Set in Concrete Revised ML20095G5361984-07-23023 July 1984 Forwards Supplemental Response to IE Bulletin 81-03 Re Flow Blockage of Cooling Water to Safety Sys Components by Corbicula Sp (Asiatic Clam) & Mytilus Sp (Mussel) ML20095G1081984-07-13013 July 1984 Forwards Supplemental Response to NRC Re Violations Noted in Insp Repts 50-438/83-05 & 50-439/83-05. Corrective actions:BNP-QCP-6.3 Revised to Clarify Listing of Attributes Inspected on Thermal Expansion Devices ML20090J1001984-06-27027 June 1984 Responds to NRC Re Violations Noted in IE Insp Rept 50-438/84-05.Corrective actions:BNP-QCP-10.6 Will Not Be Used for Revised Drawing Changes ML20113A5481984-06-25025 June 1984 Responds to NRC Re Violations Noted in Insp Repts 50-438/83-31 & 50-439/83-31.Corrective Action Will Be Completed by 840901 ML20107G9391984-06-20020 June 1984 Submits Revised Response to NRC 840601 Telcon & Re Violations Noted in Insp Repts 50-438/84-04 & 50-439/84-04.Corrective Actions:Nonconformance Rept 2856 Initiated Re Froth on Station Batteries ML20092D3201984-05-21021 May 1984 Responds to NRC Re Violations Noted in IE Insp Repts 50-438/84-09 & 50-439/84-09.Corrective Actions:Qc Procedure Revised to Prohibit Any Installation of Ssd Anchors in Concrete Walls ML20107G9541984-05-10010 May 1984 Responds to NRC Re Violations Noted in Insp Repts 50-438/84-04 & 50-439/84-04.Violation Re Station Battery Frothing Denied ML20092D3921984-05-0202 May 1984 Forwards Supplemental Response to Notice of Violation in IE Insp Repts 50-438/83-24 & 50-439/83-24,per NRC 840404 Request to Admit Part A.3 & Revise Schedule for Parts A.4 & A.5 Re Questionable Ultrasonic Exams ML20091B3051984-04-18018 April 1984 Responds to NRC Re Violations Noted in IE Insp Repts 50-438/84-05 & 50-439/84-05.Corrective Actions:All Accessible Portions of 74 Welds Inspected Visually ML20093F2351984-03-30030 March 1984 Responds to NRC Re Violations Noted in IE Insp Repts 50-438/83-31 & 50-439/84-31.Corrective Actions: Procedure IDP 52.05 Re Control & Handling of Vendor Manuals Will Be Issued by 840720,per Generic Ltr 83-28 ML20092P4581984-03-30030 March 1984 Responds to NRC Re Violations Noted in IE Insp Repts 50-438/84-03 & 50-439/84-03.Corrective Actions: Procedures to Be Revised to Provide Design Clarification That Bolt Torques Not Required to Be Reproducible ML20087P3911984-03-14014 March 1984 Responds to NRC Re Violations Noted in IE Insp Repts 50-438/84-01 & 50-439/84-01.Corrective Actions: Nonconformance Rept 2721 Generated to Document Rework of Rusted Unit 1 Conduit.Motor Starter Will Be Replaced ML20093F2781984-02-10010 February 1984 Responds to NRC Re Violations Noted in IE Insp Repts 50-438/83-31 & 50-439/83-31.Corrective Actions:Vendor Drawings Will Be Revised to Reflect Correct Solenoid Orientation.Item 1 Denied as Violation ML20092D3991984-01-19019 January 1984 Forwards Supplemental Info to Clarify Questions & Concerns Raised by NRC Region II Inspectors Re Violations in IE Insp Repts 50-438/83-24 & 50-439/83-24.Violations Involve Questionable Ultrasonic Exams ML20095G1281984-01-0404 January 1984 Supplemental Response to Violations Noted in Insp Repts 50-438/83-05 & 50-439/83-05.Corrective Action:Const QC Unit Waiting for Computer Printout to Verify Insp of All Affected Equipment Under Revs 0 & 1 to Qcp 6.3 ML20092D4051983-12-29029 December 1983 Provides Supplemental Response to Notice of Violation in Area of Ultrasonic Exams in IE Insp Repts 50-438/83-24 & 50-439/83-24,per 831128 Discussion ML20079J5181983-12-28028 December 1983 Responds to NRC Re Violations Noted in IE Insp Repts 50-438/83-28 & 50-439/83-28.Corrective Actions:Memo Emphasizing Awareness of Requirement That Heaters Remain Energized Issued & FSAR Revised to Reflect Exception ML20091B1831983-12-22022 December 1983 Responds to NRC Re Violations Noted in IE Insp Repts 50-438/83-10 & 50-439/83-10.Corrective Actions:Efforts Underway to Obtain Vendor Verification of Correct Fire Damper Installation ML20083H3061983-12-21021 December 1983 Forwards Response to NRC Re Violations Noted in IE Insp Repts 50-438/83-27 & 50-439/83-27.Corrective Actions:Training Sessions Will Be Conducted to Reemphasize Proper Insp of Clamp Spacers & Allowable Tolerance ML20091B1981983-12-15015 December 1983 Suppls Response to NRC Re Violations Noted in IE Insp Repts 50-438/83-10 & 50-439/83-10.Corrective Actions: Fire Protection Sys Nonconformances Will Be Corrected by 851114 1989-09-06
[Table view] |
Text
. - - - _ _ _ _ _ _ _ - _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ - _ _ - _ _ - - _ _ _ - _ _ _ _ _ _ - _ _ _ - - - _ _ - - - - - - - - - - - - - - - -
f TENNESSEE VALLEY AUTHORITY
^
CHATTANOOGA. TENNESSEE 37401 400 Chestnut Street Tower II U.S. Nuclear Regulatory Commission b JUl. 25 /t gulp 3,1984 Region II Attn: Mr. James P. O'Reilly, Regional Administrator 101 Marietta Street, NW, Suite 2900 Atlanta, Georgia 30323
Dear Mr. O'Reilly:
BELLEFONTE NUCLEAR PLANT UNITS 1 AND 2 - SUPPLEMENTAL RESPONSE TO BULLETIN 81-03 FLOW BLOCKAGE OF COOLING WATER TO SAFETY SYSTEM COMPONENTS BY CORBICULA SP. (ASIATIC CLAM) AND MYTILUS SP. (MUSSEL)
In my letters to you dated July 8,1981, and February 17,1983, TVA had described its program for detecting and controlling the growth of Asiatic clams in the high pressure fire protection and essential raw cooling water systems at Bellefonte Nuclear Plant. The purpose of the enclosed supplemental response is to inform you of changes to TVA's previous responses and to clearly distinguish between chlorination procedures during the plant construction phase and during normal plant operation.
If you have any questions concerning this matter, please get in touch with R. H. Shell at FTS 858-2688.
Very truly yours, TENNESSEE VALLEY AUTHORITY L. M. Mills, Manager Nuclear Licensing Enclosure cc (Enclosure):
Mr. Richard C. DeYoung, Director Office of Inspection and Enforcement U.S. Nuclear Regulatory Commission Washington, D.C. 20555 Records Center Institute of Nuclear Power Operations 1100 Circle 75 Parkway, Suite 1500 Atlanta, Georgia 30339 8408280100 840723 PDRADOCK05000g G
V@A
_ ^ ? ~ ~ """ " ~ ~ "" 'l'
, a" ENCLOSURE
. =
BELLEFONTE NUCLEAR PLANT REVISED SUPPLEMENTAL RESPONSE ON IE BULLETIN 81-03 FLOW BLOCKAGE OF COOLING WATER TO SAFETY SYSTEM COMPONENTS BY CORBICULA SP. (ASIATIC CLAM) AND MYTILUS SP. (MUSSEL) .
There are two d1anges to our previous responses on this subject. First, in our February 17, 1983 letter, TVA responded that a "small continuous flow of chlorinated water will be established during clam spawning season through all major fire protection headers." This has proven to be impractical and as such will not be practiced at Bellefonte. The High Pressure Fire Protection (HPFP) system at Bellefonte will be chlorinated in accordance with TVA's response to item 1B in our July 8,1981 letter.
Second, in the subject letter TVA stated that " permanent onsite sodium hypochlorite generation systems have been procured and will . . . be available for use" at all TVA Nuclear Plants. At the present time, it is economically advantageous to TVA to purchase the sodium hypochlorite from a commercial supplier. The purchased sodium hypochlorite will be used for chlorination.
TVA's chlorination program, during plant construction and during normal plant operation, is essentially the same. It is TVA's intent to chlorinate the Essential Raw Cooling Water (ERCW) and HPFP systems at the times of the year and to the residuals specified in our July 8,1981 letter, regardless of whether the plant is still under construction or in normal operation.
However, TVA has not yet been able to establish and maintain the chlorine residuals specified in our February 17, 1983 re sponse. TVA has been moderately successful in establishing chlorine residual in the ERCW system, although this residual has typically been less than our goal of 0.6 - 0.8 ppm total residual chlorine. TVA has had virtually no success in establishing the specified residual in the HPFP system.
TVA attributes these difficultial to the corrosive nature of sodium hypochlorite, which has resulted in frequent maintenance problems with the hypochlorite distribution and injection system, and to the inherently unstabic nature of sodium hypochlorite, which has resulted in erratic performance of the hypochlorite injection pumps. TVA is continuing to review these problems and to consider changes in system design and mainte-nance which will eliminate or minimize them.
During the construction phase at Bellefonte, TVA will continue to inspect the HPFP and ERCW systems for evidence of clam infestation. These inspections will be of the type reported by TVA in our February 17, 1983 response. Chlorination system failures, which result in a loss of chlorination of the ERCW or HPFP systems in excess of 30 days, will be evaluated to determine whether inspection, additional flushing, or shock chlorination is required to return the system (s) to a normal condition.
During normal plant operation at Bellefonte, the chlorination program for the ERCW and HPFP systems will be as described in TVA's February 17, 1983 response and as amended by this supplemental response.