Semantic search

Jump to navigation Jump to search
 Issue dateTitleTopic
ML20247C3776 September 1989Confirms Understanding of Applicability of NRC Requirements Developed During Deferral Period of PlantBackfit
ML20247G54124 March 1989Informs of Recent Changes Made within Mgt Structure of Util Organization.Util Reorganization Efforts Aimed at Implementing Changes Necessary to Reflect Reorientation from Design & Mod
ML20235L37727 August 1987Advises That Received from Two Smud Board of Directors Re Request for Adjudicatory Hearing Does Not Reflect Views of Majority of Board of Directors
ML20237H00912 August 1987Responds to Ucs Et Al 870210 Petition Requesting Public Hearing Re Sufficiency of Mods for Continued Operation of B&W Designed Nuclear Reactors.Util Requests NRC to Hold Hearing in Sacramento,Ca to Discuss Design Flaws & Dangers
ML20206P51915 April 1987Responds to Severity Level IV Violation Noted in Insp Repts 50-438/86-09 & 50-439/86-09.Corrective Actions:Procurement QA Branch Inspectors Conducted Addl Training in Welding Insp.Future Insp Plans Will Address Welding RequirementsCondition Adverse to Quality
ML20209D74428 January 1987Responds to NRC Re Violations in Noted Insp Repts 50-438/86-07 & 50-439/86-07.Corrective Actions: Requirements for Timely Documenting of Conditions Adverse to Quality Reviewed by Involved SupervisorsCondition Adverse to Quality
ML18031B13616 January 1987Forwards Updates of TVA Activities for Wks of 870119 & 26
ML18031B00114 November 1986Forwards Updates of TVA Activities for Wks of 861117 & 24
ML20215K56016 October 1986Notifies of Util Commitments on Response to IE Bulletin 85-001 Re Steam Binding of Auxiliary Feedwater Pumps. Procedures to Be Developed Will Meet Intent of Bulletin Re Monitoring Fluid Conditions & Recognizing Binding
ML20198E29820 May 1986Discusses Points of View & Concerns Expressed in Ucs Press Release & Re B&W Reactors,Including Plan Responsiveness,Auxiliary Feedwater Sys & Integrated Control Sys.Achievement of Goals Will Reduce Ucs Concerns
ML20203N3901 May 1986Forwards Rev 2 to Tdi Owners Group App Ii:Generic Maint Matrix & Justifications. Rev Approved by Tdi Owners Group & Tdi
ML20138Q85817 December 1985Forwards Update to Deficiency Rept & Outstanding Commitment Completion Schedules,Per 851107 Commitment.Milestones Revised to Allow Final Repts for Each Item to Be Next Rept Submitted
ML20132D19416 September 1985Resubmits Encl BAW-1875, B&W Owners Group Cavity Dosimetry Program, Inadvertently Addressed to Incorrect Individual at Nrc.Timely Review of Rept Requested
ML20133H1512 August 1985Forwards Drawings to Be Incorporated Into Amend 25 to FSAR Question 480.41.W/25 Oversize Drawings.Aperture Cards Available in PDR
ML20127F84410 April 1985Responds to NRC Re Violations Noted in Insp Repts 50-438/84-21 & 50-439/84-21.Corrective Actions:Plumb & Levelness Requirements Incorporated Into General Drawing, QC Procedure 6.7 Revised & Ducts Inspected
ML20127F97829 March 1985Responds to NRC Re Violations Noted in Insp Repts 50-438/85-04 & 50-439/84-04.Corrective Actions:Terminal Boards Labeled
ML20127J69428 March 1985Provides Second Supplemental Response to NRC Re Deviations Noted in Insp Repts 50-438/83-10 & 50-439/83-10. Corrective Actions:Deficient Fire Damper/Sleeve Tack Welds Installed Per Ul Approved Instructions
ML20099K13920 February 1985Responds to NRC Re Violations Noted in Insp Repts 50-438/84-26 & 50-439/84-26.Corrective actions:dual-rated Foreman No Longer Supervising Crew & Will Not Supervise Until Proper Training Received
ML20112G34526 December 1984Responds to IE Bulletin 84-03, Refueling Cavity Water Seal. Evaluation of Potential for & Consequences of Refueling Cavity Water Seal Failure Encl,Per 841204 Agreement
ML20113A8115 December 1984Responds to NRC Re Violations Noted in Insp Repts 50-438/84-20 & 50-439/84-20.Corrective Actions: Nonconformance Rept 3522 Written to Document Exceeding of Allowable Temp Limit of Paint Storage WarehouseCoatings
ML20113A3413 December 1984Suppls Response to NRC Re Violations Noted in Insp Repts 50-438/84-01 & 50-439/84-01.Corrective Actions: Relevant QC Procedures Will Be Issued by 841212
ML20101T28430 November 1984Responds to NRC Re Violations Noted in Insp Repts 50-438/84-22 & 50-439/84-22.Corrective Actions:Assemblies Placed on Curbing & Damaged Closures Replaced
ML20113A31116 November 1984Suppls Response to NRC Re Violations Noted in Insp Repts 50-438/81-29 & 50-439/81-29.Corrective Actions: Three Replacement Bolts Returned to B&W Due to Inadequate Markings.Corrective Action Will Be Completed by 850222
ML20107G93319 September 1984Submits Second Revised Response to NRC 840906 Telcon & Re Violations Noted in Insp Repts 50-438/84-04 & 50-439/84-04.Corrective Actions:Battery Cells Replaced & Reported on 840822 as NRC Bln Eeb 8416Condition Adverse to Quality
ML20106C40919 September 1984Responds to NRC Re Violations Noted in Insp Repts 50-438/84-15 & 50-439/84-15.Alleged Violation Re Failure to Follow Procedure for Inspecting for Floor Penetrations Denied
ML20106C65018 September 1984Clarifies Response to NRC Re Violations Noted in Insp Repts 50-438/84-12 & 50-439/84-12 Re Failure to Follow Procedures for Hanger Insps.Rev to Nonconformance Rept 1968 Accomplished on 840712
ML20106C35612 September 1984Suppls Response to NRC Re Violations Noted in Insp Rept 50-438/84-01.Corrective Actions:Environ Qualified Motor Starters Will Be Installed by 850330 & QC Procedure 3.4 Will Be Revised & Issued by 841014
ML20106C66031 August 1984Responds to NRC Re Violations Noted in Insp Repts 50-438/84-12 & 50-439/84-12.Corrective Actions:Disposition of Unacceptable Hanger Welds Documented on 840203 Under Nonconformance Rept 1968
ML20113A54431 August 1984Revises Response to NRC Re Violations Noted in Insp Repts 50-438/83-31 & 50-439/83-31.Corrective Actions: Administrative Controls in Nutac Rept on Generic Ltr 83-28 Will Be Reflected in Interdivisional Procedure
ML20099L2333 August 1984Submits Results of Survey to Determine Extent of Missing Washers on Wedge Bolts,Per Initial 840330 Response to Insp Repts 50-438/84-03 & 50-439/84-03.QC Procedure Re Bolt Anchors Set in Concrete Revised
ML20095G53623 July 1984Forwards Supplemental Response to IE Bulletin 81-03 Re Flow Blockage of Cooling Water to Safety Sys Components by Corbicula Sp (Asiatic Clam) & Mytilus Sp (Mussel)
ML20095G10813 July 1984Forwards Supplemental Response to NRC Re Violations Noted in Insp Repts 50-438/83-05 & 50-439/83-05. Corrective actions:BNP-QCP-6.3 Revised to Clarify Listing of Attributes Inspected on Thermal Expansion Devices
ML20090J10027 June 1984Responds to NRC Re Violations Noted in IE Insp Rept 50-438/84-05.Corrective actions:BNP-QCP-10.6 Will Not Be Used for Revised Drawing Changes
ML20113A54825 June 1984Responds to NRC Re Violations Noted in Insp Repts 50-438/83-31 & 50-439/83-31.Corrective Action Will Be Completed by 840901
ML20107G93920 June 1984Submits Revised Response to NRC 840601 Telcon & Re Violations Noted in Insp Repts 50-438/84-04 & 50-439/84-04.Corrective Actions:Nonconformance Rept 2856 Initiated Re Froth on Station BatteriesCondition Adverse to Quality
ML20092D32021 May 1984Responds to NRC Re Violations Noted in IE Insp Repts 50-438/84-09 & 50-439/84-09.Corrective Actions:Qc Procedure Revised to Prohibit Any Installation of Ssd Anchors in Concrete Walls
ML20107G95410 May 1984Responds to NRC Re Violations Noted in Insp Repts 50-438/84-04 & 50-439/84-04.Violation Re Station Battery Frothing DeniedTime of Discovery
Condition Adverse to Quality
ML20092D3922 May 1984Forwards Supplemental Response to Notice of Violation in IE Insp Repts 50-438/83-24 & 50-439/83-24,per NRC 840404 Request to Admit Part A.3 & Revise Schedule for Parts A.4 & A.5 Re Questionable Ultrasonic ExamsNondestructive Examination
ML20091B30518 April 1984Responds to NRC Re Violations Noted in IE Insp Repts 50-438/84-05 & 50-439/84-05.Corrective Actions:All Accessible Portions of 74 Welds Inspected Visually
ML20093F23530 March 1984Responds to NRC Re Violations Noted in IE Insp Repts 50-438/83-31 & 50-439/84-31.Corrective Actions: Procedure IDP 52.05 Re Control & Handling of Vendor Manuals Will Be Issued by 840720,per Generic Ltr 83-28
ML20092P45830 March 1984Responds to NRC Re Violations Noted in IE Insp Repts 50-438/84-03 & 50-439/84-03.Corrective Actions: Procedures to Be Revised to Provide Design Clarification That Bolt Torques Not Required to Be Reproducible
ML20087P39114 March 1984Responds to NRC Re Violations Noted in IE Insp Repts 50-438/84-01 & 50-439/84-01.Corrective Actions: Nonconformance Rept 2721 Generated to Document Rework of Rusted Unit 1 Conduit.Motor Starter Will Be Replaced
ML20093F27810 February 1984Responds to NRC Re Violations Noted in IE Insp Repts 50-438/83-31 & 50-439/83-31.Corrective Actions:Vendor Drawings Will Be Revised to Reflect Correct Solenoid Orientation.Item 1 Denied as Violation
ML20092D39919 January 1984Forwards Supplemental Info to Clarify Questions & Concerns Raised by NRC Region II Inspectors Re Violations in IE Insp Repts 50-438/83-24 & 50-439/83-24.Violations Involve Questionable Ultrasonic ExamsNondestructive Examination
ML20095G1284 January 1984Supplemental Response to Violations Noted in Insp Repts 50-438/83-05 & 50-439/83-05.Corrective Action:Const QC Unit Waiting for Computer Printout to Verify Insp of All Affected Equipment Under Revs 0 & 1 to Qcp 6.3
ML20092D40529 December 1983Provides Supplemental Response to Notice of Violation in Area of Ultrasonic Exams in IE Insp Repts 50-438/83-24 & 50-439/83-24,per 831128 Discussion
ML20079J51828 December 1983Responds to NRC Re Violations Noted in IE Insp Repts 50-438/83-28 & 50-439/83-28.Corrective Actions:Memo Emphasizing Awareness of Requirement That Heaters Remain Energized Issued & FSAR Revised to Reflect Exception
ML20091B18322 December 1983Responds to NRC Re Violations Noted in IE Insp Repts 50-438/83-10 & 50-439/83-10.Corrective Actions:Efforts Underway to Obtain Vendor Verification of Correct Fire Damper Installation
ML20083H30621 December 1983Forwards Response to NRC Re Violations Noted in IE Insp Repts 50-438/83-27 & 50-439/83-27.Corrective Actions:Training Sessions Will Be Conducted to Reemphasize Proper Insp of Clamp Spacers & Allowable Tolerance
ML20091B19815 December 1983Suppls Response to NRC Re Violations Noted in IE Insp Repts 50-438/83-10 & 50-439/83-10.Corrective Actions: Fire Protection Sys Nonconformances Will Be Corrected by 851114