September 8, 1982 Mr. James P. O'Reilly, Regional Administrator U. S. Nuclear Regulatory Commission Region II 101 Marietta Street, Suite 3100 Atlanta, Georgia 30303 Re: McGuire Nuclear Station Unit 1 Docket No. 50-369

Dear Mr. O'Reilly:

Please find attached Reportable Occurrence Report R0-369/82-65. This report concerns T.S.3.4.1.1, "All reactor coolant loops shall be in operation".

This incident was considered to be of no significance with respect to the health and safety of the public.

Very truly yours,

- M llal B. Tucker PBN/jfw Attachment cc: Director Records Center Office of Management and Program Analysis Institute of Nuclear Power Operations U. S. Nuclear Regulatory Commission 1820 Water Place Washington, D. C. 20555 Atlanta, Georgia 30339 Mr. P. R. Bemis Senior Resident Inspector-NRC McGuire Nuclear Station kh9 29 820908

.L~~OFFletAL C%k S K 05000369 Tg[S L

DUKE POWER COMPANY McCUIRE NUCLEAR STATION REPORTABLE OCCURRENCE REPORT NO. 82-65 REPORT DATE: September 8, 1982 FACILITY: McGuire Unit 1, Cornelius, NC IDENTIFICATION: Reactor Trip as a Result of Inadvertently Deenergizing a Reactor Coolant Pump DESCRIPTION: On August 9, 1982, while operating at 50% reactor power, Unit One was tripped by the Reactor Protection System on a senced loss of flow in reactor coolant loop A.

An intermittent ground on a 125 VDC Auxiliary Control Power battery had occurred and technicians were attempting to isolate the ground by sequentially removing and reenergizing loads. In the course of the search, control power was removed from the 6900 Volt Normal Auxiliary Power System (EPB) breaker whien feeds the Reactor Coolant Pump Switchgear (safety breaker) for reactor coolant pump A. By circuit design, the loss of control power to the 6900 V EPB breaker caused the safety breaker to open, deenergizing the pump motor.

No unusual events were experienced during the transient accompanying the trip (at 0129) and a trip recovery was commenced at 0258.

The incident was a result of Design Error, but Personnel Error also contributed because operators failed to recognize the consequence of the loss of control power prior to directing the progression of the ground isolation procedure.

EVALUATION: The reactor coolant pump safety breakers were designed to trip open when their associated 6900 Volt EPB feeder breakers are opened. A contact in the safety breaker trip coil circuit was provided to accomplish this function. The contact is closed by deencrgizing its control relay in the EPB feeder breaker control circuit. The relay in turn is energized when feeder breaker auxiliary contact is closed. Consequently, the safety breaker will open when the feeder breaker opens or when the feeder breaker control power is deenergized. In this instance control power was removed from all ITA Switchgear by opening the control power distribution panel, DCA, breaker 2B.

It should De noted that during investigation of this event several hours were spent determining the mechanism for the breaker trip through study of the associated schematic drawings. Therefore the function could have been easily overlooked by operators despite a thorough review of the circuitry.

SAFETY ANALYSIS: The automatic reactor protection loss of flow trip function was exercised and operated correctly in this incident. The health and safety of.the public were not affected.

The modification to the reactor coolant pump switchgear control circuitry will provide adequate breaker protection consistant with the original design intent.

r .' .

Report No. 82-65 Page 2 CORRECTIVE ACTION: A modification is being initiated to eliminate the function to trip reactor coolant pump safety breakers on loss of control power to the associated 6900V switchgear feeder breakers. The safety function to trip the safety breakers upon trip of the feeder breaker will be retained.

Upon implementation of the modification the 125 VDC Auxiliary Control Power System (EPK) distribution boards will be compatible to the ground isolation methodology that was in progress when the. incident occurred. Appropriate warnings have been posted on the eight EPK breakers (Units 1 and 2) which are susceptible to_this occurrence. These will remain in place until the modifica-

'tions are accomplished.

The personnel error involving inadequate research prior to conducting ground isolation procedures will be addressed in crew training sessions through the review of this report.