Special Rept Re Fire Detection Zones Removed from Svc as Conservative Precaution to Prevent Spurious Zone Fire Alarms Due to Extensive Welding & Cutting.Hourly Fire Watch Established to Inspect Affected Areas
ML20212B125
Person / Time
Site: LaSalle Constellation icon.png
Issue date: 12/18/1986
From: Diederich G
COMMONWEALTH EDISON CO.
To: James Keppler
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION III)
References
NUDOCS 8612290175
Download: ML20212B125 (1)


Text

- _ _ _

c;-

N

) Commonwealth Edison L:Sille County Nucl::r Station Rur11 Routs #1, Box 220 Mh

\ v 7 Marseilles, Illinois 61341 ppgg p;,g Telephone 815/357-6761 December 18 1986 f --

c L/& +I & Y 3k - -

pu--lr -

Mr. James G. Keppler HL Regional Administrator Region III U.S. Nuclear Regulatory Commission 799 Roosevelt Road Glen Ellyn, Illinois 60137

Dear Sir:

This special report is submitted in accordance with LaSalle Unit 2 Operating License NPF-18, Appendix A, Technical Specification 3.3.7.9 and 6.6.c.

Due to primary containment vent and purge (VQ) de::ign modification (M-1-2-84-048) construction activities, it was necessary to remove the following fire detection zones from service as a conservative precaution to prevent spurious zone fire alarms due to extensive welding and cutting in the areas.

- Detector Zone Area 2-17 U-2 Reactor Building, 740' 2-22 U-2 Reactor Building, 710' 2-22P U-2 Reactor Building, 710' 2-34 U-2 Reactor Building, 761' 2-36 U-2 Reactor Building, 786' In accordance with Action A of Technical Specification 3.3.7.9, an hourly fire watch was established to inspect the affected areas during the time the detectors are inoperable.

The smoke detectors have been out of service in excess of the allowed fourteen (14) days prior to requiring a special report. Fire detection zones 2-17, 2-22, 2-22P, 2-34 and 2-36 will be returned to service as the required wlding for the VQ modification in each respective zone is completed.

A. D .

U G. J. Diederich Station Manager LaSalle County Station GJD/DJR/kg xc: U.S. Document Control Desk INPO-Records Center File /NRC B612290175 861218 4 DR ADOCK 0500 10 gy M 213