OPERATING DATA REPORT DOCKET NO.      50-261 DATE 830202 COMPLETED BY      H.        R w Norris TELEPHONE 803-383-4524 OPERATING STATUS
: 1. Unit Name:          H. B. Robinson Unit No. 2                        Notes There are presently 157
: 2. Reporting Period:          830101, 0000/830131, 2400                    spent fuel assemblics in the 2300                        spent fuel pool.
: 3. Licensed Thermal Power (MWt):
: 4. Nameplate Rating (Gross MWe):                739
: 5. Design Electrical Rating (Net MWe):          700
: 6. Maximum Dependable Capacity (Gross MWe):            700
: 7. Maximum Dependable Capacity (Net MWe):              665
: 8. If Changes Occur in Capacity Ratings (Items Number 3 Througir 7) Since Last Report, Gin Reasons:
No change
: 9. Power Level To Which Restricted,if Any (Net MWe):        1955 Mit reactor power
: 10. Reasons For Restrictions,if Any:        Although the    unit is not restricted by any outside agency, the power level is presently reduced due to steam generator con-siderations.
This Month              Yr.-to-Date          Cumulative iI. Hours In Reporting Period                                    744                  744              104430
: 12. Number Of Hours Reactor Was Critical                        720.3                720.3            77559.97
: 13. Reactor Reserve Shutdown Hours                                18.13                18.13              1325.9
: 14. Hours Generator On-Line                                      705.52                705.52            75541.56
: 15. Unit Reserve Shutdown Hours                                    0                    0        =                23.20
: 16. Gross TI ermal Energy Generated (MWH)                1227907.4            1227907.4          _151992446
: 17. Gross Electrical Energy Generated (MWH)                394959_ .            394960              48903723
: 18. Net Electrical Energy Generated (MWH)                  370696                370696              46242793 19.' Unit Service Factor                                          94.83                94.83                        72.33
: 20. Unit Availability Factor                                      94.83                94.83                        72.36
: 21. Unit Capacity Factor (Using MDC Net)                          74.92                74.92                      66.59
: 22. Unit Capacity Factor (Using DER Net)                          71.18                71.18                      63.26
: 23. Unit Forced Outage Rate                                        5.17                  5.17                        14.14
: 24. Shutdowns Scheduled Over Next 6 Months (Type. Date and Duration of Each):
Type two 4-23-83, four week steam generator inspection outage
: 25. If Shut Down At End Of Report Period Estimated Date of Startup:            On-line
: 26. Units in Test Status (Prior to Commercial Operation):                        Forecast              Achieved
,                                INITIA L CRITICALITY                                        -                    -
INITIAL ELECTRICITY                                          -                    -
COMMERCIAL OPERATION 8302170070 030209 PDR ADOCK 05000261 R                          PDR                                                                                            goj773 sg
 
s UNIT SHUTDOWNS AND POWE.9. REDUCTIONS                    DOCKET NO. .f 0-261 UNIT NAME        H. B. Robinson DATE 830202 COMPLETED By        H. Ray Norris REPORT MONTH    January TELEPHONE 803-383-4524 e.
w    E                              E                                                                6
                              --,      .! E      3      jY5          Licensee    ,E t,          1, j''3                Cause & Corrective No.          Dat e    g      3g          s    jg&          Event      t; 9        c.                        Action to H
                                        $E        5      5dic        Report er  N0          $U                  Prevent Recurrence e    g                              u O
12-1      830101      F    13.33        A        3                      HB      INSTRU    A faulty fuse holder caused the power solenoid for "C" MSIV to de-energize closing the MISV which caused a low-low level in "C" S/G and subsequent unit trip. The fuse holder was re-placed.
1-1      830107      F    25.15        A        1                      HH      HTEXCH    #5 feedwater heater tube leaks.
Twenty-four tubes required plugging.
                                                                                                      % e unit's return to service was delayed 5.57 hours due to a reactor trip caused by a momentary spurious safeguards actuation signal.
4 1                    2                                                  3                                4 F: Forced            Reason:                                            Method:                -
Exhibit G - Instructions S: Scheduled        A Equipment Failure (Explain)                      1 -Mann-1                          for Preparation of Data B-Maintenance of Test                              2-Man 11 Scram.                    Entry Sheets for Licensee C Refueling                                        3-Autienatic Scram.                Event Report (LER) File (NUREG-D Regulatory Restriction                            4-Othe iExplain)                  0161)
E. Operator Training & License Examination F-Administntive                                                                    5
  .                            G-Operational Error (Explain)                                                          Exhibit I- Same Source (9/77)                  11-0ther (Explain) i  sg
 
9 AVERAGE DAILY UNIT POWER LEVEL DOCKET NO. 50-261 UNIT    H. B. Robinson DATE    830202 COMPLETED BY        H. Ray Norris TELEPHONE    803-383-4524 MONTH          Jam m DAY          AVERAGE DAILY POWER LEVEL                        DAY      AVERAGE DAILY POWER LEVEL-(MWe-Net)                                                    (MWe-Net) 66                                                              561
                                                                                                          ~
17 ,
2            420                                            18                560                                  1 3            523                                            19              453 4            558                                            20              472 5            558                                            21              561 6            559                                                            539 22 7            423                                            23              529 8            -20                                            24              562 9            331                                            25              562 10            560                                            26              562 13            562                                            27            562 12            561                                                            562 28 33            563                                                            564 29 l      14            563                                            30              563 33            563                                                            563 33 16            483 INSTRUCTIONS On this format, list the average daily unit power levelin MWe Net for each day in the reporting month. Compute to the nearest whole megawatt.
t r
(9/77)
{
sg
_-.}}

Revision as of 08:47, 31 March 2020

Monthly Operating Rept for Jan 1983
ML20064P006
Person / Time
Site: Robinson Duke Energy icon.png
Issue date: 02/02/1983
From: Norris H
CAROLINA POWER & LIGHT CO.
To:
Shared Package
ML20064N998 List:
References
NUDOCS 8302170070
Download: ML20064P006 (3)


Text