Encl'osure to Serial: RNPD/85-3472 Page 1 of 4 CPAL CO PLANT PERFORMANCE DATA SYSTEM PAGE i

RUN DATE 10/07/05 OPERATING DATA REPORT RPD36 RUN TIME 15;i8:06 ROBINSON UNIT 2 DOCKET NO. 050-0261 COMPLETED BY A.

E.

SCOTT OPERATING STATUS TELEPHONE (803)383-4524

i. UNIT NAME: ROBINSON UNIT 2 i NOIES There are presently 222 l

2.

REPORTING PERIOD: SEPTEMBER 85 i

Fuel Asscsublies in the Spent i

3.

LICENSED THERMAL POWER (MWT) 2300 l

Fuel Pool.

I 4.

NAMEPLATE RATING (GROSS MWE) 739.0 l

l S.

b. SIGN ELECTRICAL RATING (NET MWE) 700.0 i

i 6.

haX DEPENDABLE CAPACITY (GROSS MWE) 700.0 I i

7.

MAX DEPENDABLE CAPACITY (NET MWE) 665.0 8.

IF CHANGES OCCUR IN CAPACITY RATINGS (ITEMS 3 THRU 7) SINCE LAST REPORT, GIVE REASONS:

9.

POWER LEVEL TO WHICH RESTRICTED IF ANY (NET MWE) 92%

10. REASONS FOR RESTRICTION IF ANY: Core Peaking Factor limitations.

(EUI')

THIS YR TO CUMUL MONTH DATE ATIVE 1i. HOURS IN REPORTING PERIOD 720.00 6551.00 12778t.00

12. NUtiDER OF HOURS REACTUR CRITICAL 687.97 5650.72 89048.02 il. REACTOR RESERVE SHUTDOWN HRS 32.03 873.60 2810.67
14. HOURS GENERATOR ON LINE 669.80 5507.48 87573.43
15. UNIT RESERVE SHUTDOWN HOURS

.00

.00 23.20

16. GROSS THERMAL ENERGY GEN. (MWH) 1452278.88 11957539.92 174832774.08
17. GROSS ELEU. ENERI,Y

(, L N. (MWH) 4/9020.00 3920257.00 56265133.00

18. NET ELEC. ENERGY GENERATED (MWH) 454978.00 37202i2.00 53129873.00
19. UNIT SERVICE FACTOR 93.03 84.07 68.53
20. UNIT AVAILADTLITY FACTOR 93.03 04.07 60.55
21. UNIT CAP. FACTOR (USING MDC NET) 95.C2 85.40 62.52
22. UNIT CAP. FACTUR (USING DER NET) 90.27 81.13 59.40
23. UNIT FORCED OUTAGE RATE 6.97 13.18 15.04
24. SHUTDOWNS SCHED. OVER NEXT 6 MONTHS (TYPE, DATE, AND DURATION OF EACH)

Refueling Outage beginning February 01, 1986 for 49 days.

l

25. IF SHUlDOWN AT END OF REPORT PERIOD, ESTIMAlED DATE OF SIART UP
26. UNITS IN TEST STATUS (PRIOR TO COMMERCIAL OPERATION)

FCRCAST ACHEIVED IN11IAL CRITICALITY INITIAL ELECTRICITY CuritiERCI AL OPER A TION gOIB0242851009 R

ADOCK 05000gs3 PDR i.16 -9 l

Page 2 of 4 CP&L CO PLANT PERFORMANCE DATA SYSTEM PAGE i

RUN DATE 10/07/85 APPENDIX B - AVERAGE DAILY POWER LEVEL RPD39 RUN TIME 15:17:59 ROBINSON UNIT 2 DOCKET NO. 050-0261 COMPLETED BY A.

E.

SCOTT TELEPHONE (803)303-4524 GEPTEMBER 1985 DAY AVG. DAILY POWER LEVEL DAY AVG. DAILY POWER LEVEL (MUE-NET)

(MUE-NET) 1 719 17 302 2

719 18 270 3

715 19 456 4

711 20 724 l

5 696 21 727 6

697 22 729 7

690 23 730 8

6Y5 24

/31 9

697 25 729 10

/0Y 26

/31 11 656 27 731 12

-21 28 732 13 129 29 665 14 692 30 662 15

/26 16 730 1.16 - 8

Page 3 of 4 050-0261 DOCKET NO.

UNIT SHUTDOWNS AND POWER REDUCTIONS UNIT NAME H. B. Pobinson DATE 10-01-85 COMPLETED BY Anita E. Scott REPORT MONTil September TELEPHONE 803-383-4524

-c 5g 3

  • $5 Licensee

[g l%

Cause & Corrective No.

Date g

3g i

,s s &

Event g7 e-?

Action to

}L Prevent Recurrence H

j=

jg Reporiu mV 6

0901 850911 F

37.63 11 3

AB TPANSF Water fran Deluge System inadvertent-ly actuated "C" Main Transfonner fault pressure signal causing the Pcactor to trip. Unit was brought back on line and returned to full power.

0902 850917 F

12.58 A

3 EB INSTRU Reactor tripped due to a high voltage spike on instrument Buss #2.

Peactor was returned to full power.

I 2

3 4

F: Forced Reason:

Method:

Exhibit G -Instructions S: Scheduled A Equiprnent Failure (Explain) 1 Manual for Preparation of Data B-Mainte.1ance of Test 2-Manual Scrarn.

Entr> Sheets for Licensee C-Refueling 3-Autonutic Scrain.

Event Report (LER) File (NUREG-D-Regulatory Restriction 4-Other (Explain) 0161)

E-Operator Training & License Examination F Adnunistrative 5

G-Operational Erior (Explain)

Exhibit I Same Source 01/77)

Il-Other (Explain)

..