Osuuo SACRAMENTO MUNICIPAL UTluTY DISTRICT O 6201 S Street, P.O. Box 15830, Sacram' ento'CA 958521830.(916) 452-3211-AN ELECTRIC SYSTEM SERVlNG_THE HE' A RT OF CAllFORNIA

' - W O jj p O UNll al0: Sg AGM/NPP 89-204

-April 10, 1989 U. S. Nuclear Regulatory Commission Attn: J. B. Martin, Regional Administrator Region V 1450 Maria Lane, Suite 210 Halnut Creek, CA 94596 Docket No. 50-312 Rancho Seco Nuclear Generating Station License Nc. DPR-54 SPECIAL REPORT NUMBER 89-08: FIRE BARRIER BREACHED MORE THAN 7 DAYS

Dear Mr. Martin:

Fire barrier door AU '109 was not restored to operable status within the

' 7 days required by the Rancho' Seco Technical Specifications. The Sacramento Municipal Utility District hereby submits Special Report No. 89-08 in accordance with Technical Specification 3.14.6.2.

-Members of your staff with questions requiring additional information or clarification may contact Mr. Kurt Zimmermann at (209) 333-2935, extension 4627.

Sincerely,

!.A% Y Dan R. Keuter

%AssistantGeneralManager Nuclear Plant Manager Attachment cc w/atch: A. D'Angelo, NRC, Rancho Seco Document Control Oesk, Washington DC i

8904280076 890410 r gDR ADOCK0500g2 j ,

TSL Olo RANCHO SECo NUCLEAR GENERATING STATION D 14440 Twin Cities Road, Herald, CA 95638-9799;(209) 333 2935 I

, -)NL

.s>

SPECIAL REPORT NUMBER 89-08 Fire Barrier Breached More Than 7 Days Date of Occurrence

' March 11,11989 Plant' Conditions at Time of Occurrence

, .The plant was at cold shutdown.

Identification of Occurrence

' Fi re rier door AU 109 was not restored to operable status within the 7 days requbed by the Rancho Seco Technical Specifications.

Description of Occurrence On March 3,1989, security personnel identified that the closure device for fire barrier door AU 109 was not closing the door completely. Work Request 155418 was . initiated to repair the fire barrier door in accordance with Maintenance Procedure M.100 " Fire Barrier Door Maintenance." A delay in processing the Work Request through the maintenance work planning group

. contributed to the fire barrier door not being restored to operable status I within the required 7 days.

Corrective Action iaken An hourly firewatch was previously posted in the area and satisfied the-Technical Specification 3.14.6 requirement for the deficiency. The fire barrier door was restored to operable status on March 17, 1989. Fire barrier related Hork Requests are now being reviewed in the manager's daily plant status meetings. This review is designed to expedite the completion of the Work Requests.

l