ML20245D919
| ML20245D919 | |
| Person / Time | |
|---|---|
| Site: | Rancho Seco |
| Issue date: | 04/20/1989 |
| From: | Keuter D SACRAMENTO MUNICIPAL UTILITY DISTRICT |
| To: | Martin J NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V) |
| References | |
| 89-10, AGM-NPP-89-207, NUDOCS 8905010233 | |
| Download: ML20245D919 (2) | |
Text
___ _ _ -
l^
l;
(
MUD-SACRAMENTO MUNICIPAL UTIUTY DISTRICT O 6201 S Street, P.o. Box 15830, Sacramento CA 95852-1830,(916) 452-3211 l
AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA
{l AGM/NPP 89-207 April 20, 1989 ca as
.U. S. Nuclear Regulatory Commission Mi Attn:
J. B. Martin, Regional Administrator
- u m
- fd Region V T
m 1450 Maria Lane, Suite 210 yy,t3 og Halnut Creek, CA 94596 3
z
[
< o CD Docket No. 50-312 Rancho Seco Nuclear Generating Station License No. DPR-54 SPECIAL REPORT NUMBER 89-10:
INOPERABLE DELUGE SYSTEM Cear Mr. Martin:
The Hater Deluge System for Fire Zone 110 was not restored to operable status within the 14 days required by the Rancho Seco Technical Specifications.
The Sacramento Municipal Utility District hereby submits Special Report No. 89-10 in accordance with Technical Specification 3.14.3.2.
Members of your staff with questions requiring additional information or clarification may contact Mr. Kurt Zimmermann at (209) 333-2935, extension 4627.
Sincerely,
(
% Dan R. Keuter Assistant General Manager Nuclear Plant Manager Attachment cc w/atch:
A. D'Angelo, NRC, Rancho Seco Document Control Desk, Washington DC i
I \\
i I
8905010233 89042o
)
{DR ADOCK 05000312 f-PDC RANCHO SECO NUCLEAR GENERATING STATION D 1444o Twin Cities Road, Herald, CA 95638 9799;(209) 333-2935
w ~,
3:
9
.~
SPECIAL REPORT NUMBER 89-10 Inoperable Deluge System Date of Occurrence
-March 21, 1989 Plant Conditions at Time of Occurrence ihe plant was at 88% reactor power on March 21, 1989.
Identification of Occurrence The Water Deluge System for Fire Zone 110, Auxiliary Feedwater,
, Pump Area, was not returned to operable status within the 14 days requ..ed by the Rancho Seco Technical Specifications.
Description of Occurrence The spray and detection systems for Fire Zone 110 were removed from service
'following the January 31, 1989 AFH System overpressurization event in support of the evaluation of the-AFH pumps. The AFH System was declared operable on March 7,1989, plant heatup was initiated, and the detection system for Fire Zone 110 was-returned to operable status. On March 21, 1989, Onorations attempted to reset deluge valve FV-47100, but the valve faile' to reset. Work Request 145494 was initiated to rework the valve.
During ta. inspection of the valve, the rubber diaphragm was found to be damaged, thus preventing the valve from resetting.
l l
Corrective Action Taken An hourly fire watch was posted when the spray and detection systems were removed from service during cold shutdown.
The hourly fire watch was upgraded to a continuous fire watch prior to plant heat up.
Backup fire suppression was continuously provided for the AFH Pump Area.
The deluge valve was repaired under Hork Request 145494.
The Hater Deluge System for Fire Zone 110 was returned to operable status on April 8,1989.