Suppl to Special Rept 88-07:fire Sys Changed from Deluge Sys to Spray Type Sys.Auxiliary Feedwater Pump Motors Will Only Be Sprayed During Actual Fire Situation.Shrouding on Motor Vents Modified for Addl Protection Against Water Spray
ML20153F965
Person / Time
Site: Rancho Seco
Issue date: 08/23/1988
From: Keuter D
SACRAMENTO MUNICIPAL UTILITY DISTRICT
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
88-07, 88-7, AGM-NPP-88-446, NUDOCS 8809070557
Download: ML20153F965 (1)


Text

. *s e "SMUD sAcnAMaNTO MUNICIPAL UTILITY DitTRICT C 6201 S Street. P.o. Soun o 158N k CA 958521830. (916) 452 3211 AN ELECTRIC SYSTEgg JHE HEART OF CAllFORNIA 83 AUG 29 A$'O t

U. S. Nuclear Regulatory Commission Attn: J. B. Martin, Regional Administrator Region V i G0 Haria Lane, Suite 210  !

Halnut Creek, CA 94596 l ,

l l Docket No. 50-312 Rancho Seco Nuclear Generating Station License No. DPR-54 SUPPLEMENT TO SPECIAL 4EPORT NUMBER 88-07: INOPERABLE DELUGE SYSTEM 1

Dear Mr. Martin:

On April 11, 1988, the Sacramento Municipal Utility District submitted Special Report Number 88-07. The report dealt with Fire Zone 110 Hater -

Deluge System which protects the Auxiliary Feedwater (AFH) pump area. In the report the District comitted to perform deluge system spray tests of the AFH pump motors.

Since this commitment was made, the fire system has been changed from a deluge system to a spray type system. This change was made to limit the spray from the deluge system onto the AFH pump motors. The open head deluge type sprinklers which direct the spray ento the motors were replaced with closed head fusible link sprinklers. Because of the fusible links. l the AFH pump motors will only be sprayed during an actual fire situation.  !

The shrouding on the motor vents was modified for additional protection against water spray. This will allow the existing system to satisfy i Appendix R requirements. These modifications were completed and the i system returned to service on August 6, 1988.

Please contact me if you have any questions. Members of your staff with questions requiring additional information or clarification may contact Mr. Kurt Zimmermann at (916) 452-3211, extension 4627. 1 Sincerely, QM 8809070557 esosa3 DR ADOCK 05000312 m

g Dan R. Keuter MV Assistant General Manager, Nuclear Power Production "P5 g.M cc: A. D'Angelo, NRC, Rancho Seco Director of Nuclear Reactor Regulation, NRR, Washington

'fV