Special Rept 89-05:on 890221,Tech Spec Limit Exceeded.Caused by Fire Barrier Door AU 319 Not Being Restored to Operable Status within 7 Days Due to Door Sticking & Not Closing Properly.Fire Watch Established & Door Operability Restored
ML20247B757
Person / Time
Site: Rancho Seco
Issue date: 03/20/1989
From: Keuter D
SACRAMENTO MUNICIPAL UTILITY DISTRICT
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
89-05, 89-5, AGM-NPP-89-138, NUDOCS 8903300027
Download: ML20247B757 (2)


Text

m I

'ssuun SACRAMENTO MUNICIPAL UTILITY DISTRICT O 6201 S Street, P.O. Box 15830. Sacrarr. ento CA 958524830,(916) 452-3211 AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA AGM/NPP 89-138 March 20, 1989 U. S. Nuclear Regulatory Commission Attn:

J. B. Martin, Regional Administrator Region V 1450 Maria Lane, Suite 210 Walnut Creek, CA 94596 Docket No. 50-312 l

Rancho Seco Nuclear Generating Station l

License No. DPR-54 SPECIAL REPORT NUMBER 89-05: FIRE BARRIER BREACHED MORE THAN 7 DAYS

Dear Mr. Martin:

I l

F'~e barrier door AU 319 was not restored to operable status within the 7 days I

required by the Rancho Seco Technical Specifications.

The Sacramento l

Municipal Utility District hereby submits Special Report No. 89-05 in accordance with Technical Specification 3.14.6.2.

Members of your staff with questions requiring additional information or clarification may contact Mr. Kurt Zimmermann at (209) 333-2935, extension 4627.

1 Sincerely, pt ( {5L 20

D R. Keuter hAssistantGeneralManager Nuclear Plant Manager Attachment cc w/atch:

A. D'Angelo, NRC, Rancho Seco Document Control Desk, Washington DC 4 09033%O!k0 f

PDR l l RANCHO SECO NUCLEAR GENERATING STATION O 1444o Twin Cities Road; Herald, CA 95638 9799;(2o9) 333 2935 L______________

f 1

SPECIAL REPORT NUMBER 89-05 Fire Barriers Breached More Than 7 Days Date of Occurrence February 21, 1989 Plant Conditions at Time of Occurrence The plant was at cold shutdown.

Identification of Occurrence l

Fire barrier door AU 319 was not restored to operable status within the 7 days l

required by the Rancho Seco Technical Specifications.

j Description of Occurrence On February 12, 1989, security personnel. discovered that fire barrier door AU 319 was sticking and not closing properly.

Work Request 163175 was 1

initiated to repair the fire barrier door in accordance with Maintenance Procedure M.100 " Fire Barrier Door Maintenance." The procedure was being revised at the time and the repair of the door was delayed until the procedure revision was approved.

3 I

Corrective Action Taken An hourly firewatch was previously posted in the area and satisfied the 1

Technical Specification 3.14.6 requirement for the deficiency.

The fire barrier door was restored to operable status on March 3, 1989.

l l

1

)

_ _ _ - _ _ _ _ _ - -