Special Rept 88-14:on 880915,fire Barrier Penetrations Between Fire Areas 75/1 & 77/2 Not Returned to Operable Status within 7 Days.Caused by Insufficient Data in Design Drawings.Fire Watch Posted.Penetrations Restored by 881021
ML20207M124
Person / Time
Site: Rancho Seco
Issue date: 10/11/1988
From: Keuter D
SACRAMENTO MUNICIPAL UTILITY DISTRICT
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
AGM-NPP-88-518, NUDOCS 8810180121
Download: ML20207M124 (2)


Text

1

.')

VSMU-SACRAMENTO MUN6CIPAL UTluTY DISTRICT O P. O. Box 15830. Sacramento CA 95852 183o,(910) 452 3211 AN ELECTRIC SYSTEM SERVING THE HEART OF CAllFORNIA AGM/NPP 88-518 0 0T 1 1 1033 1

f I

U. S. Nuclear Regulatory Comission Attn:

J. B. Martin, Regional Administrator Region V 1450 Maria Lane, Suite 210 l

Halnut Creek, CA 94596 Docket No. 50-312 Rancho Seco Nuclear Generating Station License No. OPR-54 SPECIAL REPORT NUMBER 88-14: FIRE BARRIERS BREACHED MORE THAN 7 DAYS

Dear Mr. Martin:

Fire barrier penetrations between fire areas 75/1 and 77/2 were discovered to be unqualified configurations and were not restored to operable status within the 7 days specified in the Rancho Seco Technical Specifications. The Sacramento Municipal Utility District hereby submits Special Report No. 88-14 in accordance with Rancho Seco Technical Specification 3.14.6.2.

j Members of your staff with questions requiring additional information or clarification may contact Mr. Kurt Zimermann at (916) 452-3211, extension 4627.

Sincerely, i

i

)

Dan R. Keuter Assistant General Manager Nuclear Power Production Attachment cc w/atch:

A. D'Angelo, NRC, Rancho Seco I

Document Control Desk Hashington DC 8810180121 estogg (DR ADOCK 05000312 i

PDC l l RANCHO SECO NUCLEAR GENERATING STATION O 1444o Twin Cnies Road, Herald, CA 95638 9799;(209) 333 2935 I

/

. !?

SPECIAL REPORT NUMBER 88-14 Fire Barriers Breached More Than 7 Days Date of Occurrence September 15, 1988 Plant Conditions at Time of Occurrence The plant was at approximately 80% power on September 15, 1988.

Identification of OccurreEt Fire barrier penetrations between fire areas 75/1 and 77/2 were not I

returned to operable status within 7 days as required in Technical Specification 3.14.6.2.

Descriotion of Occurrence On August 17, 1988, during the performance of Surveillance Procedure SP.1006 "Refueling Interval Fire Barrier Penetrations," a technician identified three unlisted fire barrier penetrations between fire areas 75/1 and 77/2. An evaluation completed by Nuclear Engineering on 4

September 1, 1988, disclosed that the fire barrier penetrations were unqualified configurations in that insufficient data existed in design drawings to document the fire ratings of the penetrations.

Corrective Action Taken An hourly firewatch was previously posted in the area and satisfied the Technical Specification 3.14.6 requirement for the deficiency.

The fire barrier penetrations will be restored to operable status by October 21, 1988.

)