- Wen, q-. _
ne SACRAMENTO MUNICIPAL UTILITY DISTRICT C P. O. Box 15830, Sacramedid, K:AyS5852-1830, (916) 452-3211-AN ELECTRIC SYSTEM SERvlNGiTH$ HEART, OF CALIFORNIA '
~ j# CO NOV 0 3-1987 AGM/NPP 87-337 Y-RVir j
-l
/
J U. S. Nuclear Regulatory Commission l
Attn:
J. B. Martin, Regional Administrator Region V 1
Office of Inspection and Enforcement j
1450 Maria Lane, Suite 210 l
Halnut Creek, CA 94596 l
l DOCKET NO. 50-312 RANCHO SECO NUCLEAR GENERATING STATION LICENSE NO. DPR-54 1
SPECIAL REPORT NUMBER 87-22:
ISOLATION OF CO2 SYSTEMS 1
Dear Mr. Martin-i j
Various CO zones were isolated in order to perform preventive maintenance j
2 and repairs.
They were not restored to operable status within the 14 days
]
specified in the Rancho Seco Technical Specifications.
In accordance with Technical Specification Sections 3.14.4 and 6.9.5.E the Sacramento Municipal Utility District hereby submits Special Report 87-22 describing the problem, i
4 l
corrective action taken, and schedule for restoring the-systems to operable status.
Please contact me if you have any questions. Members of your staff with questions requiring additional information or clarification may contact Kurt Zimmermann at (916) 452-3211, extension 4627.
Sincerely, Joseph F. Firlit Assistant General Manager, Nuclear Power Production 8711130010 871103 Attachment PDR ADOCK 05000312 -
S PDR cc:
G. Kalman, NRC, Bethesda ;
(w/atch)
A. D'Angelo, NRC, Rancho Seco (
)
F. J. Miraglia, NRR, Bethesda (
)
, l r E,2 L RANCHO SECO NUCl. EAR GENERATING STATloN O 1444o Twin Cities Road, Herald, CA 95638-9799;(209) 333-2935-1
.b
-l ; >.
SPECIAL REPORT NUMBER 87-22 ISOLATION OF CO2 SYSTEMS-Date of Reoort November 3,1987 Date of Occurrence October 13, 1987 Plant Conditions Prior to Occurrence The plant has been in a major outage with the reactor in cold. shutdown.
Identification of Occurrence The following CO zones were not restored'to. operable status within 14' days' 2
as specified in Technical Specifications Section 3.14.4.
Zone 11 16 38 76 12 17 39 77 13 19 40.
78 14 36 41
'79 15 37 75 80 i
Description of Occurrence On September 29, 1987, the CO2 zones' listed above were' isolated (removed from service) in order to perform preventive maintenance and repairs on the1 system main isolation valve and various zone CO2 discharge selector valves.
l Corrective Action Taken l
Firewatches were established in accordance with Technical Specification Section 3.14.4.
The systems discussed above will be restored to operable i
status upon the completion of the preventive maintenance and modification activities scheduled for December 31, 1987.
4 f