1 SMUDl IL SACRAMENTO MUNICML UTILITY DISTRICT C 6201 S Street. P.o. Box 16830, Secremento CA 96862 1830 (916) 462 3211-AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA,
li L
.AGM/NUC.90-1$1-May 21,11990
'T
'U. S.'. Nuclear Regulatory Commission Attn:
J. B. Martin, Regional Administrator Region V 1450 Maria Lane. Suite 210
~Halnut Creek, CA 94596 Docket No. 50-312 Rancho Seco Nuclear Generating' Station License No. DPR-54 SPECIAL REPORT 90-09:
FIRE. BARRIERS BREACHED I40RE THAN 7 DAYS
Dear.Mr. Martin:
In accordance with Technical Specification 3.14.6.2, the District hereby
. submits Special. Report 90-09.,This special report discusses fire barriers in
.the-Auxiliary Building, Turbine Building', and Nuclear Service Electrical Building which became: inoperable'but were not returned to service within 7 days as-required by Technical Specification 3.14.6.2.
-Members of your. staff with questions requiring additional information or
-clarification may contact Ed'Benntst at (209) 333-2935, extension 4648.
s,
~ Sincerely,,
O 4d
.h [
_?
Dan'R. Keuter Assistant General Manager
' Nuclear i
Attachm0'nt cc w/atch:
.A. D'Angelo, NRC, Rancho Seco
\\
/00cument Control Desk, Hashingto OC 9005290214 900521 f
PDR ADOCK 05000312
(
S PDC j
'RdNCHO SECO NUCLEAR GENERATING' STATION O 14440 Twin Cities Road, Herald, CA 95638 9799: (209) 333 2935
- g. ' >
j
g
..-e
' f~
ATTACHMENT-SPECIAL REPORT NUMBER 90-09 g -
Fire Barriers Breached More Than 7 Days Date of Occurrence See Table 1.
Plant Conditions' at the Time of Occurret.ra The plant has been shutdown since June 7, 1989, and is in a defueled condition.
Identification of the Occurrence The fire barrier penetrations in the Auxiliary Building, Turbine Building, and
-Nuclear Service' Electrical Building listed in Table I were not restored to operable status within 7 days as required by Rancho Seco Technical Specification 3.14.6.2.
TABLE l' Fire-Barriers in the Auxiliary Building, Turbine Building, and Nuclear Service Electrical Building that f ailed SP.713 and SP.717 Oste Returned Date of Door /
Penetration Operable Occurrence EtagirAL19H Elevation Failed Status 04/24/90-16-17AB 34'-9" 04/17/90-04/27/90 04/24/90 17-29AE 35'-3" 04/17/90 04/27/90 04/24/90 17-18AE 36'-0" 04/17/90 04/27/90 04/24/90 2203-28'-5" 04/17/90 04/27/90 04/24/90 DOOR NS358 04/17/90 05/02/90
-04/25/90 1-17AL 40'-0" 04/18/90 04/27/90 04/25/90' 1-17AE 40'-0" 04/18/90' 04/27/90 04/25/90 17-18AC 37'-3" 04/18/90 04/27/90 04/25/90 17-18AD 37'-3" 04/18/90 04/27/90 04/25/90 17-18AA 32'-3" 04/18/90 04/27/90-04/25/90 17-18AB 34'-9" 04/18/90 04/27/90 04/30/90 000R NS233 04/23/90 05/02/90 05/01/90 000R NS241 04/24/90 05/03/90 05/0',/90 000R AUB061 04/25/90 05/04/90
. 05/02/90 000R NS159 04/25/90 05/09/00
, m'
c' s
'ATTAC N NT (Continued)
Description of the Occurrence P.713
'The penetrations and doors listed in Table i failed surveillance tests :
" Refueling Interval Fire Barrier Penetrations (Auxiliary Building anc' i. -bine Building, Mezzanine)" or SP.717 " Refueling Interval Fire Barrier Survu $1ance Procedure (Fire Door Assemblies-Nuclear Services riectrical Building)" due to normal degradation.
Corrective Actions Taken Operability of fire detectors was verified on at least one side of the breached barriers and hourly fire watches were established in accordance with Technical Specification 3.14.6.2.
All penetrations and doors have been returned to operable status as noted in Table 1.