_ _ _ - _ _

I u.dl' Msuun a3ro SACRAMENTO MUNICIPAL UTILITY DISTRICT.O P. O. Box 15830 Sacramento MM$1830,~ (916) 452 32? 1 4-AN ELECTRIC SYSTEM SERVING THE HEART OF CALIFORNIA SEP 151987 I 81 SEP !b P l2: 58 l

F

.'GCA 87-574-j l

.U. S. Nuclear Regulatory Commission j

Attn:

J. B. Martin, Regional Administrator

]

Region V

' Office of Inspectio, and Enforcement

)

1 1450 Maria Lane, Suits 210

>Halnut Creek, CA 94596 l

DOCKET NO. 50-312 j

/

RANCHO SECO. NUCLEAR GENERATING STATION i

LICENSE NO. DPR-54 SPECIAL REPORT NUMBER 151-17 DIESil FIRE PUMP INOPERABILITY l

Dear Hr. Martin:

l 1

Tho' diesel fire'putop was inoperable for over.the seven days specified in j

Technical Specification 3.14.2.2.

Thus, in accordance with Technical Specifications 3.14.2.2 and 6.9.5.E, the Sacramento Municipal Utility District hereby roubmits Special Report 87-17 describing the problem and corrective actions taken, j

If there are any questions concerning this report, please contact s

f

'Mr. Kurt Zimmermann at (916) 452-3211, extension 4627.

Sincerely,.

tb c)twx4

.. F O'. Carl And(griini Chief Executive Officer, Nuclear I

Attachment Qo '

G. Kalman, NRC, Bethesda (w/atch) cc:

A. D'Angelo, NRC, Rancho Seco (

)

F. J. Miraglia, NRR, Bethesda (

)

j G709230524 070915 gDR ADDCK 05000312 1

7dA l

RANCHO SECO NllCLEAR GENERATING STATION O 14440 Twire Cities Road, Herald, CA 95638 9799;(209) 333 2935

SPECIAL REPORT #87-17 DIESEL FIRE PUMP INOPERABILITY Dale of Report September 14, 1987 Date of Occurrente August 24, 1987

(

Plant Conditions Prior to Occurrence The plant has been in a major outage with the reactor in cold shutdown.

Identification of Occurrence h

The following fire protection component was not restored to operable status within seven (7) days as specified in Technical Specifications Section 3.14.2.2.

Diesel Drive Fire Pump P-996 Description of Ociprrence On August 17, 1987, the diesel driven fire pump was removed from service to investigate high temperatures on the pump's outboard bearing.

Corrective Actions Taken The motor driven fire pump, P-440, was verified operable at the time P-996 was removed f om service.

P-996 was restored to operable status on September 4, 1987 following bearing replacement and satisfactory surveillance testing.