ML20235S200

From kanterella
Jump to navigation Jump to search

Ack Receipt of Util Transmitting Proposed Amend to Physical Security Plan,In Response to Miscellaneous Amends & Search Requirements.Response to Encl Comments on Physical Security Plan Changes Requested within 30 Days
ML20235S200
Person / Time
Site: Rancho Seco
Issue date: 09/29/1987
From: Kalman G
Office of Nuclear Reactor Regulation
To: Andognini C
SACRAMENTO MUNICIPAL UTILITY DISTRICT
References
TAC-65217, NUDOCS 8710080364
Download: ML20235S200 (3)


Text

n 4

p, t.-

Docket Noe 50-312 gg gg g

.Mr.LCarl Andognini l

Chief Executive Officer, Nuclear l

Sacramento Municipal Utility District Rancho Seco Nuclear Generating Station

-14440 Twin Cities Road Sacramento, California' 95638-9799 L

Dear Mr. Andognini:

[

I

SUBJECT:

MISCELLANE0US AMENDMENTS / SEARCH REQUIREMENTS RANCHO SEC0 NUCLEAR GENERATING STATION, UNIT 1 (TAC #65217) i l

l This'is to acknowledge receipt of the Sacramento Municipal Utility District

)

letter, dated November 24, 1986, which transmitted a proposed amendment i

to the Rancho Seco Nuclear Generating Station Physical Security Plan, in response to the Miscellaneous Amendments and Search Requirements.

The submitted document has been reviewed and we have determined that additional

)

information and revisions to the plan are required prior to our approval. The j

enclosed comments are based upon pertinent NRC regulations and published guidance-

)

L describing methods, acceptable to the NRC staff, for implementing specific parts 1

of those regulations.

It is requested that you provide your-response to these comments within 30 days from receipt of this letter.

The reporting and/or record keeping requirements contained in this letter affect fewer than ten respondents; therefore, OMB clearance is not required i

under P.L.96-511.

Should you have any questions concerning the enclosed comments, please contact the reviewer, Gene McPeek, at (301) 492-4968.

l Sincerely, e710080364 e70929 George Kalman, Project Manager PDR ADOCK 050003 2 Project Directorate V PD F

Division of Reactor Projects III, IV, V and Special Projects

]

Office of Nuclear Reactor Regulation

Enclosure:

DISTRIBUTION W/ ENCLOSURES:

Physical Security Plan Comments RSGB rf Sec rf G. McPeek CBuracker(2) cc w/ enclosure:

Region V J. Lee See next page G. Kalman Docket ~Filei50312l Case File NRC PDR~

RErickson Local PDR PStarcher LBush I

fh

^

t%

P D V]

....... _ :: P DV jy DFC :RSGB ]

RSGB p __..:lRSGfga..( A..__.:...._____:

RSG e.

NA McP k

.CBuracker

LBusb
REr on

(

GKal n

,g,

...........f....._______:7/fp/87............:h......__.::fl/7l/87

/Jy/87 t)3/87 DAT

/87

$87 q

Mr. G. Carl Andognini Rancho Seco Nuclear Generating Chief Executive Officer, Nuclear Station Sacramento Municipal Utility District I

cc:

Mr. David S. Kaplan, Secretary Mr. John Bartus and General Counsel Ms. JoAnne Scott Sacramento Municipal Utility Federal Energy Regulatory Commission District 825 North Capitol Street, N. E.

6201 S Street-Washington, D.C.

20426 P. O. Box'15830-I

' Sacramento, California 95813 Thomas A. Baxter, Esq.

Shaw, Pittman, Potts & Trowbridge 2300 N Street, N.W.

Washington, D.C.

20037 Mr. John V. Vinguist Acting Manager, Nuclear Licensing Sacramento Municipal Utility District 1

Rancho Seco Nuclear Generating Station 14440 Twin Cities Road Herald, California 95638-9799 Mr. Robert B. Borsum Babcock & Wi1~ox c

Nuclear Power Generation Division Suite 220, 7910 Woodmont Avenue Bethesda, Maryland 20814 Resident Inspector / Rancho Seco c/o U. S. N. R. C.

14440 Twin Cities Road Herald, California 95638 Regional Administrator, Region V U.S. Nuclear Regulatory Commission i

1450 Maria Lane, Suite 210 Walnut Creek, California 94596 Mr. Joseph 0. Ward, Chief Radiological Health Branch State Department of Health Services 714 P Street, Office Building #8 Sacramento, California 95814 Sacramento County Board of Supervisors 827 7th Street, Room 424 Sacramento, California 95814 Ms. Helen Hubbard P. O. Box 63 Sonol, California 94586

~

l Docket No. 50-312 1

COMMENTS ON PHYSICAL SECURITY PLAN CHANGES I

(MISCELLANEOUS AMENDMENTS AND SEARCH REQUIREMENTS)

RANCHO SECO NUCLEAR GENERATING STATION UNIT NO. 1 State that vital area access controls will not be dropped for life threatening situations not involving public health and safety.

Reference 10 CFR 50.54(x) and (y) and Generic Letter 87-08 (Q&A #3).

Provide a commitment that the search requirements will be implemented within 60 days after Commission approval of the proposed revisions.

Reference 10 CFR 73.55(d)(1).

Provide a commitment that if security force members leave the protected area to perform official duties subsequent to their initial entry and search, they will be searched prior to re-entry into the protected area if they have not been under direct observation or accompanied by another member of the security force.

Reference 10 CFR 73.55(d)(1) and Generic Letter 87-08 (Q&A

  1. 11).

Provide a commitment that an access authorization system will be established to limit unescorted access to vital areas during non-emergency conditions to those individuals required to perform specific duties.

Reference 10 CFR 73.55(d)(7)(i).

Provide a commitment that a current authorization access list will be established for each vital area.

Reference 10 CFR 73.55 (d)(7)(1)(A).

Provide a commitment that vital area access lists shall be updated and reapproved by the cognizant manager / supervisor at least every 31 days.

Reference 10 CFR 73.55(d)(7)(1)(A).

Provide a commitment to periodically (annually) review physical security and contingency plans and procedures to evaluate their potential impact on plant and personnel safety.

Reference 10 CFR 73.55(d)(7)(ii)(B) and Regulatory Guide 5.65.

Provide a commitment that the secondary power supply systems for both the alarm annunciator equipment and non portable communications equipment shall be located within a vital area.

Reference 10 CFR 73.55(e)(1) and Generic Letter 87-08 (Q&A #16).

Indicate what components of the secondary power supply system will be protected as vital.

Reference 10 CFR 73.55(e)(1) and Generic Letter 87-08 (Q&A #18).

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _