'May 30 1989 0
Docket No.: 50-312 Mr. Joe Firlit Chief Executive Officer,. Nuclear
-Rancho Seco Nuclear. Generating Station 14440 Twin Cities Road Herald, California 95638-9799
Dear Mr. Firlit:
SUBJECT:
SAFETY EVALUATION FOR GENERIC LETTER 83-28, ITEM 4.5.2 (REACTOR TRIP SYSTEM RELIABILITY - ON-LINE TESTING) FOR RANCHO SECO NUCLEAR GENERATINGSTATION(TACNO.54019)
Generic Letter 83-28, Item 4.5.2 required licensees and applicants, with plants not currently designed to permit on-line testing of the reactor trip system, to justify not making modifications to permit such testing.
By letter dated November 4,1983, you submitted a response to Generic Letter 83-28, Item 4.5.2.
In our enclosed safety evaluation, the NRC staff concludes that your response to Item 4.5.2 is acceptable. Therefore, we consider Item 4.5.2 to-be complete.
It should be noted that Item 4.5.2 and 4.5.3 of Generic Letter 83-28 have been assigned the NRC. Technical Assignment Control (TAC) number 54019. The TAC will remain open until Item 4.5.3 is closed as well.
Sincerely,
/s/
George Kalman, Project Manager Project Directorate V Division of Reactor Projects - III, IV, Y and Special Projects Office of Nuclear Reactor Regulation
Enclosure:
As stated cc w/ encl:
See next page DISTRIBUTION
" Docket F11ea GKalman BGrimes SNewberry i
NRC & LPDRs SReynolds ACRS(10)
PD5 Reading SJuergens GKnighton MVirgilio' OGC BLMozafari JLee EJordan DLasher P/PD5 DRSP/PD5s4 DRSP/PD5QA./
DR PD5 DES ICB DR k D5 0Fo/
SJuergens.@
SReynoldf G
n SNew erry G
i 4 ton 1
5
/89 5/l0/89 5/h /89
/89 5/p789 5/yJ/89 i
8906060113 890530 7
DR ADOCK 0500 l
i
_. Y'*UGUq jg k
UNITED STATES a
8' -
g NUCLEAR REGULATORY COMMISSION N
.j WASHINGTON, D. C. 20555
%*****/
s May 30, 1989 Docket ilo.: 50-312 Mr. Joe Firlit Chief Executive Officer, Nuclear Rancho Seco Nuclear Generating Station 14440 Twin Cities Road Herald, California 9Eo38-9799
Dear Mr. Firlit:
SUBJECT:
SAFETY EVALUATION FOR GENERIC LETTER 83-28 ITEM 4.5.2 (REACTOR-TRIP SYSTEM RELIABILITY - Oll-LINE TESTING),FOR RANCHO SECO NUCLEAR GENERATINGSTATI0!i(TACNO.54019)
Generic Letter 83-28, Item 4.5.2 required licensees and applicants, with plants not currently designed to permit on-line testing of the reactor trir, system, to justify not making modifications tc permit such testina.
By letter datec November 4,1983, you r,ubmitted a response to Generic Letter 83-28 Item 4.5.2.
In our enclosed safety evaluation, the t;RC staff ccncludes that your response to Iteni 4.5.2 is acceptable..Therefore, we consider Item 4.5.2 to be complete.
It should be noted that Item 4.5.2 and 4.5.3 of Generic Letter 83-28 have been t.ssigned tt'e flRC Technical Assignment Centrol (TAC) number 54019. The TAC will remain open until Item 4.5.3 is closed as well.
~
Sincerely, Ap
^;-
George Kalman, Project Hanager Project Directorate V Division of Reactor Projects - III, IV, Y and Special Projects Office of Nuclear Reactor Regulation
Enclosure:
l As stated I
cc w/ enc 1:
i See next page i
m I
- 4,'
-Mr. Joe Firlit-Rancho Seco Nuclear Generating Station cc:
Mr. David S. Kaplan ' Secretary Mr. John Bartus and General Counsel Ms. JoAnne Scott Sacramento Municipal Utility District
' Federal Energy Regulatory Comission' 6201 S Street 825 North Capitol Street, N. E.
P.O.' Box 15830 Washington, D.C.
20425 Sacramento, California 95813
' Thomas A..Baxter, Esq..
Ms.-Helen Hubbard.
Shaw, Pittman, Potts & Trowbridge.
P. O. Box 63 2300 N Street, N.W..
Sunol, California 94586 i-Washington, D.C.
20037 Mr. Steven Crunk L
Menager, Nuclear Licensing Sacramento Municipal Utility District.
Rancho Seco Nuclear. Generating Station 14440 Twin Cities Road Herald,. California 95638-9799 Mr. Robert B. Borsum,. Licensing Representative Babcock & Wilcox Nuclear Power Division 1700 Rockville Pike - Suite 525 Rockville, Maryland' 20852 Resident Inspector / Rancho Seco c/o U. S. N. R. C.
14440 Twin Cities Road Herald, California 95638 Regional'Aoniinistrator, Region V U.S. Nuclear Regulatory Comission 1450 Haria Lane, Suite 210 Walnut Creek, California 94596 Mr. Paul Szalinski, Chief Radiological Health Branch State Department of Health Services 714 P Street, Office Building #8 Sacramento, California 95814 Sacramento County
- Board of Supervisors 700 H Street, Suite 2450 Sacramento, California 95814
_-___ ______-___ _ __