L-86-506, Monthly Operating Repts for Nov 1986

From kanterella
(Redirected from ML20211P015)
Jump to navigation Jump to search
Monthly Operating Repts for Nov 1986
ML20211P015
Person / Time
Site: Saint Lucie, Turkey Point, 05000000
Issue date: 11/30/1986
From: Grant N, Woody C
FLORIDA POWER & LIGHT CO.
To:
NRC OFFICE OF RESOURCE MANAGEMENT (ORM)
References
L-86-506, NUDOCS 8703020271
Download: ML20211P015 (18)


Text

..

l AVERAGE DAILY UNIT POWER Livst DOCKET NO. 10

  • UNIT Turkey Point 3 DATE Daepmher 19, 1986 COMPLETED BY N.W. Grant TELEPHONE (305) 694- 44~32 MONTH Mnvamhar- 14R6 DAY AVERACE DAILY POWER LEVEL (MWe Nes) 11/ 1/86 687 11/ 2/86 690 11/ 3/86 687 11/ 4/86 667 11/ 5/86 575 11/ 6/86 685 11/ 7/86 686 11/ 8/86 692 31/ 9/86 694 11/10/06 694 11/11/86 693 11/12/86 692 11/13/86 607 11/14/86 684 11/15/06 689 11/16/86 685 11/17/86 688 11/18/86 686 11/19/86 683 11/20/86 680 11/21/86 683 11/22/86 687 11/23/86 695 11/24/86 693 11/25/86 694 11/26/86 690 11/27/06 690 11/28/86 688 11/29/86 688 11/30/86 686 P888&isung PDH Q\ o\

j

OPERATING DATA REPORT DOCKET NO 50 - 250 DATE 12/11/86

'. COMPLETED BY N. W. GRANT TELEPHONE- 305/694/4432 OPERATING STATUS .

1. UNIT NAME: TURKEY POINT UNIT 3
2. REPORTING PERIOD: NOVEMBER 1986
3. LICENSED THERMAL POWER (MWT): ______________ 2200
4. NAMEPLATE RATING (GROSS MWE): ______________. 760
5. DESIGN ELECTRICAL RATING (NET MWE): ________ 693
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): ___ 700
7. MAXIMUM DEPENDABLE CAPACITY (NET MWE): _____ 666
8. IF' CHANGES DCCUS IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7)

SINCE LAST REPORT, GIVE REASONS: ________________________________________

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE)________________________
10. REASONS FOR RESTRICTIONS, IF ANY: _______________________________________

MONTHLY -YTD- CUMULATIVE

11. HOURS IN REPORT PERIOD: _________________ 720 8016 122625.6
12. NUMBER OF HOURS REACTOR WAS CRITICAL _____ 720.0 6354.5 85432.2
13. REACTOR RESERVE SHUTDOWN HOURS __________ 0.0 0.0 844.4
14. HOURS GENERATOR ON-LINE _________________ 720.0 6187.0 84593.8
15. UNIT RESERVE SHUTDOWN HOURS _____________ 0 0 121.8
16. GROSS THERMAL ENERGY GENERATED (MWH) ____ 1577530 13250005 175455526
17. GROSS ELECTRICAL ENERGY GERERATED (MWH) _ 516300 4303591 56175136

- 18. NET ELECTRICAL ENERGY GENERATED (MWH) ___ 492379 4075738 53185319

19. UNIT SERVICE FACTOR ____;________________ 100.0 77.2 69.0
20. UNIT AVAILABILITY FACTOR ________________ 100.0 77.2 69.1
21. CAPACITY FACTOR (USING MDC NET) _________ 102.7 76.3 66.6
22. CAPACITY FACTOR (USING DER NET) _________ 98.7 73.4 62.6
23. UNIT FORCED OUTAGE RATE _________________ 0 18.1 7.9
24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS :

REFUELING 3/5/97, 81 DAYS ______________________________________________

25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: ________

s DOCKET NO. 50-250 UNIT SHUTDOWNS AND POWER REDUCTIONS UNIT NAME Turkey Point Unit #3 DATE )ecember 12. 1986 COMPLETED BY 4. W. Grant REPORT MONTH November. 1986 TELEPHONE (305) 694-4432

, 5? "h

)g5Ei Licensee E

% L Cause & Corrective h Date i 3g i 2 Event u '2 k"l Action to

$5 $ j di g Report a rE C  !' Prevent Recurrence S

Unit #3 had no shutdowns or significant power reductions.

I I 2 3 4 F Foiced Reason : Method: Exhibit G -Instructions 5 Scheduled A Lquipment Failure (Explain) 1-Manual for Preparation of Data B-Maintenance or Test 2-Manual Scrarn. Entry Sheets for Licensee C-Refueling 3-Automatic Scram. Event Report (LER) File (NUREG-4 D Regulator) Restriction 9 Other (Explain) 0161) 1.-Operator Training & License Eumination F- Administ rative p ,

5 G-Operaticnal I i ror ( F splam ) 4- . /. 4a 4 4 eve.,..es Exhibit I Same Source t'8/77) Il-Ot her ( E xplaini l

1

SUMMARY

OF OPERATING EXPERIENCE DOCKET NO.- sn_pso UNIT Turkey Point Unit }__

DATE December 12. 1986 COMPLETED BY N. W. Grant TELEPHONE (305) 694-4432 REP RT HONTH November. 1986 Unit #3 operated at essentially full power and had no " unit shutdowns or significant power reductions."

l

Am

.: AVER AGE DAILY UNITPOWER LivrL DOCKET NO. 50-251 g,7 Turkey Point 4 DATE Decomhor 17, 1986 COMPLETED BY

, . ant TELEPHONE MONTH November. 1986 DAY AVERAGE DAILY POWER LEVEL (MWe Net) 11/ 1/86 218 11/ 2/86 592 11/ 3/86 686 11/ 4/86 688 11/ 5/86 689 11/ 6/86 687 11/ 7/86 688 11/ 8/86 691 11/ 9/86 692 11/10/86 281 11/11/86 416 11,'12/86 617 l 11/13/86 680 l 11/14/86 368 11/15/86 686 11/16/86 685 11/17/86 695 11/18/86 498 11/19/86 563 11/20/86 679 11/21/86 678 l

11/22/86 603 I 11/23/86 692 11/24/86 689 11/25/86 690 11/26/86 692 11/27/86 695 11/28/86 694 11/29/06 692 11/30/86 688

,t OPERATING DATA REPORT DOCKET NO 50 - 251

. DATE 12/11/86 COMFLETED BY N. W. GRANT TELEPHONE. 305/694/4432 OPERATING STATUS -

1. UNIT'NAME: TURKEY POINT UNIT 4
2. REPORTING PERIOD NOVEMBER 1986
3. LICENSED THERMAL POWER (MWT): ______________ 2200
4. NAMEPLATE RATING (GROSS MWE): ______________ 760
5. DESIGN ELECTRICAL RATING (NET MWE): ________ 493
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): ___ 700
7. MAXIMUM DEPENDABLE CAPACITY (NET MWE): _____ 666
8. IF CHANGES OCCUS IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7)

SINCE LAST REPORT, GIVE REASONS: ________________________________________

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE)________________________
10. REASONS FOR RESTRICTIONS, IF ANY: _______________________________________

MONTHLY -YTD- CUMULATIVE

11. HOURS IN REPORT PERIOD: _________________ 720 8016 116357.0
12. NUMBER OF HOURS REACTOR WAS CRITICAL _____ 706.4 2304.2 79939.3
13. REACTOR RESERVE SHUTDOWN HOURS __________ 0.0 0.0 166 6
14. HOURS GENERATOR ON-LINE _________________ 702 1 2087.9 77183.0
15. UNIT RESERVE SHUTDOWN HOURS _____________ 0 0 32.1
16. GROSS THERMAL ENERGY GENERATED (MWH) ____ 1459367 4184009 163221738
17. GROSS ELECTRICAL ENERGY GERERATED (MWH) _ 471225 1334266 51976838
18. NET ELECTRICAL ENERGY GENERATED (MWH) ___ 448349 1236869 49198077
19. UNIT SERVICE FACTOR _____,_______________ 97.5 26.0 66.3
20. UNIT AVAILABILITY FACTOR ________________ 97.5 26.0 66.4
21. CAPACITY FACTOR (USING MDC NET) _________ 93.5 23.2 64.9
22. CAPACITY FACTOR (USING DER NET) _________ 89.9 22.3 61.0
23. UNIT FORCED OUTAGE RATE _________________ 2.5 13.4 6.7
24. SHUTD,0WNS SCHEDULED OVER NEXT 6 MONTHS :
25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: ________

i t

I

)

4

. . . . . ,.,,-__.,--,--,,.,~.,_.4., ,..__,,,- , ~ ,_., m .,,_,m.m .v.- m.,_ ,.,.m. ,v _ _ ,.__ m.- - , m e w.-._..my,_.m,ww,w_mm__,.

PAGE 1 of 2 .,

DOCKET NO. 50-251 -

UNIT SHUTD0wNS AND POWER REDUCTIONS UMT NABIE Turkov Po- nt Uni t 4.

i DATE 3ecember .2. 1986 REPORT MONDg N n vomh p r . 1986 (30 5 -

432 i

e  % =3 g

\

E:

e.

E gsx Licensee ge, ca.,, a co,,,c,g,,

km,

{

No. Dale ij g it ,gg& Event sg Action lo

" $3 E jiEj R*P"'8 EU f'g Prevent Recurrence 6

i 4 HC HTEXCH The return to full power i 10 861023 F 0.0 H operation from the outage l to inspect for condenser

! 1eaks was delayed for l secondary chemistry control

and condenser leak checking.

1 17.9 3 251-86-25 HH VALVEX The reactor tripped foT10 wing 11 861110 F A i

' the failure of a solenoid i coil in a feedwater flow control valve which resulted l in low steam generator level.

l The coil was replaced,and full

! power operation was resumed

! after. a hold for secondary 2

ch'emistry control, I

! I 2 3 4 F Forced Reason: Method: Exhibit G . Inseructions i S Scheduled A Equipenent Failure (Explain) l-Manuel for Preparation of Data B-Maintenance of Test 2-Manuel Scrasn. Entry Sheets for Licensee 1

I C Refueling 3-Autosnatic Scrain. Event Report iLER) File INUREG-D-Regulator) Reser.ction $4ther(Explaen) 01611

! I -Operator Tsaining A Ucens I samination ,

1 F Adnunistrative 5

  • G Operatiinul I reur IF splain I c . /.e a sadowca..,# Exhibit I Same Source l'8/77) II-Other i Laplain) j

i 4

PAGE 2 of 2 UNIT 5HUTDOWNS AND FOWER REDUCDONS DOCKET NO. 50-251 UNIT NAME Turkey Po- nt Unit 4 DATE December .2, 1986 I

COMPLETED ay fl . W. Grant f REPORT MONTH N o ve mb e r , 1986 1ELEPHONE (305) 694-4432

- l "i

E' E_ E 3 Licensee E, Cause & Corrective No . Date h 3g ( )YkyE Event E? kw. Action to

  • $. E jiji g d

Repor

  • mO f'l Prevent Recurrence 12 861118 F 0.0 A 5 HH VALVEX Power was reduced to approximately 10% to repair the 4A feedwater regulator valve which had'a problem wi th the positioner.

Following repairs and a secondary chemistry hold, the unit returned to full power operation.

l l 3 4 f Forced Reason: Method: Exhibit G Instructions S Scheduled A Equiprnent Failure (Explain) 1-Manual for Preparation of Data B Maintenance of Test 2 Manual Scram. Entry Sheets for Licensee C-Refueling 3 Automatic Scram. Event ReporI (LER) File (NUREG-D-Regulatory Rest iction @Osher(Explain) 0161) 1.-Operator Training & Ucense Examination ,

F-Adnunist rative 5 G Operatomal I r ror iF splain > g _ f.e ao 44em..,# Exhibit I Same Source l'8/77) ll Other (Explain) i -

~

SUMMARY

OF OPERATING EXPERIENCE DOCKET NO. 50-251 UNIT Turkey Point Unit 4 DATE _ Decembe r 12. 1986 COMPLETED BY N v. Grant TELEPHONE f100 694-4432 REP RT HONTH November, 1986 See the " unit shutdown and power reductions" report.

,-,,,-,,..,,,-.,,~w.,,-- _ -.- ,,- -,--.-- ,-a, , - . - - . . , --.,. - _ . _ , _ _ . . - , . . . , - . - . , . - - , , , , . ,.- ., ,,,, - - , , . - _ , . . ~ .

5 AVER AGE DAILY ONIT PCtf R LivgL DOCKET No. 50 m i

UNIT St. Lucie Unit 1 DATE December 12, 1986 i

COMPLETED BY N.W. Grant TELErilONE (305)694-4432 h00 NTH November, 1986 DAY AVERACE DAILY POWER LEVEL IMWefdeo 11/ 1/86 843 11/ 2/86 843 11/ 3/86 845 11/ 4/86 843 11/ 5/86 844 11/ 6/86 841 11/ 7/06 839 11/ 8/86 838 11/ 9/86 810 11/10/86 812 l

l 11/11/86 849 I 11/12/86 849 l 11/13/06 816 11/14/06 826 11/15/86 847 i 11/16/86 848 11/17/86 848 11/18/86 819 11/19/86 818 11/20/86 846 11/21/86 848 11/22/86 848 11/23/86, 848 11/24/96 848 11/25/86 847 11/26/86 843 11/27/86 847 11/28/86 844 11/29/86 842 11/30/86 842 i

~

~.- OPERATING DATA REPORT DOCKET NO 50 - 335 i DATE 12/11/86 COMPLETED BY N. W. GRANT TELEPHONE 305/694/4432 OPERATING STATUS l' 1. UNIT NAHE! ST. LUCIE UNIT 1

2. REPORTING PERIOD NOVEMBER 1986 3.' LICENSED THERMAL POWER (MWT): _ _ _ _ _ _ _ _ _ _ _ _ _ . . 2700 I 4. NAMEPLATE RATING (GROSS MWE): ______________ 850
5. DESIGN ELECTRICAL RATING (NET MWE): ________ 830
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): ___ 872
7. MAXIMUM DEPENDABLE CAPACITY (NET MWE): _____ 839
8. IF CHANGES OCCUS IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7)

'SINCE LAST REPORT, GIVE REASONS: ________________________________________

[

9. POWER LEVEL TO WHICH RESTRICTED, I ANY (NET MWE)________________________

__________________________________F s'ie. REASONS FOR RESTRICTIONS, IF ANY: _______________________________________

I MONTHLY -YTD- CUMULAT'IVE

11. HOURS IN REPORT PERIOD
_________________ 720 8016- 87168.0
12. NUMBER OF HOURS REACTOR WAS CRITICAL _____ 720.0 7672.7 63828.7 l

i 13. REACTOR RESERVE SHUTDOWN HOURS __________ 0.0 0.0 205 3

14. HOURS GENERATOR ON-LINE _________________ 720.0 7609.6 63411.7 i 15. UNIT RESERVE SHUTDOWN HOURS _____________ 0 0 39.3
16. GROSS THERMAL ENERGY GENERATED (MWH) ____ 1933003 20333077 161225344
17. GROSS ELECTRICAL ENERGY GERERATED (MWH) _ 636510 6746940 52823445
18. NET ELECTRICAL ENERGY GENERATED (MWH) ___ 604271 6423606 49857398
19. UNIT SERVICE FACTOR _____________________ 100.0 94.9 72.7
20. UNIT AVAILABILITY FACTOR ________________ 100.0 , 94.9 7'28
21. CAPACITY FACTOR (USING MDC NET) _________ 100.0 95.5 71.6 i 22. CAPACITY FACTOR (USING DER NET) _________ 101.1 96.5 70.1 i 23. UNIT FORCED OUTAGE RATE _________________ 0 1.2 4.0
24. SHUTDOWNS SCHEDULED OVER NEXT 4 MONTHS :

REFUELING 2/14/87, 63 DAYS _____________________________________________

! 25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: ________

j i

l

DOCKET NO. 50-335 UNIT SHUTDOWNS AND POWER REDUCTIONS UNITNAME St I in-ia Ifni t #1 DATE December 12, 1986 i COWLETED BY N. W. Grant REPORTMONTH November.1986 1ELEPHONE (305) 644-4437

- E c

,  !? 3 j $5 Licensee $g **. Cause & Corrective No Date i 3g @ .3 s 5 Event g'2 E0 Action to

$~ $ jgg Report a mO g Prevent Recurrence 6

Unit #1 had no shutdowns or significant power reductions.

l i

j l

I

j I 2 3 4 F Forced Reason
Method: Exhibit G - Instructions i 5 Sched uled A Lyuipment Failure (Explam) 1-Manual for Preparation of Data B-Maintenance or Test 2-Manual Scram. Entry Sheets for Licensee 4

C. Refueling 3-Automatic Scram. Event Report (LER) File (NUREG-D-Regulatory Restriction  %-Other (Explain 1 0161) 1: Operator Training & Ucense Examination t F- Ad numst rative p ,

5 G Operatomal I irnr ( F splain t c Ao4. 44 eve ..,# Exhibit I - Same Source I (9/77) II4hher iL splain)

') SUZH4ARY OF OPERATING EXPEILTENCE DOCKET NO. 50-335 UNIT St. Lucie Unit 1 DATE December 12. 1986 COMPLETED BY N. W. Grant TELEPHONE f305) 694-4432 REPORT HONTH November 1986 Unit #1 operated at essentially full power and had no " unit shutdowns or significant power reductions".

In accordance with requirements of Technical Specifications 6.9.1.6, there were no challenges to PORV or safety valves during the report month.

{

l l

l l

l L

AVERAGE DAILY UNIT POWf t tsvfL DOCKET NO. 50-:M9 UNIT St. I ncio finit 2 DATE December 12, 1986 COMPLETED BY N.W. Grant TELEPHONg (305)604-4432 MONTH November, 1986 DAY AVERAGE DAILY POWER LEVEL (MWe Net) 11/ 1/86 860 11/ 2/86 859 11/ 3/86 838 11/ 4/86 801 11/ 5/86 850 11/ 6/86 862 11/ 7/86 862 11/ 8/86 862 11/ 9/86 862 11/10/86 862 l 11/11/86 862 11/12/86 862 11/13/86 862 11/14/86 860 11/15/06 062 11/16/86 861 11/17/86 861 11/18/86 861 11/19/86 860 11/20/86 860 11/21/86 860 11/22/86 861

, 11/23/86' 860 11/24/86 860 11/25/86 859 11/26/86 860 l 11/27/86 860 11/28/86 860 l 11/29/86 858 11/30/06 837

't OPERATING DATA REPORT DOCKET NO 50 - 389 DATE 12/11/86 COMPLETED BY N. W. GRANT TELEPHONE 305/694/4432 OPERATING STATUS

1. UNIT NAME: ST. LUCIE UNIT 2
2. REPORTING PERIOD NOVEMBER 1986
3. LICENSED THERMAL POWER (MWT): ____-_________ 2700
4. NAMEPLATE RATING (GROSS MWE): --__-_______-- 850
5. DESIGN ELECTRICAL RATING (NET MWE): _______- 830
6. MAXIMUM DEPENDABLE CAPACITY (GROSS MWE): -__ 882
7. MAXIMUM DEPENDABLE CAPACITY (NET MWE): _____ 839
8. IF CHANGES OCCUS IN CAPACITY RATINGS (ITEMS NUMBER 3 THROUGH 7)

SINCE LAST REPORT, GIVE REASONS: ___-____-__-_____-_-___-__-_____________

9. POWER LEVEL TO WHICH RESTRICTED, IF ANY (NET MWE)__-_-________ _ _-___-____
10. REASONS FOR RESTRICTIONS, IF ANY: _____-__-______-____-__________________

MONTHLY -YTD- CUMULATIVE

11. HOURS IN REPORT PERIOD: ________-__-_____ 720 8016 29065.0
12. NUMBER OF HOURS REACTOR WAS CRITICAL _____ 720.0 6582.7 24631.6
13. REACTOR RESERVE SHUTDOWN HOURS _______-__ 0.0 0.0 0.0
14. HOURS GENERATOR ON-LINE _--___-__________ 720.0 6511.5 24083.8
15. UNIT RESERVE SHUTDOWN HOURS __--_-_-_____ 0 0 0
16. GROSS THERMAL ENERGY GENERATED (MWH) ____ 1936676 17387313 62033846
17. GROSS ELECTRICAL ENERGY GERERATED (MWH) - 649530 5814200 20720880

, 18. NET ELECTRICAL ENERGY GENERATED (MWH) -__ 616873 5507096 19578139 l 19. UNIT SERVICE FACTOR ____--________-______ 100.0 81.2 82.9 l 20. UNIT AVAILABILITY FACTOR ---_________-___ 100.0 81.2 82.9

21. CAPACITY FACTOR (USING MDC NET) ___--____ 102.1 81.9 82.9
22. CAPACITY FACTOR (USING DER NET) _____--__ 103.2 82.8 82.4 l

l 23. UNIT FORCED OUTAGE RATE _________________ 0 1.1 8.4

24. SHUTDOWNS SCHEDULED OVER NEXT 6 MONTHS :
25. IF SHUT DOWN AT END OF REPORT PERIOD, ESTIMATED DATE OF STARTUP: _-______

1

(

l l

l

-l UNIT SHUTDOWNS AND POWER REDUCTIONS DOCKET NO. 50-389 UNITNAME St. Lucie Unit #2 DATE December 12, 1986 COMPLETED BY N. W. Grant REPORT MONDI November. 1986 TELEPHONE (3050 644-4439 i

. "E -

= re a ,

. 1 : E y3 -c :4 Licensee g *, Cause & Corrective N" Date i 35 4 .255 Event ET 3 Action to

$3 E j di j Report = <N 0 jO Prevent Recurrence 6

Unit #2 had no shutdowns or significant Power reductions.

I I 2 3 4 f Forced Reason: Method: Exhibit G Instructions S Scheduled A-Lquipment Failure (Explain) 1 Manual for Preparation of Data B-Maintenance or Test 2-Manual Scram. Entry Sheets for Licensee C-Refueling 3-Automatic Scram. Event ReporI(LER) File (NUREG.

D-Regulatory Restriction @-Other (Explain) 0161) 1 -Operator Training & License Examination F- Ad nu nist ra t ive 5 G Oper4tional i ror if splam) s /.o ao 44 eve ..et Exlubit I Same Source 49/77) Il-Ot her i E splain )

SU21 MARY OF OPERATING EXPERIENCE DOCKET NO. g0_389 UNIT St. Lucie Unit 2 DATE Decomhpr 12. 1986 COMPLETED BY N. W. Grant TELEPHONE (305) 694-4432 l

REPORT MONTH November. 1986 Unit #2 operated at essentially full power and had no " unit shutdowns or significant power reductions".

In accordance with requirements of Techni. cal Specifications 6.9.1.6, there were no challenges to PORV or safety valves during the report month.

l l

l l

i

~ -

g-

_' P. O. BOX 14000. JUNO BEACH, FL 33408-0420 a .

~

j)Q DECEMBER 12 1986 L-86-506 Director, Office of Resource Management U. S. Nuclear Regulatory Commission Washington, D. C. 20555 Re: Turkey Point Units 3 and 4 Docket Nos. 50-250 and 50-251 St. Lucie Units I an-12 Docket Nos. 50-335 and 50-389 Monthly Operatina Report

Dear Sir:

Attached are the November 1986 Operating Status Reports and Operating Summary Reports for Turkey Point Unit Nos. 3 and 4 and St. Lucie Unit Nos. I and 2.

Very truly yours, Ach,/

C.O.W y/

Group V President Nuclear nergy COW /NWG/gp Attachment cc: Dr. J. Nelson Grace, USNRC, Region ll Harold F. Reis, Esquire i

/t/

4 NWGI/005/l PEOPLE. . SERVING PEOPLE

-.._. .--_ -