Responds to IE Bulletin 80-13, Cracking in Core Spray Spargers. Visual Exam Performed Using closed-circuit Tv Revealed No Relevant Indications of Cracking
ML17279A282
Person / Time
Site: Columbia Energy Northwest icon.png
Issue date: 05/20/1987
From: Sorensen G
WASHINGTON PUBLIC POWER SUPPLY SYSTEM
To: Martin J
NRC OFFICE OF INSPECTION & ENFORCEMENT (IE REGION V)
References
GO2-87-173, IEB-80-13, NUDOCS 8706010326
Download: ML17279A282 (2)


Text

REQULATO 'INFORMATION DISTRIBUTION 'STE!'! (R IDS)

ACCESSION NGR: 870h010326 DOC. DATE: 87/05/20 NOTARIZED: NQ DOCKET FACIL: 50-397 WPPSS Nuclear ProJect> U;>it 2> Washington Public Po> e 05000397 AUTH. NAl"IE AUTHOR AFFILIATION SQRENSEN, 0. C. Washington Publi c Paver Supply System RECIP. NAI'!E RECIPIENT AFFILIATION NARTIN> J. B. Region 5> Office of Director

SUBJECT:

Respondss to IE Bulletin 80-1:3> "Cracking in Core Spray Spargers. " Visual examination per formed using closed-circuit TV revealed no relevant indications of cracking.

DISTRIBUTION CODE: IE11D COPIES RECEIVED: LTR TITLE: Bulletin Response (50 DKT) g ENCL Q SIZE:

NOTES:

RECIPIENT 'CQP I ES REC IP I ENT COPIES ID CODE/NA!'!E LTTR EN> L ID CODE/NAi!E LTTR EKCL r Dr) LA PD5 PD SA!"IWQRTH> R INTERNAL AEOD/DOA AEOD/DSP AEOD/DSP/TPAB NRR/DEST/ADE NRR/DEBT/ADS NRR/DOEA/EAB NRR/DOE*/QCB N /EPB NRR/PLEAS/ ILRB REG FILE 02 RQN5 FILE 01 EXTERNAL: LPDR NRC PDR NSIC TOTAL NUNBER OF COPIES REQUIRED: LTl R 17 ENCL

Washington Public Power Supply System 3000 George Washington Way P.O. Box 988 Richland, Washington 99352-09II8 (509)372-5000 May 20, 1987 G02-87-173 Docket No. 50-397 Mr. J. B. Hartin Regional Administrator U.S. Nuclear Regulatory Commission Region Y 1450 Maria Lane, Suite 210 Walnut Creek, CA 94596 Dear Mr. Martin

Subject:

NUCLEAR PLANT NO. 2 CORE SPRAY SPARGERS

Reference:

IE Bulletin 80-13 "Cracking in Core Spray Spargers",

dated May 12, 1980 During the April 1987 refueling outage, the Supply System oerformed a visual examination of the WNP-2 Core Spray Spargers per the requirements of the referenced IE Bul.letin. No relevant indications were observed in the areas examined. This letter satisfies the 30 day reporting require-ment in the referenced IE Bulletin.

The examination was performed remotely using an underwater closed circuit TV (CCTV) system capable of resolving a 0.001 inch diameter wire. The examiners were certified to Level II VT-1 under the Supply System's gA program. At the beginning and end of the examination and at four (4) hour intervals during the examinations, the CCTY system was demonstrated to be capable of resolving a 0.001 inch diameter wire in-situ.

If you have any questions or desire further information on this examina-tion, please contact Mr. P. L. Powell, Manager, WNP-2 Licensing.

Ver truly y rs,

6. C. rensen, Managel Regul ory Programs DPR/bk cc: RB Samworth - NRC NS Reynolds - BCPItR NRC Site Inspector Document Control Desk - NRC 8706010326 870520 PDR ADOCN 05000397 PDR